Honeywell S9361A207 Series Installation Instructions Manual Download Page 14

S9361A207X INTEGRATED BOILER CONTROLLERS

69-2751—05

14

TROUBLESHOOTING

IMPORTANT

1. The following service procedures are provided 

as a general guide. Follow appliance manufac-
turer’s service instructions if available.

2. On lockout and retry models, meter readings 

between gas control and ignition module must 
be taken within the trial for ignition period. 
Once the ignition module shuts off, lockout 
models must be reset through the key buttons 
and display. On retry models, wait for retry or 
reset at the thermostat.

3. If any component does not function properly, 

make sure it is correctly installed and wired 
before replacing it.

4. The ignition module cannot be repaired. If it 

malfunctions, it must be replaced.

5. Only trained, experienced service technicians 

should service ignition systems.

Perform the checkout as the first step in 
troubleshooting. Then check the appropriate 
troubleshooting guide and the schematic diagram to 
pinpoint the cause of the problem. If troubleshooting 
indicates an ignition problem, see Ignition System 
Checks below to isolate and correct the problem.

Following troubleshooting, perform the checkout 
procedure again to be sure system is operating 
normally.

Intermittent Pilot

Ignition System Checks

STEP 1: Check ignition cable.

Make sure:

• Ignition cable does not run in contact with any 

metal surfaces.

• Ignition cable is no more than 36 in. [0.9 m] long.
• Connections to the ignition module and to the 

igniter or igniter-sensor are clean and tight.

• Ignition cable provides good electrical continuity.
STEP 2: Check ignition system grounding. Nuisance 
shutdowns are often caused by a poor or erratic 
ground.

• A common ground, usually supplied by the pilot 

burner bracket, is required for the module and the 
pilot burner/igniter sensor.

Check for good metal-to-metal contact 
between the pilot burner bracket and the main 
burner.

Check the ground lead from the 
GND(BURNER) terminal on the module to the 
pilot burner. Make sure connections are clean 
and tight. If the wire is damaged or deterio-
rated, replace it with No. 14-18 gauge, mois-
ture-resistant, thermoplastic insulated wire 
with 105° C [221° F] minimum rating.
—Check the ceramic flame rod insulator for 

cracks or evidence of exposure to extreme 
heat, which can permit leakage to ground. 
Replace pilot burner/igniter-sensor and 
provide shield if necessary.

—If flame rod or bracket are bent out of posi-

tion, restore to correct position.

STEP 3: Check spark ignition circuit.

• Disconnect the ignition cable at the SPARK 

terminal on the module.

WARNING

The ignition circuit generates over 10,000 
volts and electrical shock can result.

Energize the module and listen for the audible 
sparking noise. When operating normally, there 
should be a buzzing noise that turns on and off twice 
per second for a duration of 1–7 seconds, depending 
on the model.

STEP 4: Check pilot and main burner lightoff.

• Set the system to call for heat by turning the 

thermostat above room temperature.

• Watch the pilot burner during the ignition 

sequence. See if:

Ignition spark continues after the pilot is lit.

The pilot lights and the spark stops, but main 
burner does not light.

• If so, ensure adequate flame current as follows.

Turn off furnace at circuit breaker or fuse box.

Clean the flame rod with emery cloth.

Make sure electrical connections are clean and 
tight. Replace damaged wire with moisture-
resistant No. 18 wire rated for continuous duty 
up to 105° C [221° F].

Check for cracked ceramic insulator, which can 
cause short to ground, and replace igniter-sen-
sor if necessary.

At the gas valve, disconnect main valve wire 
from the MV terminal.

Turn on power and set thermostat to call for 
heat. The pilot should light but the main burner 
will remain off because the main valve actuator 
is disconnected.

Check the pilot flame. Make sure it is blue, 
steady and envelops 3/8 to 1/2 in. [10 to 13 
mm] of the flame rod. See Fig. 9 for possible 
flame problems and their causes.

If necessary, adjust pilot flame by turning the 
pilot adjustment screw on the gas control 
clockwise to decrease or counterclockwise to 
increase pilot flame. Following adjustment, 
always replace pilot adjustment cover screw 
and tighten firmly to assure proper gas control 
operation.

Set temperature below room setpoint to end 
call for heat.

• Recheck ignition sequence as follows.

Reconnect main valve wire.

Adjust thermostat above room temperature.

Watch ignition sequence at burner.

If spark still doesn’t stop after pilot lights, 
replace module.

If main burner doesn’t light or if main burner 
lights but system locks out, check module, 
ground wire and gas control as described in 
appropriate troubleshooting chart.

Troubleshooting Error Codes

The integrated boiler control uses advanced 
diagnostic capability to assist in troubleshooting error 
conditions. Table 9 shows the codes that could arise 
on the remote or integrated display during a fault. 
Suggestions are provided in Table 5 for servicing these 
potential errors.

Summary of Contents for S9361A207 Series

Page 1: ...culator and Domestic Hot Water Circulator output Enabled with EnviraCOM communication capability to support remote monitoring and diagnostics Limit rated Temperature Sensing Probe One Sensor Model SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore an individual unit may not match the listed specifications exactly Also this...

Page 2: ...c 0 5 to 0 6 PF Ambient Ratings Humidity 0 to 95 percent relative humidity noncondensing Operating Ambient Temperature 4 F to 150 F Shipping Ambient Temperature 40 F to 175 F Flame Monitoring May vary by model Flame Establishing Period FEP Maximum 2 sec onds Flame Failure Response Time FFRT Maximum 2 5 seconds 1 µA Flame Lost Threshold 0 23 µA Accessories Ordered Separately W8735Y1000 Wireless Out...

Page 3: ...sary shield the controls to protect them from splashing water A NEMA 4 enclosure is recommended High Humidity or Dripping Water Over time dripping water or high ambient humidity can create unwanted electrical paths on the module circuit board causing the module to fail Never install an appliance where water can drip on the controls In addition high ambient humidity can cause the control to corrode...

Page 4: ...ecially so in commercial agricultural and industrial applications because 1 In such applications particularly commercial the equipment can operate 100 000 to 200 000 cycles per year Such heavy cycling can wear out the gas control in one to two years A normal boiler application for which the controls were intended typically operate fewer than 10 000 cycles per year 2 Exposure to water dirt chemical...

Page 5: ...EGRATED BOILER CONTROLLERS 5 69 2751 05 Fig 2 Recommended slot hole pattern in appliance in mm Fig 3 Align module with slots in manufacturer s control box 100 M24198 16 16 55 4 99 5 4 WATER HEATER CONTROL BOX M24229 ...

Page 6: ...ic standoff insulators as required 1 Connect one end of the cable to the male quick connect SPARK terminal on the module 2 Connect the other end of the cable to the igniter or igniter sensor stud on the pilot burner igniter sensor Connect Vent Damper Vent Damper Models A vent damper can be used with modules provided with a vent damper plug connector The Molex plug provided simplifies wiring connec...

Page 7: ...etail Fig 4 Spark to Pilot Ignition Wiring S936X M533506 C R D DHW CIRCULATOR ENVIRACOM SYSTEM CIRCULATOR L1 GND L2 DAMPER OPTIONAL INDUCER OPTIONAL 24VAC TRANSFORMER SENSOR DHW T STAT LIMIT SWITCH PRESSURE SWITCH PV PV MV GAS CONTROL SPARK IGNITER FLAME SENSE MV ...

Page 8: ...n running mode flame signal must be present Postpurge 9 System is purging at the end of a call for heat Inter purge Retry Recycle Delay 10 If the control loses flame signal during state 7 or 8 it will recycle through the 30 seconds purge time and last 2secs part of prepurge time Re Start delay due to flame failure Wait for pressure switch to open failed closed 11 The inducer is still off and the p...

Page 9: ...a three digit number and the corresponding degree designator See Display Readout Integrated Boiler Control One Rod Combined Ignitor and Sensor Model Displays See Table 6 8 for the IBC display screens Wait for vent damper to open 18 Damper actuator is energized and the system waits for damper to close Wait for vent damper to close 19 Damper actuator is de energize and the system waits for damper to...

Page 10: ...reen 3rd Screen StA State number Status bt Sensed temperature F or C Boiler Temperature SP Operating Setpoint F or C Operating Setpoint the lowest of the IQ Outdoor air reset EnviraCOM message Desired Boiler Setpoint high limit setpoint and setpoint from the remote user interface device HL_ High Limit F or C Adjust High Limit Setting HdF High Limit Differential F or C Adjust High Limit Differentia...

Page 11: ...mpound Honeywell part no 107408 to fill the space between the bulb and the well to improve heat transfer characteristics optional Make sure the sensor is held firmly in the well WIRING IMPORTANT For maximum trouble free operation run the sensor leadwires separately from any other current carrying wires All wiring must comply with local codes and ordinances Disconnect power supply before beginning ...

Page 12: ...e heating cycle returns to idle and waits for the temperature to drop again The circulator is turned on throughout the Call for Heat See Fig 7 for a graphical representation of a simple control cycle Note that the setpoint differential may vary based on OS number High Limit Controller All models include a 3 wire temperature sensor interface Boiler temperature which is utilized for High Limit funct...

Page 13: ...H OR CALL FOR HEAT LOST SWITCH OPEN SWITCH CLOSE SWITCH OPEN FLAME DEB ON FLAME DEB OFF TIME OUT TIME OUT OR MANUAL RESET LIMIT SWITCH OPEN TIME OUT FLAME SENSED FLAME PROVED TIME OUT WATER TEMPERATURE HIGH OR THERMOSTAT CALL FOR HEAT LOST RETRY DELAY TIME OUT A TIME OUT RECYCLE DELAY DAMPER PRESSURE SWITCH OPEN CHECK FLAME POST TRIAL FLAME DEB ON FLAME DEB OFF FLAME LOST A TIME OUT A TIME OUT TIM...

Page 14: ...out of posi tion restore to correct position STEP 3 Check spark ignition circuit Disconnect the ignition cable at the SPARK terminal on the module WARNING The ignition circuit generates over 10 000 volts and electrical shock can result Energize the module and listen for the audible sparking noise When operating normally there should be a buzzing noise that turns on and off twice per second for a d...

Page 15: ...s duringA D conversion Err 35 Duplicate Zone alarm was received from zone panel Err 55 Atmospheric Damper End Switch failed to close end switch contacts stuck open Err 56 Atmospheric Damper End Switch failed to open end switch contacts stuck closed Err 57 Flame Rod shorted to burner ground Err 58 AC line frequency error signal is too noisy or frequency is incorrect Err 59 Line voltage error voltag...

Page 16: ...risk Tamper evident tape has been placed on the bulk pack box to indicate if the package was opened Do not accept or use product received with damaged or missing tape Reverse engineering or modification of device is not permitted and may pose a safety risk LAZY YELLOW FLAME WAVING BLUE FLAME NOISY LIFTING BLOWING FLAME HARD SHARP FLAME SMALL BLUE FLAME CHECK FOR LACK OF GAS FROM CLOGGED ORIFICE FI...

Reviews: