background image

69-0669B—2

2

Fig. 1—Mounting R8991 on main burner
housing.

HINGE
SCREWS (2)

HOLDING
SCREWS (2)

RESET
BUTTON

R8991
OIL PRIMARY
CONTROL

HINGE

BURNER
HOUSING

M5245

TO
COMBUSTION
CHAMBER

1

THERMOSTAT
SCREW
TERMINALS

WIRING ENCLOSURE 
AREA AT REAR
OF BURNER HOUSING

1

MEANS OF SECURING R8991 TO BURNER 
HOUSING VARIES DEPENDING ON R8991 MODEL USED.

1

CLIPS

2. Make line voltage connections as shown in Fig. 2.

Connect orange wire to burner motor, white wire to line
voltage-neutral, and black wire to line voltage-hot.

3. Splice leads with solderless connectors.
4. Do not exceed load ratings listed in the Application

section.

When the line voltage wiring is completed, secure the

R8991 control to the burner housing on the side opposite of
the hinge (see Fig. 1).

24V THERMOSTAT WIRING CONNECTIONS

Run low voltage wiring from the thermostat to the R8991

location. Connect thermostat wires to thermostat screw ter-
minals (T1 and T2) on R8991. Thermostat screw terminals
are accessible on the R8991 cover (see Fig. 1).

LINE VOLTAGE CONTROLLER WIRING
CONNECTIONS

Jumper T1–T2 terminals on R8991 and connect line volt

thermostat in series with limit controller.

Fig. 2—Typical wiring diagram of R8991 for oil
burner system.

1   POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND 
     OVERLOAD PROTECTION AS REQUIRED.

2   FOR USE WITH LINE VOLT CONTROLLER, JUMPER
     T-T TERMINALS AND CONNECT LINE VOLT
     THERMOSTAT IN SERIES WITH LIMIT CONTROLLER.

WIRING CODE
LOW VOLTAGE
LINE VOLTAGE

LINE VOLT
THERMOSTAT
(IF USED)

BLACK

WHITE

ORANGE

L1

(HOT)

L2

(LINE)

24V THERMOSTAT

1

2

2

M814

LIMIT

BURNER

MOTOR

OIL

VALVE

T

T

R8991

TYPICAL R8991 CONTROL CIRCUIT

Operation

R8991 Interrupted Ignition Recycle Oil Primary and

Ignitor operation is discussed in Table 1.

The R8991 Primary and Ignitor is controlled by a small

computer. This computer determines the appropriate times
to use the five second continuous spark and when to use the
duty-cycled spark. By selecting the appropriate 32 kHz
spark, the computer decreases wear on the components and
significantly extends the life of the R8991 Primary and
Ignitor beyond that of conventional iron core primaries.

The R8991 Interrupted Ignition Recycle Oil Primary and

Ignitor may not produce a five-second continuous spark on
installation startup. The ignition spark will probably be at a
20% duty cycle of 5 Hz (spark on for 0.04 second and off
for 0.16 second).

Because the duty-cycled spark has a one-to-four on-off

cycle, it may sound like it is pulsing. This is normal and will
not affect the operation of the primary or the burner. The
duty-cycled spark will ignite the oil and the normal cycle will
proceed through Ignition Carryover and Run.

The duty-cycled spark will ignite the oil even under ad-

verse conditions such as cold oil, contaminated oil, excess
air, or fouled electrodes. By pulsing the spark, ignitor and
electrode life is extended, because the components are ener-
gized for less time and do not heat up as much as components
would in a continuous spark system.

Table 1 describes R8991 operation.

Summary of Contents for R8991

Page 1: ...nition Recycle Oil Primary and Ignitor consists of an interrupted ignition oil primary solid state ignition source and cad cell flame sensor for mounting directly on an oil burner housing This single unit control primary and ignitor operates the oil burner and oil valve if desired in response to a call for heat from the thermo stat The R8991 monitors the burner flame and shuts down the system on i...

Page 2: ...ROLLER WIRING CODE LOW VOLTAGE LINE VOLTAGE LINE VOLT THERMOSTAT IF USED BLACK WHITE ORANGE L1 HOT L2 LINE 24V THERMOSTAT 1 2 2 M814 LIMIT BURNER MOTOR OIL VALVE T T R8991 TYPICAL R8991 CONTROL CIRCUIT Operation R8991 Interrupted Ignition Recycle Oil Primary and Ignitor operation is discussed in Table 1 The R8991 Primary and Ignitor is controlled by a small computer This computer determines the ap...

Page 3: ...et button The green diagnostic light stops flashing and goes off If there is a call for heat the R8991 returns to a try for ignition External Action R8991 Action Connect line voltage power R8991 is energized if limit switch is closed There is no call for heat Green diagnostic light is on if cad cell senses flame Green light is off if cad cell does not sense flame Thermostat calls for heat R8991 do...

Page 4: ...indefinitely cycling the relay and restarting the lockout timing Troubleshooting IMPORTANT Onlyatrained experiencedservicetechni cian should perform the troubleshooting procedure To completely troubleshoot an oil burner installation check the burner and oil primary control which includes ignition source and cad cell for proper operation and condition The indicator light on the oil primary control ...

Page 5: ...Turns On Indicator Light Stays Off 3 Check indicator light after flame is established but before oil primary control locks out 3 Indicator light is on until the control locks out Indicator light starts flashing during lockout Oil primary control is defective replace control 3 Indicator light does not turn on Check cad cell sighting for view of flame go to step 4 Burner Locks Out Burner Keeps Runni...

Page 6: ...and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A www honeywell com QUALITY IS KEY ...

Page 7: ...ICATIONS Temps de mise sous sécurité 15 30 ou 45 secondes Temps de répétition de cycle 60 secondes Temps de rémanence 45 secondes HOMOLOGATIONS Composants reconnus par les Laboratoires des assureurs Inc dossier MP286 guide MCCZ2 Certifié par l Association canadienne de normalisation dossier no LR95329 1 CARACTÉRISTIQUES ÉLECTRIQUES NOMINALES Entrée 120 V c a 60 Hz Sortie Contacts du moteur du brûl...

Page 8: ...LORSQUE LE SYSTÈME COMPORTE UN RÉGULATEUR TENSION SECTEUR PLACER UN CAVALIER AUX BORNES T T ET RACCORDER LE THERMOSTAT TENSION SECTEUR EN SÉRIE AVEC LE LIMITEUR 2 S assurer que les connexions tension secteur sont conformes à l illustration de la Fig 2 Raccorder le fil orange au moteur du brûleur le fil blanc à la tension secteur neutre et le fil noir à la tension secteur sous tension 3 Épisser les...

Page 9: ...manence puis s éteint Le brûleur est en marche La demande de chaleur du thermostat est satisfaite Le brûleur cesse de fonctionner Le voyant s éteint Le brûleur ne s allume pas lors de la demande de chaleur Le moteur du brûleur et l allumeur cessent de fonctionner à la fin du délai de mise sous sécurité a Le brûleur s allume mais la flamme s éteint avant la mise sous sécurité Le voyant vert s étein...

Page 10: ...ation d alimentation en mazout 5 Régler le limiteur et régler le thermostat pour provoquer un appel de chaleur ou placer un cavalier entre les bornes T1 et T2 du R8991 pour simuler un appel de chaleur 6 Après une seconde le brûleur et l allumeur devrait se mettre en marche 7 Si le régulateur primaire se met sous sécurité avant le mazout n atteigne le brûleur appuyer sur le bouton de réarmement et ...

Page 11: ...t le filtre VÉRIFIER LE RÉGULATEUR PRIMAIRE DE MAZOUT ET L ALLUMEUR Si le problème ne provient par du brûleur ou du matériel d allumage vérifier le régulateur primaire de mazout et l allumeur au moyen du matériel ci dessous Tournevis Voltmètre 0 à 150 V c a Cavalier isolé dénudé aux deux extrémités AVERTISSEMENT Le système est alimenté en courant lors du dépannage Prendre toutes les précautions né...

Page 12: ...pas Vérifier la visée de la cellule photoélectrique pour s assurer que la flamme est bien en vue passer à l étape 4 Le brûleur se met sous sécurité Le brûleur continue sans cesse de fonctionner 4a Débrancher l alimentation tension secteur et ouvrir l interrupteur tension secteur 4b Déconnecter la cellule photoélectrique et la nettover en utilisant un linge doux Vérifier la visée et s assurer que l...

Reviews: