FIGURE 2. WIRING DIAGRAM

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

UL Listed Compatib

le

Control P

anel

CAUTION: Do not loop wire under 
terminal 1 or 2.  Break wire run to 
supervise connections.

CLASS A OPTIONAL WIRING

Remote 

Annunciator

(–)
(+)

RA

+

+

RA

+

+

RA

+

+

 

C0129-10

TAMPER-RESISTANCE

Photoelectric and temperature sensors include a tamper-resistant capability 
that prevents their removal from the base without the use of a tool. Refer to 
the base manual for details on making use of this capability.

TESTING

Before testing, notify the proper authorities that the system is undergoing 
maintenance, and will temporarily be out of service. Disable the system to 
prevent unwanted alarms.

All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors 
offer maximum performance when tested and maintained in compliance with 
NFPA 72. 

The sensor can be self-tested or manually tested as described below.

SELF-TEST TESTING

A.  Functional and Smoke-Entry Tests

The Notifier system with Self-Test sensors can carry out both functional tests 
and smoke entry tests using the Self-Test function. The Self-Test sensor gener-
ates a controlled amount of smoke which is directed into the sensing cham-
ber, testing the optical chambers response to real smoke. It also measures the 
amount of time it takes to evacuate smoke from the chamber to determine if 
there is anything masking smoke entry points on the sensor.

1.   Use the associated app and gateway (see Connected Life Safety Services 

guides).

2.   Initiate self-test from app. Wait at least 30 seconds before communicating 

with the device; wait at least 90 seconds before moving or re-cycling.

3.   Take appropriate action based on the outcome of the testing results. If it 

has failed, the device should be considered for cleaning or replacement.

NOTE: For safer testing the fire system can remain active while Self-Test is 
in progress. The process will delay any alarm input signal from the SLC in-
cluding pull stations, input modules and other sensors (not undergoing Self-
Test) by a maximum of 30 seconds. Multiple loops and panels may be tested 
simultaneously.

B.  Heat Test

The sensor places enough energy into the thermistor to allow it to register 
heat and then measures the time it takes to cool down after this heating cycle 
has been completed.

1.   Use the same process as described in FUNCTIONAL AND SMOKE ENTRY 

TEST. The process will automatically note that the FSP-951T-SELFT has a 
heating element.

2.   Take appropriate action based on the outcome of the testing results. If it 

has failed there may be an issue with the thermistor and the device should 
be considered for cleaning or replacement

C.   Visual  Inspection

This sensor contains a wireless beacon (only active during Self-Test process) 
which is designed to communicate with the Honeywell Connected Life Safety 
Services app in order to prove the successful completion of the visual inspec-
tion of any Self-Test sensor.

1.   A range of Self-Test sensors can be placed into a beaconing mode from the 

supporting app.

2.   The App will display all selected Self-Test devices in range of your smart 

phone and will place the device with the strongest signal at the top your 
App display. The App will also provide details on the device address, loca-
tion and label. (For further details on the associated app and gateway see 
Connected Life Safety Services guides).

3.   Once the sensor is in beaconing range of your smart phone, you must 

verify the completion of the visual inspection of the sensor via the App 
(recording any remedial action required if necessary). Criteria for success-
fully passing the visual inspections is available to review in the relevant 
section of NFPA 72 guidance.

4.   If the label of the self-test sensor is incorrect, you can update this on the 

App (subject to holding the relevant user licence), which will upload it to 
the system when you pair the device with the Connected Life Safety Ser-
vices gateway on completion of the visual inspection.

SELF-TEST TOKENS 

If your license requires Self-Test tokens in order to activate the Self-Test pro-
cess, please refer to your Connected Life Safety Services guides in order to 
purchase the required volume of tokens to complete testing on your project.

MANUAL TESTING

A.  Functional: Magnet Test (P/N M02-04-01 or M02-09-00) 

 This sensor can be functionally tested with a test magnet. The test magnet 
electronically simulates smoke in the sensing chamber, testing the sensor elec-
tronics and connections to the control panel.

1.   Hold the test magnet in the magnet test area as shown in Figure 3.
2.  The sensor should alarm the panel.

 Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
Coded signals, transmitted from the panel, can cause the LEDs to blink, latch 
on, or latch off. Refer to the control panel technical documentation for sensor 
LED status operation and expected delay to alarm.

B.  Smoke Entry

 Sensitivity readings are available through the FACP. Refer to the manufac-
turer’s published instructions for proper use. 

 

Additionally, canned aerosol simulated smoke (canned smoke agent) may 
be used for smoke entry testing of the smoke detector. Tested and approved 
aerosol smoke products include:

Manufacturer

Model

HSI Fire & Safety

25S, 30S (PURCHECK)

SDi

SMOKE CENTURIAN, SOLO A10, 
SMOKESABRE, TRUTEST

No Climb

TESTIFIRE 2000

When used properly, the canned smoke agent will cause the smoke detector 
to go into alarm. Refer to the manufacturer’s published instructions for proper 
use of the canned smoke agent.

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 
manufacturer. Misuse or overuse of these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.

C.   Direct Heat Method (Hair dryer of 1000-1500 watts). 

 

 A hair dryer of 1000-1500 watts should be used to test the thermistors. Di-
rect the heat toward either of the two thermistors, holding the heat source 
approximately 12 inches (30 cm) from the detector in order to avoid dam-
aging the plastic housing. The detector will reset only after it has had suf-
ficient time to cool. Make sure both thermistors are tested individually.

D.   Multi-Criteria Method. 

 

 A Testifire® by SDi provides testing of the smoke and heat sensors. Consult 
the manufacturer’s published instructions for complete instructions.

A sensor that fails any of these tests may need to be cleaned as described 
under CLEANING, and retested. 

When testing is complete, restore the system to normal operation and notify 
the proper authorities that the system is back in operation.

CLEANING

Before removing the detector, notify the proper authorities that the smoke 
detector system is undergoing maintenance and will be temporarily out of 
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.

1.  Remove the sensor to be cleaned from the system.
2.   Remove the sensor cover by pressing firmly on each of the four removal 

tabs that hold the cover in place. (See Figure 4.)

  

I56-6783-000 

 

 1/6/2021

Summary of Contents for NOTIFIER FSP-951T-SELFT

Page 1: ... condensing Operating Temperature Range 32 F to 115 F 0 C to 47 C Storage Temperature Range 4 F to 140 F 20 C to 60 C Air Velocity 0 to 4000 ft min 0 to 1219 2 m min Air Velocity using Self Test 0 to 300 ft min 0 to 304 8 m min Height 2 0 51 mm installed in B300 6 Base Diameter 6 2 156 mm installed in B300 6 Base 4 1 104 mm installed in B501 Series Base Weight 3 5 oz 100 g Isolator Load Rating 0 0...

Page 2: ...ne you must verify the completion of the visual inspection of the sensor via the App recording any remedial action required if necessary Criteria for success fully passing the visual inspections is available to review in the relevant section of NFPA 72 guidance 4 If the label of the self test sensor is incorrect you can update this on the App subject to holding the relevant user licence which will...

Page 3: ...CATION When configured at the fire alarm control panel this detector is capable of op erating in a special application mode such that it has a higher sensitivity than is normally allowed by UL 268 for areas where early warning is important In this mode the detector does not comply with the Cooking Nuisance Smoke Test Detectors Sampling ports set to the special application mode are not suitable for...

Page 4: ...g etc are adequately protected to avoid tampering of the system that could result in information disclosure spoofing and integrity violation FCC STATEMENT This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may caus...

Reviews: