98(110) CONTROL
KEYPAD
7
7.3.6.7 Hardware
settings
NOTE:
The
Hardware settings submenu
is protected with a password (see chapter Password (S6.5.1)).
Store the password in a safe place!
In the
Hardware settings submenu (S6.7)
under the
System menu
you can further control some functions
of the hardware in your frequency converter. The functions available in this menu are
Internal brake
resistor connection, Fan control, HMI acknowledge timeout and HMI retry.
Internal brake resistor connection (P6.7.1)
With this function you can tell the frequency converter, whether the internal brake resistor is connected or
not. If you have ordered the frequency converter with an internal brake resistor, the default value of this
parameter is
Connected.
However, if it is necessary to increase braking capacity by installing an external
brake resistor, or if the internal brake resistor is disconnected for another reason, it is advisable to change
the value of this function to
Not conn.
in order to avoid unnecessary fault trips.
Enter the edit mode by pushing the
. Use the
to change the internal
brake resistor status. Accept the change with the
or return to the previous level with the
Note!
The brake resistor is available as optional equipment for all classes. It can be installed internally in
classes FR4 to FR6.
Figure 7-21. Internal brake resistor connection
Fan control (P6.7.2)
This function allows you to control the frequency converter’s cooling fan. You can set the fan to run con-
tinuously when the power is switched on or depending on the temperature of the unit. If the latter function
has been selected the fan is switched on automatically when the heat sink temperature reaches 60
°
C or
the converter is in RUN state. The fan receives a stop command when the heat sink temperature falls to
55
°
C and the converter is in STOP state. However, the fan runs for about a minute after receiving the stop
command or switching on the power, as well as after changing the value from
Continuous
to
Temperature.
Note!
The fan runs always when the drive is in RUN state.
S1
Î
S8
READY
I/Ot erm
READY
I/Ot erm
READY
I/Ot erm
enter
READY
I/Ot erm
READY
I/Ot erm
P1
Î
P4
System Menu
HW settings
InternBrakeRes
Connected
Not conn.
InternBrakeRes
Connected
InternBrakeRes