INSTALLATION GUIDE
This Installation Guide is for informational purposes only. Honeywell makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious.
Specifications are subject to change without notice.
PLT-01558, Rev A.1
PLT-01558, Rev A.1
INSTALLATION GUIDE
Page 1
Parts
1 – OmniClass Reader
1 – Installation Guide
2 – #6-32 x .375” Phillips machine screws
3 – #6-32 x .375” spanner security screw
2 – 7-pin Terminal connectors for terminal readers
1 – 10-pin Terminal connector
Recommended
•
Cable, 5-9 conductor (Wiegand or Clock-and-Data), 4 conductor Twisted Pair Over-All Shield and UL
approved, Belden3107A or equivalent (OSDP)
•
Linear DC power supply
•
Metal or plastic junction box
•
Security tool (for anti-tamper screw) HID 04-0001-03
•
Drill with various bits for mounting hardware
•
Mounting hardware
•
Reader spacer when mounting on or near metal or metal junction boxes - see How to Order Guide
•
IP65 Mounting gasket, recommended for outdoor installation
•
Back box
Specification
PRODUCT
BASE PART
NUMBER
INPUT
VOLTAGE (VDC)
CURRENT
1
OPERATING
TEMPERATURE
5
CABLE LENGTH
6
REGULATORY
REF NUMBER
STANDBY
AVG
2
MAX AVG
3
PEAK
4
OM30/OM32 (R10)
7
900N
5 - 16VDC
60mA
95mA
200mA
-30° to 150° F
(-35° to 65° C)
Communication Lines
Wiegand
= 500 ft - 22 AWG (152 m)
300 ft - 24 AWG 91 m)
RS-485
= Max bus length
4000 ft - 24 AWG (1,219 m)
Max length between nodes:
1640 ft - 24 AWG (500m)
R10Ex
1
x
2
x
3
OM31/OM33 (RP10)
7
900P
75mA
100mA
RP10Ex
1
x
2
x
3
OM15/OM17 (R15)
7
910N
60mA
95mA
R15Ex
1
x
2
x
3
OM16/OM18 (RP15)
7
910P
75mA
100mA
RP15Ex
1
x
2
x
3
OM40/OM42 (R40)
7
920N
65mA
95mA
R40Ex
1
x
2
x
3
OM41/OM43 (RP40)
7
920P
85mA
100mA
RP40Ex
1
x
2
x
3
OM55/OM57 (RK40)
7
921N
5.5 - 16VDC
85mA
100mA
220mA
RK40Ex
1
x
2
x
3
OM56/OM58 (RPK40)
7
921P
95mA
105mA
RPK40
Ex
1
x
2
x
3
Bluetooth Specifications
OPERATING TEMPERATURE
FREQUENCY
FCC & IC IDS
-15° to 150° F (-25° to 65° C)
2.4 - 2.480 GHz
FCC-ID: JQ6-ICLASSBTM
IC-ID: 2236B-ICLASSBTM
The final product, containing the modular transmitter must be labeled with its own FCC ID and IC ID. If the FCC & IC ID is not visible, when the module is installed inside
another device, then the final assembly label must contain the FCC and IC ID numbers with a statement such as follows: “Contains Transmitter Module with FCC ID JQ6-
ICLASSBTM and IC ID 2236B-ICLASSBTM”.
1 Communication protocols other than Wiegand or Clock & Data (for control
panels), as well as credential interfaces over BLE (not applicable for 9xxL
models), require an additional hardware module which increases current
by 40mA.
2 Standby AVG - RMS current draw without a card in the RF field.
3 Maximum AVG - RMS current draw during continuous card reads. Not
evaluated by UL.
4 Peak - highest instantaneous current draw during RF communication.
5 When configured for Bluetooth Operating Range is -13° to 150° F
(-25° to 65° C)
6 Wiegand Cable Lengths:
100 ft (30.5 m) 22 AWG @ 5 - 6.4VDC
500 ft (152 m) 22 AWG @ 6.5 - 16VDC
7 Mobile Enabled Products, see specifications below.
UL Reference Number Deciphering
x
1
Reader Colors:
K = Black
x
2
Wiring:
N = Pigtail
T = Terminal
5 = 5 meter Pigtail
x
3
Communications:
N = No Module
R = RS-485 (OSDP)
L = Indala Prox
B = Bluetooth