3 NM, 5 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS

62-0274—07

2

Humidity Ratings:

5% to 95% R.H., Non-Condensing

Electrical Connections: 

Field wiring 18 AWG (0.5 mm) to 14 AWG (1.5 mm) 

conductors (stranded or solid) and up to 2 - 14 AWG (1.5 

mm) conductors (stranded) to screw terminals, located 

under the removable access cover.

Auxiliary Switch (One SPDT):

Switch adjustable from 0-95° 

500 uA Resistive at 5 Vdc (minimum)

250 Vac, 8 A resistive, 3 A inductive

Mounting: Self-centering shaft adapter (shaft coupling):

Round damper shafts: 3/8 to 5/8 in. (9 to 16 mm)

Square damper shafts: 1/4 to 1/2 in. (6 to 13 mm)

Minimum Damper Shaft Length:

1 in. (25 mm); 3 in.(76 mm) recommended.

Spring Return Timing (at rated load):

< 25 seconds @ -4°F to 130°F (-20°C to 55°C)

< 60 seconds @ -22°F (-30°C)

Cable Specification:

300 V, 75° C, Plenum Rated, 3 ft length from end of access 

cover, 18 AWG

Sylk™ Bus:

Sylk is a two-wire, polarity insensitive bus that provides 

communications between a Sylk-enabled actuator and a 

Sylk-enabled controller.  For wiring, the Sylk-enabled 

actuator may be mounted up to 200 ft. (61 m) from the 

controller; twisted pair wire is recommended for wire runs 

longer than 100 ft. (30.5 m).  Using Sylk-enabled actuators 

saves I/O on the controller and is faster and cheaper to 

install since the bus is polarity insensitive.

Fig. 1. Dimensional drawing of actuator in in. (mm).

Stroke:

95° ±3°, mechanically limited.

Approvals:

UL873

IEC 60730-1 and Part 2–14

UL1097 for Double Insulation

CE Certification Low Voltage Directive 2006/95/EC

CE EMC 2004/108/EC

C-Tick N314

Enclosure Ratings:

IP54

NEMA 2

Flame Resistance UL94-5VA

Input Impedance: 

95 kOhm minimum.

Feedback Signal:

0(2)-10 Vdc, 3 mA minimum.

Analog Output Signal:

0(2)-10 Vdc

Noise Rating at 1m (Maximum):

Driving

Floating/Modulating/Econ/Sylk-enabled: < 40 dB(A)

2-Position: < 50 dB(A)

Spring Return: < 60 dB(A)

Accessories:

27518 Balljoint (5/16 in.)

103598 Balljoint (1/4 in.)

27520B, C, E, G, H, K, L, Q Pushrod (5/16 in. diameter)

STRN-STRNRLF Water-tight Cable Gland/Strain-relief 

Fitting (10 pack)

STRN-WMK-01 Wall Mount Kit

STRN-ECONO-01 Economizer Retrofit Kit

STRN-CRK-01 Crank Arm Kit

STRN-SCSA Self Centering Shaft Adapter

STRN-CA-01 Crank Arm (Non-Self-Centering)

STRN-CA-02 Crank Arm (Self-Centering)

STRN-BRKT Anti-Rotation Bracket

M28945

3-55/64 (98)

6-61/64

(177)

1-1/8

(29)

 5-27/32

(148)

1-9/16

(40)

3-5/32 (80)

4-9/16

(116)

1-15/16

(49)

1-1/16

(27)

2-1/64

(55)

47/64

(19)

2-27/64 (61)

36 (914)

1

1

CABLE AND STRAIN 
RELIEF ON SELECT 
MODELS ONLY.

Summary of Contents for MS4105A1030

Page 1: ...erating Temperature 40 to 150 F 40 to 65 C 22 to 150 F 30 to 65 C Two position only Shipping and Storage Temperature 40 to 150 F 40 to 65 C 1 Number represents range 2 2 10 Vdc 3 0 2 10 Vdc Table 1 Models Power Supply Model Number Model Number including 3 ft whip Torque Voltage VA Driving1 Drive sec Control Input Output Description SPDT Aux Switch MS3103J1030 27 lb in 3 Nm 24 Vac dc 50 60 Hz 20 24...

Page 2: ...ded for wire runs longer than 100 ft 30 5 m Using Sylk enabled actuators saves I O on the controller and is faster and cheaper to install since the bus is polarity insensitive Fig 1 Dimensional drawing of actuator in in mm Stroke 95 3 mechanically limited Approvals UL873 IEC 60730 1 and Part 2 14 UL1097 for Double Insulation CE Certification Low Voltage Directive 2006 95 EC CE EMC 2004 108 EC C Ti...

Page 3: ...o indicate the hub rotary position Fig 2 Spring Return DCA mounting orientation Measure Damper Valve Shaft Length If the shaft is less than three inches in length the shaft coupling must be located between the damper valve and actuator housing If the shaft length is more than three inches the shaft coupling may be located on either side of the actuator housing Spring return actuators shall be dire...

Page 4: ...s than 95 degrees a simple adjustment can be made When the rotational mounting of the shaft coupling is changed the actuator drives less than the full 90 degrees stroke The stroke is adjustable in 5 degree increments Once adjusted the actuator drives until the shaft coupling reaches the mechanical stop part of the housing The stop causes the motor to discontinue driving and the shaft coupling driv...

Page 5: ...sing 10 mm wrench tighten shaft coupling securely onto damper shaft using maximum 240 lb in 27 1 Nm torque NOTE See Fig 6 for proper mounting to a square damper shaft Fig 6 Proper mounting to square damper shaft Fig 7 Mounting actuator to damper housing WIRING CAUTION Electrical Shock or Equipment Damage Hazard Disconnect all power supplies before installation Motors with auxiliary switches can ha...

Page 6: ...inal block s See Fig 9 and 11 NOTE Use either 1 2 in x 14 NPS or M20 x 1 5 strain relief or conduit adapters Fig 8 Removing access cover Typical Wiring Without Cables See Fig 9 through 23 for typical wiring details for actuators without cables whips See Fig 24 through 26 for wiring actuators with cables whips Fig 9 Terminal block details Fig 10 Terminal block details Fig 11 S BUS Terminal block de...

Page 7: ...osition potentiometer external minimum position potentiometer S BUS 5 feedback feedback feedback feedback Analog output ACTUATOR SPST 24 VAC 1 1 2 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE V 1 2 M29121 ACTUATOR SPST 1 1 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED V 1 2 M29122 SPDT 24 ...

Page 8: ...CONTROLLER 24 VAC 1 1 2 3 2 490 TO 510 OHMS 1 2 W MINIMUM LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWITCH TO MODULATING V FEEDBACK FEEDBACK 5 4 3 1 2 M28627 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 0 90 90 0 ACTUATOR 0 2 TO 10 VDC PROPORTIONING CONTROLLER 24 VAC 1 1 2 3 2 LINE VOLTAGE POWER SUPPLY PROVIDE DIS...

Page 9: ...ailure Actuator Override To override the control signal for freeze protection or similar applications 1 Override to full open a Disconnect the input signal from terminal 3 b Apply 24 Vac to terminal 3 c See Fig 22 2 Override to full closed a Disconnect the input signal from terminal 3 b See Fig 23 Fig 22 Override to full open ACTUATOR V FEEDBACK 5 4 3 1 2 M32679 3 POSITION MINIMUM POSITION 1 EXTER...

Page 10: ...ntrol signal See Fig 4 4 Apply control signal for actuator full open or full closed position See Fig 11 and Table 2 a 0 2 10 Vdc apply 10 Vdc signal to terminal 3 b 10 0 2 Vdc apply 0 2 Vdc signal to terminal 3 c 0 4 20 mA apply 20 mA signal to terminal 3 d 20 0 4mA apply 0 4 mA signal to terminal 3 e Floating apply 24 Vac to appropriate 0 90 3 or 90 0 4 terminal 5 Actuator drives to full open or ...

Page 11: ... match the input signal as actuator drives towards 0 position Direct Checkout 1 Mount actuator for required application either clock wise or counterclockwise rotation to open the damper or valve 2 Check damper position and make sure that 24 Vdc Vac is present at the appropriate connections See Fig 9 3 Apply control signal to the appropriate connections to move the damper to the opposite position T...

Page 12: ...lutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 62 0274 07 M S Rev 05 11 Printed in U S A ...

Reviews: