Output Signal Feedback (F)

An analog output signal (2 to 10 Vdc) that represents the
actual actuator stem position is available at Terminal F. It can
be used for remote indication of the stem position. When the
actuator stem is fully extended, the output signal is 10 Vdc.

When the actuator stem is up, the output signal is 0 or 2 Vdc.
The output of the signal does not change when the action of
the actuator is reversed using W3. See Direction of Action.

Actuator Override

The output signal override function can be used for freeze
protection or similar applications. It forces the actuator into
an end position, overriding the control signal. To exercise this
function, connect the 24 Vac common (or T2) to either
Terminal O1 or O2. Connecting to Terminal O1 fully extends
the actuator stem. Connecting to O2 fully retracts the
actuator stem.

The control signal (+) is ignored when the override signal is
applied to Terminal O1 or O2. This override can be achieved

Fig. 14. Connections for overriding control signal

to drive actuator to a specific position.

Direction of Action

The direction of the actuator action can be changed by
repositioning selector plug W3, which is factory set so that
the stem extends on increasing signal and retracts on
decreasing signal. When the actuator stem is fully extended,
the output signal from the feedback (F) function is 10 Vdc.
The output of the signal does not change when W3 is used to
reverse the action of the actuator, see Fig. 12.

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 
OVERLOAD PROTECTION AS REQUIRED.

F

+

0-10Vdc OR 2-10 Vdc CONTROL SIGNAL. SEE SIGNAL 
INPUT (+) SECTION.

SEE OVERRIDE SECTION FOR DETAILS ON 
OVERRIDE OPERATION.

2-10 Vdc FEEDBACK SIGNAL. SEE OUTPUT SIGNAL 
FEEDBACK SECTION.

ML7425

WIRING
STRIP

F

+

T2

T1

O1

O2

TS

1

3

4

2

INPUT

(FEEDBACK)

OUTPUT

3

2

SP3T

OVERRIDE

SWITCH

4

1

L1 
(HOT)

L2

M7906A

CAUTION

Equipment Damage Hazard.
Improper voltage through the 43191680 Dual
Auxiliary Switch will damage the switch beyond
repair.
Use the 43191680 Dual Auxiliary Switch with 24 Vac
applications

 only.

OPERATION

General

In the ML7425, the drive of a synchronous motor is converted
into the linear motion of the actuator stem by using a spur
gear transmission. A button retainer clip connects the actuator
stem to the valve stem.

An integrated spring package limits the stem force to a
factory-adjusted value in either direction. Installed
microswitches turn off the actuator when the specified stem
force is reached.

The ML7425A,B Spring Return Valve Actuators provide a
safety valve position in event of power failure. On power
failure, the ML7425A returns the stem to the bottom position.
On power failure, ML7425B returns the stem fully upward.

The ML7425 actuators are shipped from the factory with a
spring handle retaining clip installed, so that the actuator can
be connected to the valve without applying power. This clip is
removed after the actuator is installed on the valve. See
Installation section.

Signal Input (+)

The analog input signal (+) range is set at the factory to 0 to
10 Vdc. Changing the position of the W2 selector plug sets
the range to 2 through 10 Vdc. Selector plugs W1, W2, and
W3 are positioned on the back side of the PCB protection
sheet. See Fig. 12 for location of the selector plugs.

Signal Input Failure

Using selector plug W1, the actuator can be set to run to one
of three positions in event of a signal failure:

1.

0% — Actuator position corresponds with 0 or 2 Vdc

signal

2.

50% — Actuator stem in mid-position

3. 100% — Actuator position according to 10 Vdc signal

NOTE:

W1 is factory set at the mid-position.

with a switch or a relay, see Fig. 14.

Summary of Contents for ML7425A Series

Page 1: ...everse the direction of action FEATURES Quick and easy installation No separate linkage required ML7425A extends actuator stem on power failure ML7425B retracts actuator stem on power failure Conduit connector is standard No adjustments required True spring return on power failure Accurate valve positioning Low power consumption High close off ratings Force limiting end switches 0 to 10 Vdc or 2 t...

Page 2: ...11H J Screw 150 150 150 145 V5011N1 3 Screw 230 230 163 104 67 37 V5011N2 Screw 100 100 100 100 67 37 V5013B Flange 21 14 V5013C Flange 21 14 V5013F Screw 150 150 150 126 77 49 V5013N Screw 230 230 163 104 67 37 V3350 1 Flange 21 14 V3360 1 Flange 21 b 14 b V3450 1 Flange 21 14 V3460 1 Flange 21 b 14 b Stem Force 135 lbf 600N Actuator Stroke 3 4 in 20 mm Actuator Run Time at 60 Hz 90 seconds Sprin...

Page 3: ...n the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation L...

Page 4: ...ift the handle See Fig 5 7 Remove manual spring handle retaining clip and lift and release the handle See Fig 5 The easiest way to safely perform this operation is to a remove the retaining clip then b wedge a small flat bladed screwdriver under the manual spring handle at the point marked in Fig 5 and pry up the handle Fig 3 Securing ML7425 to valve M6632 Fig 2 Attaching the actuator to the valve...

Page 5: ...wiring diagrams in Fig 7 through 11 connect power and control wires to the ML7425 Make sure that all wiring is correct NOTE Make the selector plug changes if required before replacing the cover See Fig 12 3 When wiring is complete replace the cover on the ML7425 See Fig 13 4 Apply power and control signals to the ML7425 M6629 Fig 6 Connecting power and control wiring to ML7425 M6630 Fig 7 ML7425 w...

Page 6: ...ne transformer L1 HOT L2 1 1 WIRING STRIP F T2 T1 O1 O2 TS 1 1 2 2 3 3 4 5 6 ML7425 SENSOR T775 WITH 4 20 MA OUTPUT SINGLE TRANSFORMER 40 VA 24 VAC POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M7897 500 OHM RESISTOR Fig 12 Location of W1 W2 and W3 selector plugs M6628 Fig 13 Replacing cover on ML7425 Auxiliary Potentiometers The 43191679 Auxiliary Potentiometers can be...

Page 7: ...dc FEEDBACK SIGNAL SEE OUTPUT SIGNAL FEEDBACK SECTION ML7425 WIRING STRIP F T2 T1 O1 O2 TS 1 3 4 2 INPUT FEEDBACK OUTPUT 3 2 SP3T OVERRIDE SWITCH 4 1 L1 HOT L2 M7906A CAUTION Equipment Damage Hazard Improper voltage through the 43191680 Dual Auxiliary Switch will damage the switch beyond repair Use the 43191680 Dual Auxiliary Switch with 24 Vac applications only OPERATION General In the ML7425 the...

Page 8: ...g replacement and modernization products from your TRADELINE wholesaler or distributor refer to the TRADELINE Catalog or price sheets for complete ordering number If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Home and Building Control Sales Office check white pages of your phone directory 2 Home and...