TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
63-2675—01
12
INSTALLER SETUP NUMBERS (ISU), SETTINGS, AND TESTS (TABLE 6)
Use the Installer System Test to test the heating, cooling and
fan. Refer to the latter portion of Table 6.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling and
fan. The setting chosen for System Type (ISU 0170)
can prevent some System Test Numbers from
appearing.
NOTE: Unless otherwise noted, setup items are accessible
through only the Installer setup and not the User
setup.
Table 6. Installer Setup Menu.
Installer
Setup
Number
Installer Setup
Name
Default
Setting
All Settings
Notes
0120
Date (Year Upper)
20
20—21
Available year range: 2001 - 2178
0130
Date (Year Lower)
08
00-99
Available year range: 2001 - 2178
0140
Date (Month)
6
1-12
0150
Date (Day)
15
1-31 (Month Dependent)
0160
Schedule Options
4
0—Non-Programmable
4—Programmable
0170
System Selection
1—
1—1H/1C Conv
2—1H w/o fan
3—1H with fan
4—1C
5—1H/1C HP
6—2H/1C HP
7—4 pipe Fan Coil
8—2 pipe Fan Coil
9—2 pipe Fan Coil w/ Aux Heat
10—PTAC 1H/1C (Hi speed, Lo
speed Fan)
11—PTAC 2H/1C (Hi speed, Lo
speed Fan)
Relay Y is used for 2 pipe fan coil output relay.
0180
Heat Fan Operation 0
0—Fossil
1—Electric
Only shows up if conventional system with heat
stages and fan capability is selected (ISU 0170). If
heat pump is selected, fan defaults to electric. If fan
coil or PTAC modes are selected, fan defaults to
electric (does not show up).
0185
Pre-occupancy
Purge Duration
0
0—no duration
1—one hour
2—two hours
3—three hours
Shown only if system has fan and schedule is
programmable (ISU 0160).
Pre-occupancy purge is enabled by a nonzero
duration.
0190
Reversing Valve
O/B
0
0—O (O/B On Cool)
1—B (O/B On Heat)
Only shown if heat pump or PTAC system is selected.
0220
Cycles Per Hour
(CPH) for first stage
cooling/compressor
3
1-6
Only shown if system has cool stages (ISU 0170).
Shown for heat pump, fan coil, PTAC, and
conventional cooling stages.
0240
CPH for first stage
heat
5
1-12
Only shown if system is conventional with heat
stages, 4 pipe fan coil, 2 pipe fan coil (ISU 0170).
0270
CPH for Em Heat
9
1-12
Only shown if HP with reheat, 2 pipe fan coil with
reheat, and PTAC with reheat (ISU 0170).
0280
Continuous
Backlight
0
0—No
1—Yes
Always shown; however, if AC power is not present,
the option is overridden and normal backlight
operation occurs.
0300
Changeover
0
0—Manual
1—Auto
Only shown if system has both heat and cool stages
(ISU 0170). Shown for CNV, HP, PTAC and 4 pipe fan
coil (ISU 0170). Not shown for 2 pipe fan coil modes.