Installation Instructions / OmniAssure Touch Square

3

3.6

Test the reader / Commissioning

Apply power (the green LED indicates power) and present a valid creden-

tial. The light ring should flash and the sounder should produce a short

tone indicating a successful read. If the Host system is connected the light

ring and sounder should follow the functionality of the Host system.

3.7

Cable specification

– The reader is supplied with 2 m (6 ft.) of shielded, 8-conductor

0,14 mm² (AWG 26) cable which may be extended with the length

and size of cable listed below.

min. conductor size

for panel power suppy

max. cable

length

9,5 V

1)

12 V

18 V

Interface

meters

feet

mm² AWG mm² AWG mm² AWG

61

200

0,55 20 0,33 22 0,22 24

91

300

0,82 18

0,5

20 0,33 22

Wiegand / 

RS-485

(cable

power)

152

500

1,35 16 0,81 18 0,54 20

RS-485 

(local power) 1220

4000

0,16 mm² / AWG 25

1)

to ensure that the reader power supply is at least 7 V DC

3.8

Wire assignments

The connection must be carried out in de-energized state! Risk of

damage!

To ensure reliable functioning, ensure that a possible extension of the 4 m

connecting cable does not exceed 152 m (condition: no external voltage

supply unit is required). For extension purposes up to 152 m an additional

JY(ST)Y (6x2x0.6 mm) cable can be used.
The reader can be used remotely for extension purposes at a distance of

max. 1220 m. We recommend using a Cat 5 connecting cable (condition:

an external voltage supply unit for the reader is required).

In general, by use of RS-485 interface:

 When the reader is the last user

on the RS-485 bus, a 120 Ω end-of-line resistor (from TRX+ to TRX-)

must be installed in front of the reader. For further information, refer to the

description of the corresponding controller.

Interface

Wire color

Wiegand

RS-485

red

POWER (+U_b)

POWER (+U_b)

black

GND (0 V)

GND (0 V)

white

D1

TRX+

green

D0

TRX-

blue

Hold line

do not connect

yellow

Buzzer

do not connect

orange

LED green

do not connect

purple

Tamper

do not connect

Caution

Floating communication lines may cause spurious emissions, invalidating

certification. Ensure all communication lines are properly biased and ter-

minated.

Input Hold line

This input makes it pos-

sible to switch 2 read-

ers in parallel (e.g. at

NetAXS).

Reader 1

Reader 2

Hold line 2

Hold line 1

NetAXS

GND

Tamper line

Physical tamper switches:

– tear-off
– enclosure
The  electronic  switch  opens  when

the operating vU_b fails.

mechanical tamper switch
electronic tamper switch

Tamper line

4

Operation

When  a  credential  is  read  successfully,  the  light  ring  lights  briefly,  the

sounder sounds a short tone and the credential associated code is sent

to the Host system.
The light ring and sounder are also controllable by the Host system.
Reader output formats are determined by the personalization of the cre-

dential and/or configuration of the reader; on SmartTech and MultiTech

readers  the  behaviour  of  the  light  ring  and  sounder  can  be  modified

through configuration.

4.1

Short briefing of buttons and LEDs

OmniAssure Touch Square 16 key

A

B

I

E

C

F

D

G

H

K

J

A

Numeric keypad for PIN entry

(PIN= Personal identification number)

B

LED light ring

C, E, G, I

Not used

D

LED green

F

LED yellow

H

Duo LED red/green

J

Acknowledge: execute the PIN code / Activate

the BLE credential

K

Clear PIN code entry

Summary of Contents for OmniAssure

Page 1: ...lish Russian Turkish and Mandarin GLOBAL DACH www security honeywell com www security honeywell de Model name Smart proX Mobile Color Item no X X X Black OT4800BHONG OmniAssure Touch Square X X Black OT4700BHONG X X X Black OT4816BHONG OmniAssure Touch Square 16 key X X Black OT4716BHONG X X X White OT4800WHONG OmniAssure Touch Square X X White OT4700WHONG X X X White OT4816WHONG OmniAssure Touch ...

Page 2: ...recommended 3 1 1 Mounting height In order to operate the keypad and read the indications optimally install the reader at a height of 130 to 140 cm 51 to 55 above the floor 3 1 2 Necessary cable reserve In order for the reader to be able to dismounted when necessary there must be a sufficient cable reserve in the direct vicinity of the reader Depending on the type of mounting the cable reserve can...

Page 3: ...er on the RS 485 bus a 120 Ω end of line resistor from TRX to TRX must be installed in front of the reader For further information refer to the description of the corresponding controller Interface Wire color Wiegand RS 485 red POWER U_b POWER U_b black GND 0 V GND 0 V white D1 TRX green D0 TRX blue Hold line do not connect yellow Buzzer do not connect orange LED green do not connect purple Tamper...

Page 4: ...F UID L WG37 DF UID L WG56 EM Prox WG26 EM Prox WG32 EM Prox WG34 EM Prox WG40 HID MF UID WG26 MF UID WG32 MF DF UID WG26 MF DF UID WG32 MF DF UID WG37 MF DF UID WG56 MF DF UID L WG26 MF DF UID L WG32 MF DF UID L WG37 MF DF UID L WG56 OSDP OmiAssure OES WG38 HID UniKey OSDP OmiAssure OES WG38 OmniAssure OES WG38 OmniAssure OES WG38 UniKey 38 bit EM Prox EM4450 WG32 QKey WG34 2 Config App for progr...

Page 5: ...th the instructions may cause harmful interference to radio com munications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following...

Page 6: ......

Page 7: ......

Page 8: ...Honeywell Commercial Security Novar GmbH Johannes Mauthe Straße 14 D 72458 Albstadt www honeywell com security de P30742 10 0G0 01 2019 05 07 2019 Novar GmbH ...

Reviews: