Configuration and Programming
Configuring the FACP
3.3 Configuring the FACP
3.3.1 Software Type ID Codes
ACPS-610 points must be programmed at the FACP with Software Type ID codes. Refer to the
panel programming manual for specific Software Type ID codes. Table 3.3 below gives general
categories of codes that may be used for the AFP-100, AFP-200, AFP-300/400, AFC-600,
AM2020/AFP-1010 FACPs. See FACP manual for more information.
Table 3.3 Software Type ID Codes, AFP-100, AFP-200, AFP-300/400, AFC-600,
AM2020/AFP-1010
Table 3.4 below categorizes codes used with the NFS FACPs.
Table 3.4 NFS-3030/NFS2-3030, NFS-640/NFS2-640, NFS-320 Software Type Codes
3.4 Two Stage Alert/Evacuation (Canada Only)
3.4.1 Addressing in Two-Stage Mode
Two Stage Alert/Evacuation is a mode option for use in Canada only, with the NFS-3030/NFS2-
3030, NFS-640/NFS2-640, NFS-320, or AM2020/AFP1010. In this mode each coded NAC
output operates in one of two stages: alert or evacuation. The alert stage generates a pulsing output
of 20 pulses per minute: the evacuation stage generates an output in the NFPA Temporal Pattern
(Canadian 1), March Time--120 ppm--(Canadian 2), or a continuous tone (Canadian 3).
Select the Two Stage mode from the Coding Type worksheet (page 33). Any individual ACPS-610
output circuits must be set to the coded NAC option on the corresponding Output Configuration
Worksheet in PK-PPS (page 32).
When the ACPS-610 is set to dual-stage, each output circuit uses two control addresses, even if the
circuit is not configured for dual-stage (i.e. not a coded NAC). The installer should ascertain that an
appropriate block of consecutive FACP addresses is available prior to addressing an ACPS-610 in
Two Stage. Table 3.1 on page 26 shows Two Stage addressing and address consumption.
The first address for each output does one of three things:
1.
If the output is a coded NAC, activating the first associated address activates Stage 1 (alert).
Point Type
Allowable Software Type ID Codes
Trouble Points
Software Type ID Codes for trouble monitors
NAC Points
Software Type ID Codes for supervised NAC circuits
+24V Relay Points
Software Type ID Codes for relay circuits
Point Type
Module
Type
NFS-3030/NFS2-3030
NFS-640
NFS2-640
NFS-320
VeriFire Tools for NFS-
3030/NFS2-3030, NFS-
640/NFS2-640, and NFS-320
Type Code
Label
FlashScan
Type
Type Code
Label
Type Code
Label
FlashScan
Type
Trouble Points
Monitor
Power Monitr
PS Mon
Power
Monitr
Power Monitr
PS Monitor
NAC Points
Control
Control
PS NAC
Control
Control
PS Control
+24V Relay
Control
Relay
PS Relay
Relay
Relay
PS Relay
NOTE:
When a UPS is used, program the associated monitor module with a trouble point Type
ID from Table 3.3.