GENERAL CONSIDERATIONS

To ensure reliable long term operation, mount ignition control

at a position in the appliance with a low ambient temperature

and a low radiation.
High temperatures will affect product life.
If the S4567 is installed in an area subject to water (dripping,

spraying, rain, etc.) then means shall be provided to protect

the components.
To suppress Radio Interferency Interference (RFI) the ignition

control including spark igniter cabling should be mounted in

sufficient shielded environment.
NOTE:Electrical rating of connected controls (e.g. room

thermostat) should be appropriate for the load that is

switched by the ignition control.

INSTALLATION

IMPORTANT

Disconnect power supply to prevent electrical shock

and/or equipment damage.
Wiring must be in accordance with local regulations.
The appliance manufacturer’s instructions should

always be followed when provided. If such

instructions are not provided see fig. 1. or 2. for

typical systems.
Before installing or replacing any control check that

type number is correct for the application.
Conduct a thorough check out when installation is

completed.
At the first start the ignition control can be in

lock--out; depress reset button to free control.

CAUTION

If ignition frequency is

25 Hz or pulse

energy

>

45

As, the ignition cable and its

connections shall have a protection against electrical

schck hazard.

Fusing

In order to prevent unsafe conditions at too high current, the

automatic ignition controls must be externally fused with a

4 A fuse (F).

Wiring

CAUTION

Label all wires prior to disconnection when servicing

controls.
Wiring errors can cause improper and dangerous

operation.

Use leadwire which can withstand 105

_

C ambient.

Use leadwire which is proven against moisture.

Wiring between automatic ignition control and spark

sensing probe should have good quality insulation,

suitable for the temperatures encountered.

Spark gap

Max. allowable spark gap 3.5 mm

Supply voltage polarity

WARNING

If automatic ignition control seems to operate normally

but does not detect flame, check for right polarity of

power supply (line, neutral).

Checking flame current

For direct burner application the minimum value should be

0.9

A.

To check flame current connect a DC micro--Ampèremeter

between flame sensing wire and flame sensing rod.

If flame current is insufficient check that flame sensing rod

is fully enveloped by the flame and that burner is reliable

grounded to automatic ignition control.

Meter connections polluted with e.g. alkaline substances

lying close to earth can cause flame current simulation.

Make sure no false flame current can flow from meter

connections to earth.

Final checkout of the installation

Set appliance in operation after any adjustment and observe

several complete cycles to ensure that all burner components

function correctly.

Maintenancee and service

Under normal circumstances no maintenance or service is

required nor possible.

The S4567A 1001 and S4567B1017 ignition controls are field

replacaeble.

Home and Building Control

Combustion Controls Center Europe

Honeywell BV
Phileas Foggstraat 7

7821 AJ Emmen
The Netherlands

Tel: +31 (--)591 695911
Fax: +31 (--)591 695200

http://europe.hbc.honeywell.com

Summary of Contents for S4567A 1001

Page 1: ...dance SPECIFICATIONS Model S4567A 1001 ignition control for atmospheric direct burner ignition S4567B 1017 ignition control for atmospheric direct burner ignition and flame opto output Supply voltage 220 240 Vac 50 60 Hz Power consumption 4 VA Humidity 90 RH max at 40 _C non condensing Ambient temperature 15 60 _C Electrical rating Gas valve output pin 2 of S4567A 1001 suitable for one VK4105 Use ...

Page 2: ...ignition time and flame establishment If flame is not established within the safety time Ts the ignition control locks out If the flame is lost during normal run the ignition control repeats start sequence Lock out reset The ignition control can be reset by depressing the external reset button If a first reset is not succesful wait at least 15 seconds before attempting another one NOTE 1 When firs...

Page 3: ... N 10K 1K 10K 5 V LM Limiter RS Reset switch Fig 2 Connection diagram S4567B 1017 Gas valve and external gas valve A 1001 t0 t1 t2 t4 t5 Tc Tw t6 Ts Thermostat Limiter Alarm Ignition Flame rod Legend t3 Tc Tw Fig 3 Functional diagram S4567A 1001 and S4567B 1017 ...

Page 4: ...rnally fused with a 4 A fuse F Wiring CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Use leadwire which can withstand 105 _C ambient Use leadwire which is proven against moisture Wiring between automatic ignition control and spark sensing probe should have good quality insulation suitable for the temperatures encounte...

Reviews: