Cable length

Flame sensing: 1000 mm max.

Ignition: 500 mm max.

Ignition

Spark voltage:

>

15 kV at 40 pF load

Repetition rate: S4567A 1001: 40 Hz

S4567B 1017: 33 Hz

Spark energy: S4567A 1001: 9

As

S4567B 1017: 3

As

Max. spark gap: 3.5 mm

Remark

Integrated flame (S4567B 1017 only), alarm and reset opto

couplers with safe separation.

SYSTEM OPERATION

S4567A 1001 and S4567B 1017 (see fig. 3.)

When there is a call for heat a self check time (T

c

) plus waiting

period (T

w

) elapse before built--in igniter and gas valve(s) are

switched on.

The ignition spark ignites gas and resulting flame is detected

by the flame rod.

Ignition is switched off after extended ignition time and flame

establishment.

If flame is not established within the safety time (T

s

), the

ignition control locks out.

If the flame is lost during normal run, the ignition control

repeats start sequence.

Lock- out reset

The ignition control can be reset by depressing the external

reset button.

If a first reset is not succesful, wait at least 15 seconds before

attempting another one.
NOTE 1.: When first starting, the control can be in the

lock--out condition; depress the reset button to free

the controls.

After a manual reset an extended waiting time will

occur.

NOTE 2.: If during normal use the reset button is pressed, the

gas valves drop off and the ignition control starts a

new sequence after releasing the reset button.

Side connection

4

5

L

3

3

1

RS

6

2

LM

N

10K

1K

+

--

5 V

LM -- Limiter

RS -- Reset switch

GV -- Gas valve

GV

Fig. 1. Connection diagram S4567A 1001

Summary of Contents for S4567A 1001

Page 1: ...dance SPECIFICATIONS Model S4567A 1001 ignition control for atmospheric direct burner ignition S4567B 1017 ignition control for atmospheric direct burner ignition and flame opto output Supply voltage 220 240 Vac 50 60 Hz Power consumption 4 VA Humidity 90 RH max at 40 _C non condensing Ambient temperature 15 60 _C Electrical rating Gas valve output pin 2 of S4567A 1001 suitable for one VK4105 Use ...

Page 2: ...ignition time and flame establishment If flame is not established within the safety time Ts the ignition control locks out If the flame is lost during normal run the ignition control repeats start sequence Lock out reset The ignition control can be reset by depressing the external reset button If a first reset is not succesful wait at least 15 seconds before attempting another one NOTE 1 When firs...

Page 3: ... N 10K 1K 10K 5 V LM Limiter RS Reset switch Fig 2 Connection diagram S4567B 1017 Gas valve and external gas valve A 1001 t0 t1 t2 t4 t5 Tc Tw t6 Ts Thermostat Limiter Alarm Ignition Flame rod Legend t3 Tc Tw Fig 3 Functional diagram S4567A 1001 and S4567B 1017 ...

Page 4: ...rnally fused with a 4 A fuse F Wiring CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Use leadwire which can withstand 105 _C ambient Use leadwire which is proven against moisture Wiring between automatic ignition control and spark sensing probe should have good quality insulation suitable for the temperatures encounte...

Reviews: