background image

FIGURE 3. FEATURES OF THE PHOTO DETECTOR

Magnet 

Test 

Marker

LED

Base 

Alignment 

Notch

Magnet Test Marker

Base Alignment Notch

LED

 C2021-00

FIGURE 4. CLEANING THE PHOTO DETECTOR 

 

Cover 

Removal 

Tabs

Sensor Cover

Sensing Chamber 

Cover and Screen

Sensing Chamber 

 C2022-00

SPECIAL APPLICATION

When configured at the fire alarm control panel, this detector is capable of op-
erating in a special application mode such that it has a higher sensitivity than 
is normally allowed by UL 268 for areas where early warning is important. In 
this mode, the detector does not comply with the Cooking Nuisance Smoke 
Test. Detectors (Sampling ports) set to the special application mode are not 
suitable for use in areas where cooking appliances may be used. If cooking 
appliances are used within the protected space, a normal application detector 
or normal application mode must be used for that area.
Special application mode is not for general use and the detector may be more 
prone to false alarms if used in unsuitable environments. While no list is 
all-inclusive, some examples of unsuitable environments for special applica-
tion mode are areas with airborne particulate or aerosols including sawing, 
drilling, and grinding operations, textile or agricultural processing, or areas 
with engines that are not vented to the outside. A complete list of aerosol and 
particulate sources is available in the Annex of NFPA 72. 
Suitable environments for special application mode could include early warn-
ing for hospitals, museums, assisted living and other areas that do not have 
airborne particulate or aerosols. 
Refer to the fire alarm control panel documentation for information on how to 
configure the detector for special application mode.

  

I56-6782-000 

 

 1/6/2021

Summary of Contents for NOTIFIER FSP-951-SELFT

Page 1: ...ity using Self Test 0 to 300 ft min 0 to 304 8 m min Height 2 0 51 mm installed in B300 6 Base Diameter 6 2 156 mm installed in B300 6 Base 4 1 104 mm installed in B501 Base Weight 3 5 oz 100 g Isolator Load Rating 0 0063 Please refer to your isolator base module manual for isolator calculation instructions UL 268 listed for Open Air Protection This sensor must be installed in compliance with the ...

Page 2: ...it to the system when you pair the device with the Connected Life Safety Ser vices gateway on completion of the visual inspection SELF TEST TOKENS If your license requires Self Test tokens in order to activate the Self Test pro cess please refer to your Connected Life Safety Services guides in order to purchase the required volume of tokens to complete testing on your project MANUAL TESTING A Func...

Page 3: ...ithin the protected space a normal application detector or normal application mode must be used for that area Special application mode is not for general use and the detector may be more prone to false alarms if used in unsuitable environments While no list is all inclusive some examples of unsuitable environments for special applica tion mode are areas with airborne particulate or aerosols includ...

Page 4: ...tected to avoid tampering of the system that could result in information disclosure spoofing and integrity violation FCC STATEMENT This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation WA...

Reviews: