Honeywell S9360A Manual Download Page 16

S9360A, S9361A, S9380A, S9381A INTEGRATED BOILER CONTROLLERS

66-1203—05

16

TROUBLESHOOTING

IMPORTANT

1. The following service procedures are provided 

as a general guide. Follow appliance manufac-

turer’s service instructions if available.

2. On lockout and retry models, meter readings 

between gas control and ignition module must 

be taken within the trial for ignition period. Once 

the ignition module shuts off, lockout models 

must be reset through the key buttons and dis-

play. On retry models, wait for retry or reset at 

the thermostat.

3. If any component does not function properly, 

make sure it is correctly installed and wired 

before replacing it.

4. The ignition module cannot be repaired. If it mal-

functions, it must be replaced.

5. Only trained, experienced service technicians 

should service ignition systems.

Perform the checkout as the first step in troubleshooting. 

Then check the appropriate troubleshooting guide and the 

schematic diagram to pinpoint the cause of the problem. If 

troubleshooting indicates an ignition problem, see Ignition 

System Checks below to isolate and correct the problem.

Following troubleshooting, perform the checkout 

procedure again to be sure system is operating normally.

Intermittent Pilot

Ignition System Checks

STEP 1: Check ignition cable.

Make sure:

• Ignition cable does not run in contact with any metal 

surfaces.

• Ignition cable is no more than 36 in. [0.9 m] long.

• Connections to the ignition module and to the igniter or 

igniter-sensor are clean and tight.

• Ignition cable provides good electrical continuity.

STEP 2: Check ignition system grounding. Nuisance 

shutdowns are often caused by a poor or erratic ground.

• A common ground, usually supplied by the pilot burner 

bracket, is required for the module and the pilot burner/

igniter sensor.

— Check for good metal-to-metal contact between 

the pilot burner bracket and the main burner.

— Check the ground lead from the GND(BURNER) 

terminal on the module to the pilot burner. Make 

sure connections are clean and tight. If the wire is 

damaged or deteriorated, replace it with No. 14-18 

gauge, moisture-resistant, thermoplastic insu-

lated wire with 105° C [221° F] minimum rating.

—Check the ceramic flame rod insulator for cracks 

or evidence of exposure to extreme heat, 

which can permit leakage to ground. Replace 

pilot burner/igniter-sensor and provide shield 

if necessary.

—If flame rod or bracket are bent out of position, 

restore to correct position.

STEP 3: Check spark ignition circuit.

• Disconnect the ignition cable at the SPARK terminal on 

the module.

WARNING

The ignition circuit generates over 10,000 volts 

and electrical shock can result.

Energize the module and listen for the audible sparking 

noise. When operating normally, there should be a 

buzzing noise that turns on and off twice per second for a 

duration of 1–7 seconds, depending on the model.

STEP 4: Check pilot and main burner lightoff.

• Set the system to call for heat by turning the 

thermostat above room temperature.

• Watch the pilot burner during the ignition sequence. 

See if:

— Ignition spark continues after the pilot is lit.

— The pilot lights and the spark stops, but main 

burner does not light.

• If so, ensure adequate flame current as follows.

— Turn off furnace at circuit breaker or fuse box.

— Clean the flame rod with emery cloth.

— Make sure electrical connections are clean and 

tight. Replace damaged wire with moisture-resis-

tant No. 18 wire rated for continuous duty up to 

105° C [221° F].

— Check for cracked ceramic insulator, which can 

cause short to ground, and replace igniter-sensor 

if necessary.

— At the gas valve, disconnect main valve wire from 

the MV terminal.

— Turn on power and set thermostat to call for heat. 

The pilot should light but the main burner will 

remain off because the main valve actuator is dis-

connected.

— Check the pilot flame. Make sure it is blue, steady 

and envelops 3/8 to 1/2 in. [10 to 13 mm] of the 

flame rod. See Fig. 12 for possible flame problems 

and their causes.

— If necessary, adjust pilot flame by turning the pilot 

adjustment screw on the gas control clockwise to 

decrease or counterclockwise to increase pilot 

flame. Following adjustment, always replace pilot 

adjustment cover screw and tighten firmly to 

assure proper gas control operation.

— Set temperature below room setpoint to end call 

for heat.

• Recheck ignition sequence as follows.

— Reconnect main valve wire.

— Adjust thermostat above room temperature.

— Watch ignition sequence at burner.

— If spark still doesn’t stop after pilot lights, replace 

module.

— If main burner doesn’t light or if main burner lights 

but system locks out, check module, ground wire 

and gas control as described in appropriate trou-

bleshooting chart.

Troubleshooting Error Codes

The integrated boiler control uses advanced diagnostic 

capability to assist in troubleshooting error conditions. 

Table 8 shows the codes that could arise on the remote or 

integrated display during a fault. Suggestions are 

provided in Table 5 for servicing these potential errors.

Summary of Contents for S9360A

Page 1: ...pe two rod separate ignitor and sensor one rod combined ignitor and sensor SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore an individual unit may not match the listed specifications exactly Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be exp...

Page 2: ...50 F Shipping Ambient Temperature 40 F to 175 F Flame Monitoring May vary by model Flame Establishing Period FEP Maximum 2 seconds Flame Failure Response Time FFRT Maximum 2 seconds 1 μA Flame Stabilization Time 4 seconds Time from ignit ing the main burner and detecting loss of flame the flame current is allowed to be under the flame lost threshold for this time while waiting for burner to stabil...

Page 3: ...l cleaning procedures If necessary shield the controls to protect them from splashing water A NEMA 4 enclosure is recommended High Humidity or Dripping Water Over time dripping water or high ambient humidity can create unwanted electrical paths on the module circuit board causing the module to fail Never install an appliance where water can drip on the controls In addition high ambient humidity ca...

Page 4: ...n but especially so in commercial agricultural and industrial applications because 1 In such applications particularly commercial the equipment can operate 100 000 to 200 000 cycles per year Such heavy cycling can wear out the gas control in one to two years A normal boiler applica tion for which the controls were intended typically operate fewer than 10 000 cycles per year 2 Exposure to water dir...

Page 5: ...9381A INTEGRATED BOILER CONTROLLERS 5 66 1203 05 Fig 2 Recommended slot hole pattern in appliance in mm Fig 3 Align module with slots in manufacturer s control box 100 M24198 16 16 55 4 99 5 4 WATER HEATER CONTROL BOX M24229 ...

Page 6: ...fit one end the module end with 1 4 in connector receptacle and the other with a connector to match the pilot assembly Protect both ends with insulated boots NOTE Cable length must be 36 in 0 9 m or less The cable must not be in continuous contact with a metal surface or spark voltage will be greatly reduced Use ceramic or plastic standoff insulators as required 1 Connect one end of the cable to t...

Page 7: ...61A2095 has a 1 minute retry delay and a 5 minute recycle delay Other lockouts will automatically clear after 1 hour Model Ignition Type Draft Type No of Ignition Trials Igniter Sensor Type Automatic Restart Timee Ignition Activation Perioda Prepurge Timingb Postpurge Timingb S9360A S9361A Intermittent Pilot Spark Induced 6 Separate Combinedc 1 hour N A 30 15 S9360A S9361A Intermittent Pilot Spark...

Page 8: ...ark to Pilot Ignition Wiring S936X 2 rod separate ignitor and sensor M33682 CIRCULATOR SPARK IGNITER FLAME SENSE INDUCER L1 L2 GND GND 24 VAC TRANSFORMER DAMPER ENVIRACOM DIAGNOSTIC GAS CONTROL MV PV PV MV PRESSURE SWITCH LIMIT SWITCH T STAT C R D ENVIRACOM SENSOR OPTIONAL BASED ON MODEL 1 1 1 ...

Page 9: ... 9 66 1203 05 Fig 5 Direct Spark Ignition DSI Wiring S938X 1 rod combined ignitor and sensor C R D ENVIRACOM SYSTEM CIRCULATOR L1 GND L2 INDUCER 24VAC TRANSFORMER SENSOR M33505 T STAT LIMIT SWITCH PRESSURE SWITCH GAS CONTROL MV PV MV SPARK IGNITER FLAME SENSE ...

Page 10: ...ig 6 Spark to Pilot Ignition S936X 1 rod combined ignitor and sensor M33830 C R D ENVIRACOM SYSTEM CIRCULATOR L1 GND L2 DAMPER INDUCER 24VAC TRANSFORMER SENSOR T STAT LIMIT SWITCH PRESSURE SWITCH PV PV MV GAS CONTROL MV OPTIONAL BASED ON MODEL 1 1 1 SPARK IGNITER FLAME SENSE ...

Page 11: ...System is in running mode flame signal must be present Postpurge 9 System is purging at the end of a call for heat Inter purge Retry Recycle Delay 10 If the control loses flame signal during state 7 or 8 it will recycle through the 30 seconds purge time and last 2 seconds part of prepurge time Re Start delay due to flame failure Wait for pressure switch to open failed closed 11 The inducer is stil...

Page 12: ... DOWN button until the parameter has reached the desired value After 60 seconds without any button inputs the control will automatically return to the READ mode Display In the RUN mode status items and parameters are viewable To read settings press and release the I key to find the parameter of interest For example press and release I until setpoint sp is displayed followed by a three digit number...

Page 13: ...ponse Use heat conductive compound Honeywell part no 107408 to fill the space between the bulb and the well to improve heat transfer characteristics optional Make sure the sensor is held firmly in the well WIRING IMPORTANT For maximum trouble free operation run the sensor leadwires separately from any other cur rent carrying wires All wiring must comply with local codes and ordinances Disconnect p...

Page 14: ...this point the burner is de activated the ignition module completes the heating cycle returns to idle and waits for the temperature to drop again The circulator is turned on throughout the Call for Heat See Fig 10 for a graphical representation of a simple control cycle Note that the setpoint differential may vary based on OS number High Limit Controller All models include a 3 wire temperature sen...

Page 15: ...CK FLAME PRE TRIAL SOFT LOCKOUT PROVE FLAME STOP SPARKING FLAME STABILIZATION TURN MAIN VALVE ON RUN POSTPURGE WATER TEMPERATURE LOW AND THERMOSTAT ACTIVE BIAS DONE WATER TEMP HIGH OR CALL FOR HEAT LOST SWITCH OPEN SWITCH CLOSE SWITCH OPEN FLAME DEB ON FLAME DEB OFF TIME OUT TIME OUT OR MANUAL RESET LIMIT SWITCH OPEN TIME OUT FLAME SENSED DSI TIME OUT FLAME PROVED TIME OUT WATER TEMPERATURE HIGH O...

Page 16: ...re bent out of position restore to correct position STEP 3 Check spark ignition circuit Disconnect the ignition cable at the SPARK terminal on the module WARNING The ignition circuit generates over 10 000 volts and electrical shock can result Energize the module and listen for the audible sparking noise When operating normally there should be a buzzing noise that turns on and off twice per second ...

Page 17: ...or gain too many failures during A D conversion Atmospheric Damper End Switch failed to close end switch contacts stuck open Atmospheric Damper End Switch failed to open end switch contacts stuck closed Flame Rod shorted to burner ground AC line frequency error signal is too noisy or frequency is incorrect Line voltage error voltage out of spec high or low Thermostat input higher than threshold Li...

Page 18: ... ORIFICE FILTER CLOGGED PILOT FILTER LOW GAS SUPPLY PRESSURE PILOT ADJUSTMENT AT MINIMUM CHECK FOR LACK OF AIR FROM DIRTY ORIFICE DIRTY LINT SCREEN IF USED DIRTY PRIMARY AIR OPENING IF THERE IS ONE PILOT ADJUSTMENT AT MINIMUM CHECK FOR EXCESSIVE DRAFT AT PILOT LOCATION RECIRCULATING PRODUCTS OF COMBUSTION CHECK FOR HIGH GAS PRESSURE THIS FLAME IS CHARACTERISTIC OF MANUFACTURED GAS CHECK FOR HIGH G...

Page 19: ...S9360A S9361A S9380A S9381A INTEGRATED BOILER CONTROLLERS 19 66 1203 05 ...

Page 20: ...NTROLLERS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2015 Honeywell International Inc 66 1203 05 M S Rev 08 15 Printed in United States ...

Reviews: