3. Configuration
3.1. Safety Messages
10
OWA 100 Adapter User Manual
Rev. 2
July
2011
3. Configuration
3.1 Safety
Messages
These instruction procedures may require special precautions to ensure the safety of the personnel
performing the operations. Information that potentially raises safety issues is indicated by a warning
symbol (
). Please refer to the following safety messages before performing an operation preceded by
this symbol.
Warnings
WARNING – POTENTIAL ELECTROSTATIC CHARGING HAZARD
The OWA 100 OneWireless Adaptor enclosure is non-conductive Lexan, EXL9330
Polycarbonate and may generate an ignition-capable level of electrostatic charge
under certain extreme conditions. The user should ensure that the equipment is
not installed in a location where it may be subjected to external conditions (such as
high-pressure steam), which might cause a build-up of electrostatic charge on non-
conducting surfaces.
WARNING
Failure to follow these instructions could result in death or serious injury.
•
Make sure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
The OneWireless Adapter can only be opened for battery insertion and
activation, or installed in a potentially hazardous location when the location is
declared to be non-hazardous.
•
Before mounting the OneWireless Adapter to an existing field transmitter, verify
that the instruments are installed in accordance with applicable intrinsically safe
or nonincendive field wiring practices.
•
Verify that the certification parameters of the OneWireless Adapter are
consistent with the appropriate hazardous locations certifications.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following conditions: This device may not cause harmful interference. This device
must accept any interference received, including interference that may cause
undesired operation.
This device must be installed to ensure a minimum antenna separation distance of
20 cm from all persons.