TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
63-2675—01
14
0349
Auto Fan Reset
0—Inactive
1—Reset back to Auto after 2
hours
2—Reset back to Auto after 4
hours
The timer will be set after the user selects the
constant fan speed. Fan will be set to Auto
automatically when time out. The start time is
calculated after initial call for heat/cool is satisfied,
then 2 hour timing begins.
The timer will be set after the user selects the
constant fan speed. Fan will be set to Auto
automatically when time out. The start time is
calculated after initial call for heat/cool is satisfied,
then 4 hour timing begins. Only available for fan coil
or PTAC applications (ISU #170)
0535
Temporary
Occupied Duration
Limit
3
0–12 hours
0 means no limit.
0540
Number of Periods 4
2—2 Periods
4—4 Periods
Does not appear if Non-programmable is chosen (ISU
0160).
Applies to all days of the week. If 2 is selected the
Cancel Period option will not appear on the display.
0580
Minimum
Compressor Off
Time
5
0—Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes
Only shown if system has cool stages in CNV, Heat
Pump, PTAC (ISU 0170).
0600
Heat Temperature
Range Stops
90
40 to 90°F (4 to 32°C)
Only shown if system has heat stages (ISU 0170).
0610
Cool Temperature
Range Stops
50
50 to 99°F (10 to 37°C)
Only shown if system has cool stages (ISU 0170).
0640
Clock Format
12
12—12 Hour
24—24 Hour
0650
Extended Fan-on
time Heat
0
0—Off
90—90 seconds
Not displayed if fan set to fossil or cool only systems
(ISU 0170)
0660
Extended Fan-on
time Cool
0
0—Off
40—40 seconds
Only shown if system has cool stages. (ISU 0170)
0670
Keypad Lockout
0
0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Partial Lockout 3
4—Fully Locked
Unlocked: All functions accessible.
Partial 1: Locks out schedule and system changes.
Partial 2: Locks out schedule, system, and fan
changes.
Partial 3: Locks out schedule, system, fan, and up/
down arrow changes.
Full: Entire interface locked/non-functional.
0680
Temperature
Control Heat
2
1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if system has heat stages (ISU 0170).
Only integral gains are affected by this setting. The
setting affects control operation in all control regimes
(not just recovery or setpoint change).
0685
Recovery Heat
Ramp Rate
5
0-20°F/hour
Only shown if system has heat stages (ISU 0170).
0 disables the ramped recovery (step setpoint change
at period start time).
0690
Temperature
Control Cool
2
1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if system has cool stages (ISU 0170).
Only integral gains are affected by this setting. The
setting affects control operation in all control regimes
(not just recovery or setpoint change).
0695
Recovery Cool
Ramp Rate
3
0-20°F/hour
Only shown if system has cool stages (ISU 0170).
0 disables the ramped recovery (step setpoint change
at the period start time).
Table 6. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting
All Settings
Notes