N20, N34 SERIES CN7220, CN7234

 

CN0B-0341CH33 R0407 

4

 

Manual Adjustment 

 
IMPORTANT

 

In order to prevent equipment damage, you must 
remove power before manual adjustment.
 

 

After removing power,

 

the gear train can be disengaged using 

the declutch button, permitting the actuator shaft to be manually 
rotated to any position. The feedback signal will then follow the 
new position. 

 

Limitation of Rotation Stroke 

 

Two mechanical end limits (adjustable in 3° increments) are 
provided (20 Nm [177 lb-in] models, only) to limit the angle of 
rotation as desired (see Fig. 7).

 

 

 

 

 

 

 
 
 
 
 

              Fig. 7. Mechanical end limits 

 
The mechanical end limits must be securely fastened in place 
as shown in Fig. 8. Specifically, it is important that they 
properly mesh with the rotational angle scales when the 
screws are tightened. 
 

 
 
 
 
 
 
 
 
 
     Fig.8. Correct / incorrect tightening of end limits 
 

Override 

If terminal 3 of the terminal strip (see section “Wiring Diagrams” 
on page 5) is unplugged, the stroke will be 0%; reversing the 
rotation direction using the rotation direction switch will result in 
a max. stroke of 100%. If terminal 3 is jumped with terminal 1 
(24 V), the stroke will be 50%.

 

 
 
 
 
 
 
 

 

INSTALLATION 

 

These actuators are designed for single-point mounting. 

IMPORTANT

 

In order to prevent equipment damage, you must 
remove power or set the rotation direction switch to

 

the

 “Service/Off” position before manual operation.

 

Mounting Instructions 

All information and steps are included in the Installation   
Instructions supplied with the actuator. 

Mounting Position 

The actuators can be mounted in any position (no IP54 or NEMA2 if 
mounted upside down; see Fig. 9). Choose an orientation permitting 
easy access to the actuator's cables and controls. 
 

 

   Fig. 9. Mounting for IP54

 

 

Mounting Bracket and Screws 

If the actuator is to be mounted directly on a damper shaft, use the 
mounting bracket and screws included in the delivery package. 
 

Self-Centering Shaft Adapter 

The self-centering shaft adapter can be used for shafts having 
various diameters (10...27 mm [3/8...1-1/16”]) and shapes (square or 
round) 

In the case of short shafts, the shaft adapter may be reversed and 
mounted on the duct side. 
 

Stroke Limitation with Mechanical End Limits 

The mechanical end limits (20 Nm [177 lb-in] models, only) enable 

the stroke to be limited from 0...90° in increments of 3°.

 

 
 
 
 
 
 
 

 

 

IP54

IP54

IP54

IP54

Summary of Contents for N20 Series

Page 1: ...ONS Supply voltage 24 Vac 20 50 60 Hz 24 Vdc 10 20 Nominal voltage 24 Vac 50 60 Hz 24 Vdc All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN7220 6 VA 6 W CN7234 8 VA 6 W Ambient limits Ambient operating limits 20 60 5 140 F Ambient storage limits 40 80 40 175 F Relative humidity 5 95 non condensing Safety Protection standard IP54 as per EN 60529 ...

Page 2: ...ry package includes the actuator itself parts 1 through 8 see Fig 2 the anti rotation bracket screws and the SM mounting plate and screws Modulating Control The actuator is capable of being operated by several controllers providing Vdc or mA output Rotary Movement The control signal and the corresponding rotation direction clockwise or counterclockwise can be selected using the rotation direction ...

Page 3: ... Fig 4 Dip switches view with PCB at bottom 4 If it is set to OFF no autoadapting is performed and the control signal map remains constant The autoadapt functionality does not have to be triggered Rather the SmartAct actuator does this automatically when the min and max control signals are provided see Fig 5 the feedback signal is likewise autoadapted Fig 5 Actuator positioning curve Adjusting the...

Page 4: ...e of 100 If terminal 3 is jumped with terminal 1 24 V the stroke will be 50 INSTALLATION These actuators are designed for single point mounting IMPORTANT In order to prevent equipment damage you must remove power or set the rotation direction switch to the Service Off position before manual operation Mounting Instructions All information and steps are included in the Installation Instructions supp...

Page 5: ... two terminal strips including a layout with a description for each of the terminals Fig 11 Actuator with access cover removed Wiring Diagrams CN7220 CN7234 Optional Accessories The following optional accessories can be ordered separately Auxiliary Switch Kit Order no SW2 Connecting cable terminal name 1 24 Vac 24 Vdc 2 24 Vac 24 Vdc 3Y 0 2 10 Vdc 0 4 20 mA control signal supply and signal lines 5...

Page 6: ...n China on recycled paper containing at least 10 post consumer paper fibers Dimensions Automation and Control Solutions Honeywell International Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C ...

Reviews: