ACPS-610/E Manual —
P/N 53018:A1 07/31/2007
33
Programming the ACPS-610
Configuration and Programming
3.2.8 Global Settings
Figure 3.7 PK-PPS: Coding Type
Coding Type
Code type is a global setting that applies to all NAC outputs configured as
C
ODED
. (See
Section 3.2.6 on page 30.) NAC codes can be generated internally or they can come from an
external source via the power supply’s UZC sync input (TB1).
Choose the internal or external coding for all coded NAC outputs.
E
XTERNAL
(UZC):
The NAC sends a signal that is determined by an external source via the
power supply’s UZC sync input (TB1). Select this option when the power supply will be
connected (via TB1) to an external coded signal. This option will not be available if the
UZC is already configured to accept a synchronized signal.
M
ARCH
T
IME
:
The NAC sends a pulsed signal of 120 PPM (Pulses Per Minute).
T
EMPORAL
:
The NAC sends a pulsed signal in a pattern of three cycles of 0.5s on/off
followed by 1.5s off. Temporal is the standard NFPA 72 evacuation pattern.
C
ANADIAN
:
T
WO
S
TAGE
1:
The NAC sends a dual-stage signal of Alert tone followed by a
temporal pattern.
T
WO
S
TAGE
2:
The NAC sends a dual-stage signal of Alert tone followed by 120 PPM
(March Time).
T
WO
S
TAGE
3:
The NAC sends a dual-stage signal of Alert tone followed by a
continuous tone.
P
K
-PPS
_C
od
eTyp
es.j
p