Honeywell S9360A Manual Download Page 3

S9360A, S9361A, S9380A, S9381A INTEGRATED BOILER CONTROLLERS

3

66-1203—05

14,000,485-016 1/4 in. (6.35 mm) diameter, 1-1/4 in.

(31.75 mm) length glass cartridge Fuse, 1 A, 

Slow-Blow.

120650 Heat Conductive Compound. 

Ignition Cables:

32004766-012—36-in. standard ignition cable (one end 

with 90° boot, and other end with 1/4-in. quick con-

nect).

Use cable types recommended in Table 3.

Table 3. Recommended Ignition Cables.

Transformer Requirement:

Add current ratings of module, pilot valve, main valve, vent 

damper and any other components of the control sys-

tem to determine transformer size requirement.

The AT150B1260—commonly used 50 VA transformer.

Approvals:

Varies with control model.

ANSI Z21.20 Automatic Gas Ignition Systems and 

Components.

ANSI Z21.23 Gas Appliance Thermostats.

EN298: Automatic Gas Burner Control Systems

ANSI Z21.87: Automatic Gas Shutoff Devices for Hot 

Water Supply Systems.

UL353 Limit Controls.

INSTALLATION

Automatic Ignition Control domestic and commercial 

boiler systems are used on a wide variety of equipment. 

Some of these applications may make heavy demands on 

the controls, either because of frequent cycling, or 

because of moisture, corrosive chemicals, dust or 

excessive heat in the environment. In these situations, 

special steps may be required to prevent nuisance 

shutdowns and premature control failures. These 

applications require Honeywell Engineering review; 

contact your Honeywell Sales Representative for 

assistance.

Frequent Cycling

These controls are designed for use on domestic and 

commercial boiler systems that typically cycle less than 

10,000 cycles per year. In an application with significantly 

greater cycling rates, we recommend monthly checkout 

because the controls may wear out more quickly.

Water or Steam Cleaning

Once a module or gas control has been wet, it may 

operate unreliably and must be replaced. If the appliance 

is likely to be cleaned with water or steam, the controls 

and associated wiring should be covered so that water or 

steam cannot reach them. The controls should be high 

enough above the bottom of the cabinet so they will not be 

subjected to flooding or splashing during normal cleaning 

procedures. If necessary, shield the controls to protect 

them from splashing water. A NEMA 4 enclosure is 

recommended.

High Humidity or Dripping Water

Over time, dripping water or high ambient humidity can 

create unwanted electrical paths on the module circuit 

board, causing the module to fail. 

Never

 install an 

appliance where water can drip on the controls.

In addition, high ambient humidity can cause the control 

to corrode and finally fail.

Where the appliance may be installed in a humid 

atmosphere, make sure air circulation around the module 

and gas control is adequate to prevent condensation. It is 

also important to regularly check out the system. A NEMA 

4 enclosure may be needed.

Corrosive Chemicals

Corrosive chemicals can also attack the module and gas 

control and eventually cause a failure. Where chemicals 

may be used routinely for cleaning, make sure the 

cleaning solution cannot reach the controls. Where 

chemicals are likely to be suspended in the air, as in some 

industrial and agricultural applications, protect the module 

from exposure with a NEMA 4 enclosure.

Dust or Grease Accumulation

Heavy accumulation of dust or grease may cause the 

controls to malfunction. Where dust or grease may be a 

problem, provide covers for the module and gas control 

that limit environmental contamination. A NEMA 4 

enclosure is recommended for the module.

Heat

The controls can be damaged by excessively high 

temperatures. Make sure the maximum ambient 

temperature at the control locations will not exceed the 

rating of the control. If the appliance normally operates at 

very high temperatures, insulation, shielding, and air 

circulation may be necessary to protect the controls. 

Proper insulation or shielding should b provided by the 

appliance manufacturer; make sure adequate air 

circulation is maintained when the appliance is installed.

Table 1. Wells for Controller.

Part 

Number

Spud Size

in. (mm)

Insertion 

in. (mm)

Insulation 

in. (mm)

123869A 1/2 (12.7) NPT

3 (76.2)

1-1/2 (38.1)

123870A 3/4 (19.05) NPT 3 (76.2)

1-1/2 (38.1)

Table 2. Sensors for Controller.

Part Number

Length in. 

(mm)

Application

50001464-001

12 (304.8) Well-mounted controls

50001464-003

24 (609.6) Flush-mounted controls

50001464-004

36 (914.4)

50001464-005

48 (1219.2)

Cable Type

Voltage 

Rating (rms)

Temperature Rating

°C

°F

UL Style 3217 10,000

150

302

UL Style 3257 10,000

250

484

Summary of Contents for S9360A

Page 1: ...pe two rod separate ignitor and sensor one rod combined ignitor and sensor SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore an individual unit may not match the listed specifications exactly Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be exp...

Page 2: ...50 F Shipping Ambient Temperature 40 F to 175 F Flame Monitoring May vary by model Flame Establishing Period FEP Maximum 2 seconds Flame Failure Response Time FFRT Maximum 2 seconds 1 μA Flame Stabilization Time 4 seconds Time from ignit ing the main burner and detecting loss of flame the flame current is allowed to be under the flame lost threshold for this time while waiting for burner to stabil...

Page 3: ...l cleaning procedures If necessary shield the controls to protect them from splashing water A NEMA 4 enclosure is recommended High Humidity or Dripping Water Over time dripping water or high ambient humidity can create unwanted electrical paths on the module circuit board causing the module to fail Never install an appliance where water can drip on the controls In addition high ambient humidity ca...

Page 4: ...n but especially so in commercial agricultural and industrial applications because 1 In such applications particularly commercial the equipment can operate 100 000 to 200 000 cycles per year Such heavy cycling can wear out the gas control in one to two years A normal boiler applica tion for which the controls were intended typically operate fewer than 10 000 cycles per year 2 Exposure to water dir...

Page 5: ...9381A INTEGRATED BOILER CONTROLLERS 5 66 1203 05 Fig 2 Recommended slot hole pattern in appliance in mm Fig 3 Align module with slots in manufacturer s control box 100 M24198 16 16 55 4 99 5 4 WATER HEATER CONTROL BOX M24229 ...

Page 6: ...fit one end the module end with 1 4 in connector receptacle and the other with a connector to match the pilot assembly Protect both ends with insulated boots NOTE Cable length must be 36 in 0 9 m or less The cable must not be in continuous contact with a metal surface or spark voltage will be greatly reduced Use ceramic or plastic standoff insulators as required 1 Connect one end of the cable to t...

Page 7: ...61A2095 has a 1 minute retry delay and a 5 minute recycle delay Other lockouts will automatically clear after 1 hour Model Ignition Type Draft Type No of Ignition Trials Igniter Sensor Type Automatic Restart Timee Ignition Activation Perioda Prepurge Timingb Postpurge Timingb S9360A S9361A Intermittent Pilot Spark Induced 6 Separate Combinedc 1 hour N A 30 15 S9360A S9361A Intermittent Pilot Spark...

Page 8: ...ark to Pilot Ignition Wiring S936X 2 rod separate ignitor and sensor M33682 CIRCULATOR SPARK IGNITER FLAME SENSE INDUCER L1 L2 GND GND 24 VAC TRANSFORMER DAMPER ENVIRACOM DIAGNOSTIC GAS CONTROL MV PV PV MV PRESSURE SWITCH LIMIT SWITCH T STAT C R D ENVIRACOM SENSOR OPTIONAL BASED ON MODEL 1 1 1 ...

Page 9: ... 9 66 1203 05 Fig 5 Direct Spark Ignition DSI Wiring S938X 1 rod combined ignitor and sensor C R D ENVIRACOM SYSTEM CIRCULATOR L1 GND L2 INDUCER 24VAC TRANSFORMER SENSOR M33505 T STAT LIMIT SWITCH PRESSURE SWITCH GAS CONTROL MV PV MV SPARK IGNITER FLAME SENSE ...

Page 10: ...ig 6 Spark to Pilot Ignition S936X 1 rod combined ignitor and sensor M33830 C R D ENVIRACOM SYSTEM CIRCULATOR L1 GND L2 DAMPER INDUCER 24VAC TRANSFORMER SENSOR T STAT LIMIT SWITCH PRESSURE SWITCH PV PV MV GAS CONTROL MV OPTIONAL BASED ON MODEL 1 1 1 SPARK IGNITER FLAME SENSE ...

Page 11: ...System is in running mode flame signal must be present Postpurge 9 System is purging at the end of a call for heat Inter purge Retry Recycle Delay 10 If the control loses flame signal during state 7 or 8 it will recycle through the 30 seconds purge time and last 2 seconds part of prepurge time Re Start delay due to flame failure Wait for pressure switch to open failed closed 11 The inducer is stil...

Page 12: ... DOWN button until the parameter has reached the desired value After 60 seconds without any button inputs the control will automatically return to the READ mode Display In the RUN mode status items and parameters are viewable To read settings press and release the I key to find the parameter of interest For example press and release I until setpoint sp is displayed followed by a three digit number...

Page 13: ...ponse Use heat conductive compound Honeywell part no 107408 to fill the space between the bulb and the well to improve heat transfer characteristics optional Make sure the sensor is held firmly in the well WIRING IMPORTANT For maximum trouble free operation run the sensor leadwires separately from any other cur rent carrying wires All wiring must comply with local codes and ordinances Disconnect p...

Page 14: ...this point the burner is de activated the ignition module completes the heating cycle returns to idle and waits for the temperature to drop again The circulator is turned on throughout the Call for Heat See Fig 10 for a graphical representation of a simple control cycle Note that the setpoint differential may vary based on OS number High Limit Controller All models include a 3 wire temperature sen...

Page 15: ...CK FLAME PRE TRIAL SOFT LOCKOUT PROVE FLAME STOP SPARKING FLAME STABILIZATION TURN MAIN VALVE ON RUN POSTPURGE WATER TEMPERATURE LOW AND THERMOSTAT ACTIVE BIAS DONE WATER TEMP HIGH OR CALL FOR HEAT LOST SWITCH OPEN SWITCH CLOSE SWITCH OPEN FLAME DEB ON FLAME DEB OFF TIME OUT TIME OUT OR MANUAL RESET LIMIT SWITCH OPEN TIME OUT FLAME SENSED DSI TIME OUT FLAME PROVED TIME OUT WATER TEMPERATURE HIGH O...

Page 16: ...re bent out of position restore to correct position STEP 3 Check spark ignition circuit Disconnect the ignition cable at the SPARK terminal on the module WARNING The ignition circuit generates over 10 000 volts and electrical shock can result Energize the module and listen for the audible sparking noise When operating normally there should be a buzzing noise that turns on and off twice per second ...

Page 17: ...or gain too many failures during A D conversion Atmospheric Damper End Switch failed to close end switch contacts stuck open Atmospheric Damper End Switch failed to open end switch contacts stuck closed Flame Rod shorted to burner ground AC line frequency error signal is too noisy or frequency is incorrect Line voltage error voltage out of spec high or low Thermostat input higher than threshold Li...

Page 18: ... ORIFICE FILTER CLOGGED PILOT FILTER LOW GAS SUPPLY PRESSURE PILOT ADJUSTMENT AT MINIMUM CHECK FOR LACK OF AIR FROM DIRTY ORIFICE DIRTY LINT SCREEN IF USED DIRTY PRIMARY AIR OPENING IF THERE IS ONE PILOT ADJUSTMENT AT MINIMUM CHECK FOR EXCESSIVE DRAFT AT PILOT LOCATION RECIRCULATING PRODUCTS OF COMBUSTION CHECK FOR HIGH GAS PRESSURE THIS FLAME IS CHARACTERISTIC OF MANUFACTURED GAS CHECK FOR HIGH G...

Page 19: ...S9360A S9361A S9380A S9381A INTEGRATED BOILER CONTROLLERS 19 66 1203 05 ...

Page 20: ...NTROLLERS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2015 Honeywell International Inc 66 1203 05 M S Rev 08 15 Printed in United States ...

Reviews: