97
MAN0530 Issue 10 - 11/09
Searchline Excel
2104M0506
Show Config
This option displays the configuration parameters the user can set in the same way as for the
Show Gas
option. The configurable settings a
nd values are shown in the following table:
Configuration Parameters
Display Text
Min Value Max Value Step Size
Default Values
Protocol Address
Digital
Address
0
255
1
0
Time to Block
Block
Warn
Time
5s
600s
5s
30
Time to Fault
Block
Fault
Time
0s
600s
5s
120
Max Response
Maximum
T90
1s
60s
1s
60
Analogue Style
Analogue
Mode
Alarm or Continuous
C
Inhibit Current
Inhibit
mA
0mA
3mA
0.05mA
2.0
Block Current
Blocked
mA
0mA
4mA
0.05mA
2.5
Low Signal Current
Low
Signal
mA
0mA
4mA
0.05mA
3.0
Low Signal Level
Low
Signal
%
0%
90%
1%
33%
Alarm Threshold
Alarm
Threshold
10%
100%
1%
20%
Report fault due to blockage
RPRT
Blocked
Fault
Enable or Disable
E
show install
This option displays the installation configuration parameters in the same way as for the
Show Gas
option. The configurable settings and values are shown below:
Installation Configuration
Display Text
Description
Parameters
System Type
System
Type
Short Range
Medium Range
Long Range
Duct Mount
Path Length
Path
Length
5m min.
200m max.
1m step
0.5m min.
5m max.
0.1m step
A.5.6 Chg Mode
This menu option toggles the operating mode of the interrogator between
Excel
,
Optima
and
Optima Plus
to match the gas detector it is attached to. When invoked the mode is displayed
in the identification banner (the same as the one displayed when the unit is switched on) for
three seconds as follows:
Z - SHC1 aaaaaa
Interrogator 4V0
where:
aaaaaa
The type of gas detector that the interrogator is currently set to, i.e.
Excel
,
OPTIMA
or
OPTIMA PLUS
.
APPENDIX A - HANDHELD INTERROGATOR