34
OWA 100 Adapter User Manual
Rev. 2
July
2011
Parameter
Routing vs. non-
Routing"
Specification - Unit can be set as a Field Routing or non-Field Routing device; the
number of routing devices is set by the system manager.
Using the device as a routing device will impact battery life, the more messages routed
through a device, the greater the impact on battery life.
CE Conformity
These transmitters conform with the protection requirements of European Council
Directives: 2004/108/EC, the EMC Directive and 1999/5/EC, the Telecommunications
Directive per EN 300 328, V1.7.1 (2004-11), EN 300 489-1, V1.6.1 (2005-09), EN 300
489-17, V1.2.1 (2002-08), EN 301 893 V1.4.1 and EN 61326-1:2005, Electrical
Equipment for Measurement, Control and Laboratory Use – EMC Requirements
* Actual range can vary depending on site topography.
Physical Specifications
Parameter
Description
Mounting
½” NPT or M20 Stainless Steel fitting that allows the adapter to be attached directly to the
conduit entry of any 2 or 4-wire HART device (standard options). Mounting should result
in the antenna being vertically oriented. An optional Remote Mounting Kit is available.
Housing
Molded Lexan Polycarbonate
V0 Rating and UV Stable.
Meets NEMA 4X (hosedown and corrosion resistant), IP 66 (dust/tight/hosedown).
Dimensions
See Specification sheet.
Net Weight
Approximately 1.0lb/(0.45Kg)