background image

3

69-0669B—2

Checkout

CAUTION

To prevent damage to the R8991, do not use an
ignition tester to check out the R8991 Ignition
Source. Iron core transformer ignition testers can
damage solid state ignitors.

CAUTION

When using R8991 with a 24V thermostat, discon-
nect  at least one lead wire from the T1-T2 ter-
minals  on R8991 before jumpering T1-T2 to
simulate a call for heat or damage to thermostat
heat anticipator can result.

IMPORTANT: Only a trained, experienced service tech-

nician should perform the checkout procedure.

NOTE: The reset button can also be used to return the

R8991 to the idle mode during trial for ignition, ignition
carryover, or run mode by pressing in and holding down
the button. When the reset button is released, the R8991

initiates a trial for ignition if a call for heat continues.
This  facilitates system checkout by simulating that the
thermostat is not calling for heat (pressing in and holding
down the button) without changing the thermostat setting.

START SYSTEM

WARNING

FIRE OR EXPLOSION HAZARD.
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY OR DEATH.
Make sure combustion chamber is free of oil or oil
vapor before starting the system.

1. Make sure the system is powered. Check the circuit

breaker or fuse and close the system switch, if provided. If
indicator light is flashing at 1/4 Hz (2 seconds on, 2 seconds
off), this indicates that the control is in the recycle mode. Wait
60 seconds for the recycle period to end. After 60 seconds,
the indicator light stops flashing.

2. If indicator light is flashing at 2 Hz (1/4 second on,

1/4 second off), indicating that the control is locked out, push
in and release the red reset button on the R8991 Interrupted
Ignition Recycle Oil Primary and Ignitor. The light should
stop flashing.

TABLE 1—R8991 OPERATION.

a

 During lockout, the green diagnostic light starts flashing at 2 Hz (1/4 second on, 1/4 second off). Reset R8991 by pushing in
and releasing the red reset button. The green diagnostic light stops flashing and goes off. If there is a call for heat, the R8991
returns to a try for ignition.

External Action

R8991 Action

Connect line voltage power.

R8991 is energized if limit switch is closed.

There is no call for heat.

Green diagnostic light is on if cad cell senses flame. Green light is off if cad
cell does not sense flame.

Thermostat calls for heat.

R8991 does not try for ignition if cad cell senses flame. If cad cell does not
sense flame, burner is energized after a one second delay and ignition is on.  
NOTE: The ignition on is a pulsing action. See description above this table.

Cad cell senses flame within lockout
time.

Diagnostic light and ignition are on. Ignition continues for 45 seconds after
cad cell senses flame (Ignition Carryover), then turns off. Burner is running.

Thermostat call for heat is satisfied.

Burner stops. Diagnostic light turns off.

Burner fails to ignite on call for heat. Burner motor and ignition are turned off at end of lockout time.

a

Burner ignites, but flame fails prior
to lockout time.

Green diagnostic light turns off.
Ignition remains on until either cad cell senses flame or lockout time ends.
If flame was not re-established, the R8991 locks out.

a

Burner ignites, but flame fails after
lockout time and during Ignition
Carryover.

Burner shuts off. R8991 enters recycle mode and the green diagnostic light
flashes at 1/4 Hz (2 seconds on, 2 seconds off). The control waits 60 seconds
before attempting to restart.

Flame fails during burner-on cycle.  

Burner shuts off. R8991 enters recycle mode and the green diagnostic light
flashes at 1/4 Hz (2 seconds on, 2 seconds off). The control waits 60 seconds
before attempting to restart.

Power fails during call for heat.

Burner shuts off safely. R8991 automatically attempts to relight with all safety
checks when power is restored.

Power fails during recycle mode.

When power is restored, R8991 will not respond to a call for heat until a full
60 second recycle period is complete.

Power fails during lockout mode.

R8991 remains locked out.
When power is restored, R8991 stays in lockout mode.

a

Summary of Contents for R8991

Page 1: ...nition Recycle Oil Primary and Ignitor consists of an interrupted ignition oil primary solid state ignition source and cad cell flame sensor for mounting directly on an oil burner housing This single unit control primary and ignitor operates the oil burner and oil valve if desired in response to a call for heat from the thermo stat The R8991 monitors the burner flame and shuts down the system on i...

Page 2: ...ROLLER WIRING CODE LOW VOLTAGE LINE VOLTAGE LINE VOLT THERMOSTAT IF USED BLACK WHITE ORANGE L1 HOT L2 LINE 24V THERMOSTAT 1 2 2 M814 LIMIT BURNER MOTOR OIL VALVE T T R8991 TYPICAL R8991 CONTROL CIRCUIT Operation R8991 Interrupted Ignition Recycle Oil Primary and Ignitor operation is discussed in Table 1 The R8991 Primary and Ignitor is controlled by a small computer This computer determines the ap...

Page 3: ...et button The green diagnostic light stops flashing and goes off If there is a call for heat the R8991 returns to a try for ignition External Action R8991 Action Connect line voltage power R8991 is energized if limit switch is closed There is no call for heat Green diagnostic light is on if cad cell senses flame Green light is off if cad cell does not sense flame Thermostat calls for heat R8991 do...

Page 4: ...indefinitely cycling the relay and restarting the lockout timing Troubleshooting IMPORTANT Onlyatrained experiencedservicetechni cian should perform the troubleshooting procedure To completely troubleshoot an oil burner installation check the burner and oil primary control which includes ignition source and cad cell for proper operation and condition The indicator light on the oil primary control ...

Page 5: ...Turns On Indicator Light Stays Off 3 Check indicator light after flame is established but before oil primary control locks out 3 Indicator light is on until the control locks out Indicator light starts flashing during lockout Oil primary control is defective replace control 3 Indicator light does not turn on Check cad cell sighting for view of flame go to step 4 Burner Locks Out Burner Keeps Runni...

Page 6: ...and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A www honeywell com QUALITY IS KEY ...

Page 7: ...ICATIONS Temps de mise sous sécurité 15 30 ou 45 secondes Temps de répétition de cycle 60 secondes Temps de rémanence 45 secondes HOMOLOGATIONS Composants reconnus par les Laboratoires des assureurs Inc dossier MP286 guide MCCZ2 Certifié par l Association canadienne de normalisation dossier no LR95329 1 CARACTÉRISTIQUES ÉLECTRIQUES NOMINALES Entrée 120 V c a 60 Hz Sortie Contacts du moteur du brûl...

Page 8: ...LORSQUE LE SYSTÈME COMPORTE UN RÉGULATEUR TENSION SECTEUR PLACER UN CAVALIER AUX BORNES T T ET RACCORDER LE THERMOSTAT TENSION SECTEUR EN SÉRIE AVEC LE LIMITEUR 2 S assurer que les connexions tension secteur sont conformes à l illustration de la Fig 2 Raccorder le fil orange au moteur du brûleur le fil blanc à la tension secteur neutre et le fil noir à la tension secteur sous tension 3 Épisser les...

Page 9: ...manence puis s éteint Le brûleur est en marche La demande de chaleur du thermostat est satisfaite Le brûleur cesse de fonctionner Le voyant s éteint Le brûleur ne s allume pas lors de la demande de chaleur Le moteur du brûleur et l allumeur cessent de fonctionner à la fin du délai de mise sous sécurité a Le brûleur s allume mais la flamme s éteint avant la mise sous sécurité Le voyant vert s étein...

Page 10: ...ation d alimentation en mazout 5 Régler le limiteur et régler le thermostat pour provoquer un appel de chaleur ou placer un cavalier entre les bornes T1 et T2 du R8991 pour simuler un appel de chaleur 6 Après une seconde le brûleur et l allumeur devrait se mettre en marche 7 Si le régulateur primaire se met sous sécurité avant le mazout n atteigne le brûleur appuyer sur le bouton de réarmement et ...

Page 11: ...t le filtre VÉRIFIER LE RÉGULATEUR PRIMAIRE DE MAZOUT ET L ALLUMEUR Si le problème ne provient par du brûleur ou du matériel d allumage vérifier le régulateur primaire de mazout et l allumeur au moyen du matériel ci dessous Tournevis Voltmètre 0 à 150 V c a Cavalier isolé dénudé aux deux extrémités AVERTISSEMENT Le système est alimenté en courant lors du dépannage Prendre toutes les précautions né...

Page 12: ...pas Vérifier la visée de la cellule photoélectrique pour s assurer que la flamme est bien en vue passer à l étape 4 Le brûleur se met sous sécurité Le brûleur continue sans cesse de fonctionner 4a Débrancher l alimentation tension secteur et ouvrir l interrupteur tension secteur 4b Déconnecter la cellule photoélectrique et la nettover en utilisant un linge doux Vérifier la visée et s assurer que l...

Reviews: