Honeywell S8600 Manual Download Page 19

19 

69-0463 

 
 

 

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวัฒนา กทม. 10170. 
Website: 

https://www.add-furnace.com/

 โทร: 02-888-3472 

Line ID: @add11 e-mail: [email protected] 

ANSI STANDARDS 

 

EXHIBIT A 

 

RECOMMENDED PROCEDURE FOR SAFETY INSPECTION OF AN EXISTING 

APPLIANCE INSTALLATION AS A PRELIMINARY STEP TO APPLYING 

AN AUTOMATIC INTERMITTENT PILOT SYSTEM 

The following procedure is intended as a guide to aid 

in determining that an appliance is properly installed and 
is in a safe condition for continuing use. 

This procedure is predicated on central furnace and 

boiler  installations  equipped  with  an  atmospheric  gas 
burner(s) and not of the direct vent type. It should  be 
recognized  that  generalized  test  procedures  cannot 
anticipate  all  situations.  Accordingly,  in  some  cases, 
deviation  from  this  procedure  may  be  necessary  to 
determine safe operation of the equipment. 

a.  This procedure should be performed prior to any 
attempt at modification of the appliance or the instal- 
lation. 
b.  If it is determined there is a condition which could 
result in unsafe operation, the appliance should  be 
shut off and the owner advised of the unsafe condi- 
tion. 
The following steps should be followed in making the 

safety inspection: 

 

1.  Conduct  a  Gas  Leakage  Test  of  the  appliance 

piping  and  control  system  downstream  of  the  shutoff 
valve in the supply line to the appliance. 

 

2. Visually inspect the venting system for proper size 

and horizontal pitch and determine there is no blockage 
or restrictions, leakage or corrosion or other deficiencies 
which could cause an unsafe condition. 

 

3. Shut off all gas to the appliance and shut off any 

other fuel-burning appliance within the same room. Use 
the shutoff valve in the shutoff valve in the supply line to 
each appliance. 

 

4. Inspect burners and crossovers for blockage and 

corrosion. 

 

5.  Applicable only to warm air heating appliances. 

Inspect heat exchangers for cracks, openings or exces- 
sive corrosion. 

 

6. Applicable only to boilers. Inspect for evidence of 

water or combustion product leaks. 

 

7. Insofar as is practical, close all building doors and 

windows and all doors between the space in which the 
appliance is located and other spaces of the building. 
Turn on clothes dryers. Turn on any exhaust fans, such 
as range  hoods and  bathroom exhausts,  so  they will 

operate at maximum speed. Do not operate a summer 
exhaust fan. Close fireplace dampers. If, after complet- 
ing steps 7 through 12, it is believed sufficient combus- 
tion air is not available, refer to 1.3.4 of the National Fuel 
Gas Code (Z223.1) for guidance. 

 

8.  Place in operation the appliance being inspected. 

Follow  the  lighting  instructions.  Adjust  thermostat  so 
appliance will operate continuously. 

 

9.  a.  Determine that the pilot is burning properly and 

that main burner ignition is satisfactory by inter- 
rupting and re-establishing the electrical supply to 
the appliance in any convenient manner. 

 

b.  Determine manifold pressure in order to match 
input after the new control is installed. 

 

a. 

Visually determine that main burner gas is burn- 

ing properly; i.e., no floating, lifting or flashback. 
Adjust the primary air shutter(s) as required. 

b. 

If appliance is equipped with high and low flame 

control or flame modulation, check for proper main 
burner operation at low flame. 

 

11.  Test for spillage at the draft hood relief opening 

after 5 minutes of main burner operation. Use a draft 
gauge, the flame of a match or candle, or smoke from a 
cigarette, cigar or pipe. 

 

12.  Return doors, windows, exhaust fans, fireplace 

dampers and all other fuel-burning appliances to their 
previous conditions of use. 

 

13.  Applicable only to warm air heating appliances. 

Check both limit controller and fan controller for proper 
operation. Limit controller operation can be checked by 
temporarily  disconnecting  the  electrical  supply  to  the 
blower motor and determining that the limit control acts 
to shut off the main burner gas. 

 

14.  Applicable only to boilers: 

a.  Determine that the circulating water pumps are 
in operating condition. 
b.  Test  low  water  cutoffs,  automatic  feed  con- 
trols, pressure and temperature limit controls and 
relief  valves  in  accordance  with  the 
manufacturer’s  recommendations  and  instruc- 
tions to determine they are in operating condition. 

 

 

EXHIBIT A OF ANSI STANDARD Z21.71 FOR AUTOMATIC INTERMITTENT PILOT IGNITION SYSTEMS FOR FIELD 
INSTALLATION 

Summary of Contents for S8600

Page 1: ...ANING Once a module or gas control has been wet it may operate unreliably and must be replaced If the appliance is likely to be cleaned with water or steam the controls and associated wiring should be covered so water orsteam flow cannot reach them The controls should be high enough above the bottom of the cabinet so they will not be subject tofloodingorsplashingduringnormalcleaningprocedures If n...

Page 2: ...on Some considerations are Cyclingfrequency Appliances that may cycle more than 20 000 times annually should be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again be fore the next use PERFORM PREINSTALLATION SAFETY INSPECTION The preinstallation checks described in ANSI Standard Z21 71 on page 19 must be done before the replacement modu...

Page 3: ... end to vent damper To connect the D80B follow the wiring diagrams sup plied with the vent damper or see Fig 7 for typical connec tions Connect Ignition Module 1 Connectremainingsystemcomponentstotheignition module terminals as shown in the appropriate wiring dia gram Figs 1 to 10 Fig 1 is a basic circuit for a heating only atmos pheric burner with S8600F H M S8610F H S8660D or S8670D Fig 2 shows ...

Page 4: ... Strip the other end of the wire and fasten it under the igniter bracket mounting screw If necessary use a shield to protect the ground wire from radiant heat 3 The burner serves as the common grounding area If thereisnotgoodmetal to metalcontactbetweentheburner and ground run a lead from the burner to ground NOTE Earth ground is not required REPLACING MODULE WITH TH R TH W TERMINALS On modules th...

Page 5: ... CONTROL 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED THERMO STAT 1ST 2ND OPERATOR OPERATOR MAIN VALVE PILOT COM 3 197516A WIRING HARNESS SPARK DAMPER PLUG 5 VENT 24V GND 24V TH W S8600F H M S8610F H GND MV MV PV PV BURNER PILOT GAS SUPPLY LIMIT CONTROLLER GROUND IGNITER 1 L2 L1 HOT 4 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND L...

Page 6: ...SE SPARK 5 VENT DAMPER PLUG 24V GND 24V TH W S8600A B S8610A B GND MV MV PV PV BURNER M1177C L2 L1 HOT 1 PILOT GAS SUPPLY COMBUSTION 1 AIR BLOWER MOTOR GROUND 5 FOR MODULE WITH TH W TERMINAL AND VENT DAMPER PLUG CONNECT THERMOSTAT TO TH W LEAVE 24V OPEN DO NOT REMOVE VENT DAMPER PLUG PILOT BURNER Q345 Q346 Q348 Q362 Q381 PILOT BURNER IGNITER SENSOR LIMIT CONTROLLER L2 L1 HOT 2 ALTERNATE LIMIT CONT...

Page 7: ...L COMBUSTION AIR BLOWER RELAY 4 Q381PILOT BURNER IGNITER SENSOR PILOT BURNER GROUND PILOT GAS SUPPLY LIMIT CONTROLLER 1 L1 L2 L1 L2 HOT 1 COMBUSTION AIR BLOWER MOTOR HOT M1178C 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TOTRANSFORMER 5 FOR MOD...

Page 8: ...UND PILOT GAS SUPPLY 4 1K3 1 2 3 4 5 6 L2 L1 HOT 1 TRANSFORMER LIMIT 2 CONTROLLER THERMOSTAT OR CONTROLLER LIMIT CONTROLLER 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TOTRANSFORMER 5 FOR MODULE WITH TH W TERMINAL AND VENT DAMPER PLUG CONNECT T...

Page 9: ...R SENSOR PILOT BURNER GROUND PILOT GAS SUPPLY LIMIT CON TROLLER FAN CENTER 4 R C W G Y MOTOR COMBUSTION AIR BLOWER RELAY COIL FAN MOTOR FAN CONTROL C H 2 AIR PROVING SWITCH 1 POWER SUPPLY PROVIDE DISCONNECTMEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER 5 FOR MODULE ...

Page 10: ...OR PILOT BURNER GROUND PILOT GAS SUPPLY CABLE 2 L1 HOT 1 BLUE YELLOW G L1 5 BLACK TP 1K ORANGE B R L8148J 1K1 1K3 Z W T TV 1K2 AUTO MANUAL SWITCH C1 FAN MOTOR L2 L2 B3 B2 B1 C2 M1181C THERMOSTAT 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 CUT PLUG OFF MODULE END OF D80D WIRE HARNESS CONNECT LEADWIRE COLORS AS SHOWN 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 FOR MODULE WI...

Page 11: ...y Turn gas supply off Set thermostat or controller above room temperature to call for heat Watch for spark at pilot burner either immediately or following prepurge See device label Time spark from start to shutoff See device label On S8600M wait 6 min nom Ignition sequence should start again followed by shutoff after 90 sec max Open manual gas cock and make sure no gas is flowing to pilot or main ...

Page 12: ...ustion air blower starts on a call for heat On proof of airflow the air proving switch closes and energizes the S8660 S8670 When the module is used in an atmospheric system the call for heat energizes the module In either case the module first initiates a 45 sec delay to allow system prepurge After prepurge the module starts the pilot ignition sequence START STAGE 1 TRIAL FOR IGNIITION 3 Pilot bur...

Page 13: ...yretry for ignition Operation on ignition failure is the same as lockout modules except that a timer starts timing imme diately following shutoff Six minutes nom five minutes min after shutoff the module restarts the ignition se quence The ignition trial shutoff wait sequence continues until either the pilot lights or the thermostat is set below room temperature to end the call for heat The module...

Page 14: ...exposure to extreme heat which can permit leakage to ground Replace pilot burner igniter sensor and provide shield ifnecessary If flame rod or bracket are bent out of position restore to correct position STEP 3 Check spark ignition circuit You will need a short jumper wire made from ignition cable or other heavily insulated wire Close the manual gas valve Disconnect the ignition cable at the SPARK...

Page 15: ...stem SPARK STOPS WHEN PILOT IS LIT Check continuity of ignition cable and ground wire Clean flame rod Check electrical connections between flame rod and module Check for cracked ceramic flame rod insulator Check that pilot flame covers flame rod and is steady and blue Adjust pilot flame If problem persists replace module Spark okay Pull ignition lead and check spark at module TURN GAS SUPPLY OFF T...

Page 16: ...16 44 ซ บรมราชชนนี 70 ถ บรมราชชนนี ศาลาธรรมสพน ทวีวัฒนา กทม 10170 Website https www add furnace com โทร 02 888 3472 Line ID add11 e mail add028883472 gmail com Fig 15 S8660 S8670 troubleshooting guide ...

Page 17: ...CIRCUITS SPARK IGNITER SENSOR GND BUR NER BURNER GROUND MAIN 1K1 1K2 3K2 VALVE MV PILOT MV PV 2K 3K1 VALVE PV 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3K RELAY ON 100 PERCENT SHUTOFF MODELS ONLY ON NON SHUTOFF MODELS PV AND MV WIRED AS FOLLOWS TO 24V TO 24V GND MAIN INTERNAL WIRING 1K1 2K2 1K2 VALVE MV PILOT VALVE PV MV PV EX...

Page 18: ...E DETECTOR CIRCUIT RELAY DRIVERS HYBRID CIRCUIT TIMING CIRCUITS SPARK IGNITER GND BUR NER BURNER GROUND MAIN 1K1 1K2 3K2 VALVE MV PILOT MV PV 2K 3K1 VALVE PV 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3K RELAY ON 100 PERCENT SHUTOFF MODELS ONLY ON NON SHUTOFF MODELS PV AND 3 MV WIRED AS FOLLOWS TO 24V MAIN TO 24V GND INTERNAL W...

Page 19: ...all building doors and windows and all doors between the space in which the appliance is located and other spaces of the building Turn on clothes dryers Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers If after complet ing steps 7 through 12 it is believed sufficient combus tion air ...

Page 20: ...laced with a Class 2 transformer of adequate rating 6 Check the heat anticipator in the comfort thermo stat to determine if it is properly adjusted to the current draw of the control system Follow the thermostat manufacturer s instructions 7 Make certain wiring connections are tight and wires are positioned and secured so they will not be able to contact high temperature locations 8 Conduct a Gas ...

Reviews: