Setting Slider Tabs
Set R Slider Tab, see Figure 9.
• Use built-in jumper
(R Slider Tab)
to differentiate between one or two
transformer systems.
• If there is only one R wire, and it is
connected to the
R
,
Rc
, or
RH
terminal
on the old thermostat, set the slider to
the
up
position
(1 wire)
.
• If there is one wire connected to the
R
terminal and one wire connected to the
Rc
terminal, set the slider to the
down
position
(2 wires)
.
Set U Slider Tab, see Figure 10.
• Use built-in jumper (U Slider Tab) for
IAQ device.
• When the
U Slider Tab
is in the down
position
(2 wires)
the U contacts are a
dry set of contacts.
• If your IAQ device is powered by the
cooling transformer, move the
U Slider
Tab
to the up position (1 wire). When
this is done, the lower U terminal is
internally jumped to the Rc terminal.
In this application, you would hook
up one wire from your IAQ device to
the upper U terminal and the other
to the common side of the cooling
transformer. The 1 wire setting is most
commonly used when using a fresh
air damper for ventilation or using low
speed fan for dehumidification.
• See wiring examples on the next page.