Honeywell S4567A 1001 Instruction Sheet Download Page 1

INSTRUCTION SHEET

S4567A 1001 & S4567B 1017

IGNITION CONTROL FOR COMBINED VALVE AND IGNITION SYSTEM

EN1R--9132 0011R7--NE

APPLICATION

The Combined Valve and Ignition system (CVI) has specially

been developed for application in gas fired appliances with

either intermittent pilot or direct burner ignition.
For this system, the S4567A 1001 and S4567B 1017 ignition

controls have been designed to attach directly onto the

VK4105 gas controls.
The combined system then provides programmed safe light

up, flame supervision and regulation of gas flow to the main

burner.

DESCRIPTION

The S4567A 1001 and S4567B 1017 ignition controls provide

automatic ignition for direct gas burner applications.
The S4567A 1001 and S4567B 1017 ignition controls comply

with EN 55014 and function in accordance with:

-- EN 298, code A/M/C/L/X/N.

-- ANSI Z21.20

FEATURES

Flame supervision.

Built in 33 Hz or 40 Hz ignition.

External reset and alarm.

Accurate safety timer.

Supply voltages of 220 ... 240 V in a single product.

Full operating sequence after flame loss.

Safe separation opto couplers for flame output

(S4567B 1017 only), alarm output and reset input.

Non volatile lock--out according EN 298.

Gas valve live output (S4567A 1001 only).

Flame rod safely accessible because of protective

impedance.

SPECIFICATIONS

Model

S4567A 1001 ignition control for atmospheric, direct

burner ignition.

S4567B 1017 ignition control for atmospheric, direct

burner ignition and flame opto output

Supply voltage

220 ... 240 Vac, 50 ... 60 Hz

Power consumption

4 VA

Humidity

90% RH max. at 40

_

C (non condensing)

Ambient temperature

--15 ... 60

_

C

Electrical rating

Gas valve output (pin 2 of S4567A 1001): suitable for one

VK4105. Use rectifier plug from the 45.900.441--“series “,

e. g. 45.900.441--030

Electrical connection

High voltage spark: 2.8 x 0.5 mm spade terminal

Flame sensing: 4.8 x 0.8 mm spade terminal

PCB connector: Stocko mks 2823 3 and 4 pole

IP protection degree in accordance with EN 60529

IP 00 (standard)
IP 04 or IP X4

Use: cover set 45.900.431--004 or

cover set 45.900.431--005

(flame retardant according to UL94--V0)

cable grommet 45.900.442--008/009

sleeve 45.900.442--003

gasket 45.900.442--007/011

IP 44

As IP 04 but the appliance manufacturer must connect the

ignition output in such a way that it cannot be taken off

without the use of a tool.
In order to prevent the risk of an electric shock when the

ignition control is mounted in the appliance, additional

protection of the ignition output must be provided by the

application manufacturer in all above cases.

Timing

Self check time (T

c

): 1.5 s

Safety time (T

s

): 10 s

Flame sensing

Min. flame current: 0.9

A

Response time on:

>

0.2 s

Response time off at I

flame

= 2

A :

<

1 s

Subject

to

change

w

ithout

notice.

Printed

in

the

N

etherlands.

Summary of Contents for S4567A 1001

Page 1: ...dance SPECIFICATIONS Model S4567A 1001 ignition control for atmospheric direct burner ignition S4567B 1017 ignition control for atmospheric direct burner ignition and flame opto output Supply voltage 220 240 Vac 50 60 Hz Power consumption 4 VA Humidity 90 RH max at 40 _C non condensing Ambient temperature 15 60 _C Electrical rating Gas valve output pin 2 of S4567A 1001 suitable for one VK4105 Use ...

Page 2: ...ignition time and flame establishment If flame is not established within the safety time Ts the ignition control locks out If the flame is lost during normal run the ignition control repeats start sequence Lock out reset The ignition control can be reset by depressing the external reset button If a first reset is not succesful wait at least 15 seconds before attempting another one NOTE 1 When firs...

Page 3: ... N 10K 1K 10K 5 V LM Limiter RS Reset switch Fig 2 Connection diagram S4567B 1017 Gas valve and external gas valve A 1001 t0 t1 t2 t4 t5 Tc Tw t6 Ts Thermostat Limiter Alarm Ignition Flame rod Legend t3 Tc Tw Fig 3 Functional diagram S4567A 1001 and S4567B 1017 ...

Page 4: ...rnally fused with a 4 A fuse F Wiring CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Use leadwire which can withstand 105 _C ambient Use leadwire which is proven against moisture Wiring between automatic ignition control and spark sensing probe should have good quality insulation suitable for the temperatures encounte...