Charger
Backup
CON3 & CON2 Links
Current
Batteries (Ah)
Charger
Backup
CON3 & CON2 Links
Current
Batteries (Ah)
To fit the PSU7A assembly (A) into a remote battery enclosure,
proceed as follows:
1
Place a nylon spacer (B) over each of the four stand-offs (C)
on the rear wall of the enclosure. Screw an M4 X 16 SEM
screw (D) approximately 2 or 3 rotations into each stand-off.
DO NOT FULLY TIGHTEN. The PSU7A assembly must be
orientated so that the mains connector is to the upper left.
Position the PSU7A over the screws, then tighten them to
secure the assembly in place.
Procedure for Fitting PSU kit into a Remote
Battery/PSU Enclosure
IMPORTANT NOTE when using 130Ah
Battery Back Up....
To ensure correct operation of the PSU7A when used with
130Ah back up batteries, two remote enclosures MUST be
used. The PSU7A must be installed in one enclosure and ALL
the batteries must be installed in the other enclosure. For
further details when using the 130Ah batteries, refer to
instruction sheet 997-270-000-X.
IMPORTANT NOTE when using 130Ah
Battery Back Up....
To ensure correct operation of the PSU7A when used with
130Ah back up batteries, two remote enclosures MUST be
used. The PSU7A must be installed in one enclosure and ALL
the batteries must be installed in the other enclosure. For
further details when using the 130Ah batteries, refer to
instruction sheet 997-270-000-X.
1
4
Installing the Kit PSU7A Assembly in a Remote Enclosure
Use these knockouts for
low voltage connections
A
B
C
D
2
CON3
CON3
CON3
I/O
F
S
3
0
0
TH- TH+ BATT + B
CON2
CON2
CON2
2
The PSU output is configured using jumper links; the three
valid options are: no links fitted, one or both fitted. Refer to
the table below left for guidance on the fitting of jumper links
on the PSU PCB in the appropriate position. Jumper
headers CON 2 and CON 3 are located to the left of the
thermistor wiring connectors when the PSU is orientated
with the wiring connectors at the bottom (as illustrated).
CAUTION: Incorrect fitting of the link(s) or failing to fit both
links with 78Ah or 130Ah backup batteries, will
reduce the power available to the panel during
quiescent operation or invalidate the battery
charging requirement of EN54 Part 4.
7.3
79 - 130
CON 2 & 3
7.3
79 - 130
CON 2 & 3
4.5
42 - 78
CON 2 ONLY
4.5
42 - 78
CON 2 ONLY
IMPORTANT NOTE
If the PSU7A is used in the remote battery
enclosure the enclosure must be mounted in close
association with the cie. Power cables must be
routed through steel conduit connecting the two
enclosures.
IMPORTANT NOTE
If the PSU7A is used in the remote battery
enclosure the enclosure must be mounted in close
association with the cie. Power cables must be
routed through steel conduit connecting the two
enclosures.