N200-310-00
I56-6591-001
Table 1: Sounder Tones
No
Pattern
Nominal
Frequency (Hz)
Switching Cycle
2nd Stage
Tone
2
Alternating
800/970
1Hz
8
3
Alternating
800/970
2Hz
8
4
Alternating
2400/2900
3Hz
10
5
Alternating
2500/3100
2Hz
10
6
Alternating
988/645
2Hz
8
7
Continuous
660
1
8
(3)
Continuous
970
2
(3)
9
Continuous
1200
2
10
Continuous
2850
4
11
Sweep
150‐1000
Rising from 150Hz to 1000Hz (10s), 40s
@ 1000 Hz, falling from 1000Hz to 150Hz
(10s), 20s @ 150Hz (Total 80s)
22
13
(1)
Sweep
500 ‐ 1200
0.25s off, 3.75s on
12
14
(1)
Intermittent
660
3.33Hz 150ms on, 150ms off
7
15
(1)
Intermittent
970
0.8Hz 0.25s on, 1s off
8
16
(1)
Intermittent
970
0.5Hz 1s on, 1s off
8
17
(1)
Intermittent
2850
1Hz
10
18
(1)
Intermittent
970
1Hz 500ms on, 500ms off
8
19
(1)
Intermittent
950
0.22Hz (0.5s on, 0.5s off) rpt x3, 1.5s off
12
20
(1)
Continuous
800
22
21
(1)
Sweep
400‐1200
(0.5s on, 0.5s off) rpt x3, 1.5s off
12
22
Sweep
1200 ‐ 500
0.99Hz 1s on, 0.01s off
20
23
Sweep
2400 ‐ 2850
7Hz
10
24
(1)
Sweep
500 ‐ 1200
(0.5s off, 3.5s on)
8
25
Sweep
800 ‐ 970
50Hz
8
26
Sweep
800 ‐ 970
7Hz
8
27
Sweep
800 ‐ 970
1Hz
8
28
Sweep
2400 – 2850
50Hz
10
29
Sweep
500 – 1000
7Hz
8
30
Sweep
500 – 1200 – 500
0.166Hz rise 1s, stable 4s, fall 1s
8
31
Sweep
800 – 1000
2Hz
8
32
Sweep
2400 ‐ 2850
1Hz
10
33
(2)
Continuous
4000
5
36
(1)
Intermittent
660
0.05Hz 6.5s on, 13s off
7
37
(1,2)
Intermittent
660
0.277Hz 1.8s on, 1.8s off
7
38
(1,2)
Intermittent
2850
4Hz (150ms on, 100ms off)
10
Notes:
(1) Tones not affected by intermittent user pattern
(2) Only available through Advanced Protocol commands
(3) Default tones; (Default volume = HIGH)
Sounder Output data, in accordance with EN54-3, is available in Document Ref: S00-7000-000.
Note: LOW volume tones are not approved to EN54-3.