Installing the Kit PSU7A Assembly in a Back Box (Continued)

3

11

22

IF PSU7A IS A REPLACEMENT FOR 'OLD' 
VERSION WITH INTEGRAL MAINS LEAD: Remove 
the existing mains terminal block and use its screw to 
fit terminal block of mains cable PN: 082-254 in its 
place. The cable has a factory-fitted clip which must 
be affixed to the side wall of the back box (at the 
marked cross-hairs - see illustration at right).

YOU MUST ALSO MAKE THE SAFETY 
EARTH CONNECTION (K to L).

IF PSU7A IS A REPLACEMENT FOR 'OLD' 
VERSION WITH INTEGRAL MAINS LEAD: Remove 
the existing mains terminal block and use its screw to 
fit terminal block of mains cable PN: 082-254 in its 
place. The cable has a factory-fitted clip which must 
be affixed to the side wall of the back box (at the 
marked cross-hairs - see illustration at right).

YOU MUST ALSO MAKE THE SAFETY 
EARTH CONNECTION (K to L).

!!

230 VAC,

50/60 Hz

H

I

E

L

G

J

F

K

M

NN

LL

MF: 5A (T) 250V HRC

MF: 5A (T) 250V HRC

LL

NN

230V    (a.c.), 5A

230V    (a.c.), 5A

1

The 230VAC mains input wiring (H) must be 

terminated at the mains termination block (I) in the 
top right-hand side of the Back Box. The PSU mains 
cable (E) is factory-fitted to the termination block. 
Push the mains cable's connector into the socket on 
the PSU7A. Pull tight the cable clip at the side of the 
back box.

2

The blade connector (G) to the left of the terminal 

block is also used to earth the main chassis; the 
other end of this earth lead (J) connects to the main 
chassis rear enclosure earth terminal. The safety 
earth is provided by a short factory-fitted lead (K) 
from the mains termination block to the blade 
connector (L) on the Back Box side wall. This blade 
connector is also used to earth the DTP/Booster 
module earth lead (M).

Mains and Safety Earth Wiring 
Connections

!!

Note:

Connections to the DTP/Booster module kit are shown 

on the instruction sheet (997-267-000-X) supplied with 
that kit.

Note:

All blade connections to earth 

incorporate a locking barb. To make a 
connection push the shrouded 
receptacle on to the earth blade (1). To 
remove this connection, pull the 
shroud (2), NOT the earth wire.

WARNING. Risk of electric shock. Before working 

on mains connections, ensure the mains power 
supply to the panel is disconnected.

Segregate mains wiring from all other wiring.

TRANSIT CABLE CLIP: Before proceeding, CAREFULLY cut 
the cable clip that secures the ferrite cable loop to the front of 
the back box. DO NOT cut the cable clip that secures the 
mains cable to the side of the back box.

TRANSIT CABLE CLIP: Before proceeding, CAREFULLY cut 
the cable clip that secures the ferrite cable loop to the front of 
the back box. DO NOT cut the cable clip that secures the 
mains cable to the side of the back box.

'X'

230 VAC,

50 Hz

H

I

E

C

J

M

K

NN

LL

MF: 5A (T) 250V HRC

MF: 5A (T) 250V HRC

LL

NN

230V    (a.c.), 5A

230V    (a.c.), 5A

VIEW

X

F

Connections in 'original' back box

1

The 230VAC mains input wiring (H) must be terminated at  the 
mains termination block (I) in the  top right-hand side of the 
Back Box. The PSU mains cable (E)  is factory-fitted to the 
termination block. Push the mains cable's  connector into the 
socket on the PSU7A. Pull tight  the cable clip at the side  of 
the back box.

2

One of the blade connectors is used to earth the main  
chassis; the other end of this earth lead (J) connects to the  
main chassis rear enclosure earth terminal. The safety 
earth is provided by a short factory-fitted lead (K) from the  
mains termination block to the another of the blade 
connectors. The fourth blade connector is used to earth the 
DTP/Booster module earth lead (M).

Connections in 'revised' back box

Note:

Connections to the DTP/Booster module kit are shown 

on the instruction sheet (997-267-000-X) supplied with 
that kit.

997-277-000-9, Issue 9 February 2010

Summary of Contents for Notifier PSU7A

Page 1: ...ote Battery PSU Enclosure providing the instructions described below are followed The PSU must be fitted BEFORE installing the main chassis in the Back Box The PSU Assembly is secured to the Back Box or Remote Battery PSU Enclosure using four M4 x 16 SEM screws and nylon spacers A DTP Booster module MUST be fitted to the ID3000 chassis when using a PSU7A OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTA...

Page 2: ...ATTERIES UNTIL INSTRUCTED TO DO SO IN THE INSTALLATION AND COMMISSIONING MANUAL When so instructed connect them to the battery connector iv using the correct cables supplied in the PSU kit Follow the connection procedure given in the manual but note that any references to a connector should be replaced by references to ring terminals ENSURE CORRECT POLARITY 5 Locate the thermistor assembly in clos...

Page 3: ... Connections to the DTP Booster module kit are shown on the instruction sheet 997 267 000 X supplied with that kit Note All blade connections to earth incorporate a locking barb To make a connection push the shrouded receptacle on to the earth blade 1 To remove this connection pull the shroud 2 NOT the earth wire WARNING Risk of electric shock Before working on mains connections ensure the mains p...

Page 4: ... For further details when using the 130Ah batteries refer to instruction sheet 997 270 000 X 1 4 Installing the Kit PSU7A Assembly in a Remote Enclosure Use these knockouts for low voltage connections A B C D 2 CON3 CON3 CON3 I O FS300 TH TH BATT B CON2 CON2 CON2 2 The PSU output is configured using jumper links the three valid options are no links fitted one or both fitted Refer to the table belo...

Page 5: ...s follows 1 Connect the PSU7A Charger Inhibit wiring between the CI connector i and the DTP Booster module in the panel using suitable cables as detailed in the table above Connect to and to 2 Connect the PSU output iii to the DTP Booster module using suitable cables as detailed in the table above to provide the dual transmission path 3 DO NOT CONNECT THE BATTERIES UNTIL INSTRUCTED TO DO SO IN THE...

Page 6: ...panel has a safety earth connection which may be connected to a convenient safety earth bonding point 3 The230VACmainsinputwiring H mustbeterminatedat the mains termination block I in the top left hand side of the Battery PSU Enclosure The PSU mains cable E is factory fitted to the termination block Push the mains cable s connector into the socket of the PSU7A Pull tight the cable clipatthesideoft...

Page 7: ...ious page for details The power supply provides dual redundancy of fusing and power connections to the main panel The table below compares the key specifications PSU7A Specifications 1 Charged to 80 within 24 hours 2 Currents in this table refer to the maximum current available at the output of the DTP Booster 3 Refer to instruction sheet 997 270 000 X for the sizes and battery capacity of other e...

Reviews: