4. Managing HART Devices using FDC Application Software
4.6. Online configuration
Revision 3
MC Toolkit (MCT404) User Manual
55
Executing methods on a device
To execute methods on devices, perform the following steps.
Note
: For example, consider the following scenario to execute Loop test.
1.
On the
Device Home
page, tap
Functions
tab.
2.
Tap
Online
>
Select
.
3.
The
Device Configuration
page appears which displays the top and bottom panes.
4.
Navigate to the desired menu. The bottom pane will display items under that menu.
5.
Select a method from the list. For example,
Loop Test
.
6.
Tap
Execute
.
A warning message appears displaying a message that loop must be removed from the automatic
control.
7.
Tap
OK
.
8.
The
Loop Test
dialog box appears displaying the information to choose analog output level.
9.
Choose the analog output level and tap
OK
.
Note
: To cancel the method execution, tap
Abort
.
10.
A message appears displaying the information that the output value of the device is fixed.
11.
Tap
OK
.
12.
The
Loop Test
dialog box appears displaying information to choose analog output level.
13.
In the Choose analog output level combo box, tap to select
End
.
14.
Tap
OK
.
The method is executed successfully.