S9360A, S9361A, S9380A, S9381A INTEGRATED BOILER CONTROLLERS
13
66-1203—05
Integrated Boiler Control Model Displays
See Table 6 for the IBC display screens.
Boiler Temperature Controller
When the water temperature reaches setpoint, the
controller ends the heating cycle. When the water
temperature drops below the setpoint minus the
differential, the control restarts a heat cycle to re-heat the
tank of water.
If the water temperature exceeds the max allowed
temperature, the control enters a manual reset lockout
state. For models that have reset capability, press any on-
board button (when present), cycle power, or use the local
(“rSt”) to reset.
CHECKOUT
Put the system into operation and observe operation
through at least one complete cycle to make sure that the
controller operates properly. See Troubleshooting section
to assist in determining system operation.
LOCATION AND MOUNTING
Sensing Bulb(s)
The boiler manufacturer usually provides a tapping for the
sensing bulb at a point where average water temperature
can be measured. See Fig. 8. Follow the boiler
manufacturer instructions.
The sensing bulb can be installed in an immersion well.
Wells and fittings must be ordered separately. See 68-
0040.
When an immersion well is used, the sensor should fit
snugly and should touch the bottom of the well for best
temperature response. Use heat-conductive compound
(Honeywell part no. 107408) to fill the space between the
bulb and the well to improve heat transfer characteristics
(optional). Make sure the sensor is held firmly in the well.
WIRING
IMPORTANT:
For maximum trouble free operation, run the
sensor leadwires separately from any other cur-
rent-carrying wires.
All wiring must comply with local codes and ordinances.
Disconnect power supply before beginning wiring.
Connect according to water heater manufacturer
instructions.
Fig. 8. Typical location of limit function sensor and
control module.
Table 6. 7-Segment LED Display - Installer Mode Options.
3-Digit 7-Segment Display
Default
Range
Description
1st
Screen
2nd Screen
3rd
Screen
<High Limit>
°
or °
180
130 to 220 °F
Adjust High Limit Setting
<High Limit Differential>
°
or °
15
10 to 30 °F
Adjust High Limit Differential
<Pump Overrun Time>
SEC
60
0-120 seconds
Pump Overrun Time
<ODR maximal temp.>
°
or °
55
40 to 70 °F
Maximal outdoor temperature
<ODR minimal temp.>
°
or °
0
-40 to 40 °F
Minimal outdoor temperature
<minimal water temp.>
°
or °
140
130 to 150 °F
Minimal boiler temperature
<minimal boiler temp.>
°
or °
140
OFF,
120 to 160 °F
Thermal purging minimal temperature
(Parameter is available only if outdoor
temperature is invalid)
<maximal delay>
Min
2
1 to 10 minutes
Maximal Thermal Purge time
(Parameter is available only if outdoor
temperature is invalid)
or
NA
NA
Reset Lockout
°
or °
F
F or C
Select degrees F or C Mode
M27076
PILOT
MAIN
BURNER
INLET
INTEGRATED
BOILER
CONTROL
INDUCER
MOTOR
(OPTIONAL)
SUPPLY
PUMP
LIMIT
SENSOR