S8600F,H,M; S8610F,H; S8660D; S8670D
5 VENT
GND
24V
TH-W
DAMPER
MV MV/PV PV (BURNER)
GND 24V (OPT)
PLUG (OPT)
SPARK
PILOT
COM
MAIN
VALVE
5
END SWITCH
N.O. N.C.
3
D80B
1ST
2ND
OPERATOR OPERATOR
DUAL VALVE COMBINATION
GAS CONTROL
1K2
1K1
R
Q345, Q346,
Q348, Q362, Q381
PILOT BURNER/
IGNITER-SENSOR
PILOT
BURNER
GROUND
PILOT GAS
SUPPLY
4
1K3
1
2
3
4
5
6
L2
L1
(HOT)
1
TRANSFORMER
LIMIT
2
CONTROLLER
THERMOSTAT
OR
CONTROLLER
LIMIT
CONTROLLER
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 ALTERNATE LIMIT CONTROLLER LOCATION.
3 MAXIMUM CABLE LENGTH 3 ft [0.9 m].
4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.
5 FOR MODULE WITH TH-W TERMINAL AND VENT DAMPER PLUG, CONNECT THERMOSTAT TO TH-W.
LEAVE 24V OPEN. DO NOT REMOVE VENT DAMPER PLUG.
6 COLORS REFER TO WIRE HARNESS, IF USED.
M1180C
Fig. 7
—S8600F,H,M; S8610F,H; S8660D; S8670D in a heating system with an atmospheric burner and a
D80B vent damper.