Chapter 2 - Planning
2.6.8
Environmental
Operating temperature
+10 °C to +35 °C (50 °F to 95 °F) with a maximum
temperature gradation of 10° per hour.
Note: For Altitudes above 2950 feet , the maximum
operating temperature is derated 1 °F/550 ft.
All temperature ratings shown are for sea level. An
altitude derating of 1 °C per 300 m (1.8 °F per 1,000 ft)
to 3048 m (10,000 ft) is applicable. No direct sunlight
allowed.
Shipping temperature
-30 °C to 50 °C (-22 °F to 122 °F)
Storage temperature
–40 °C to 65 °C (–40 °F to 149 °F)
Maximum wet bulb temperature 28 °C (82.4 °F)
ATTENTION
All temperature ratings described previously
are for sea level. An altitude derating of 1 °C
per 300 m (1.8 °F per 1,000 ft) to 3048 m
(10,000 ft) is applicable. Direct sunlight is not
allowed.
Operating humidity
10% to 80% Relative Humidity with 29 °C (84.2 °F)
maximum dew point
Storage humidity
5% to 95% RH with 33 °C (91 °F) maximum dew
point. Atmosphere must be non-condensing at all
times.
ATTENTION
Storing maximum humidity of 95% is based
on a maximum temperature of 45 °C (113
°F). Altitude maximum for storage
corresponds to a pressure minimum of 70
KPa.
Airborne Contaminants
Airborne Contaminants < 300 angstroms/month
Copper Reactivity Level
Copper Reactivity Level < 3 mm3/m3 parts per billion
H2S Gas concentration
H2S Gas concentration < 10 mm3/m3 parts per billion
S02, S03 Gas concentration
S02, S03 Gas concentration < 1 mm3/m3 parts per
- 16 -