Data Field Descriptions
With ADEMCO Contact ID® Reporting:
Enter a digit in the first box to enable the zone to report. Use a different
digit for each zone until you have used up available digits. If the number of zones exceeds the number of available
digits, begin with digit 1 again. This is an "enabling" code only and is not the actual code sent to the central station
office. Entries in the second boxes will be ignored. For system status (non-alarm) codes, enter a “1” in the first box for all
the system conditions you want to send to the central station. A "0" in the first box disables the report.
For the LynxSIA Plus control, the
✻
✻
✻
✻
59 Exit Error Report Code and
✻
✻
✻
✻
68 Cancel Report Code options are
always enabled. A report code can be entered if reporting formats other than Contact ID
®
are used.
SYSTEM STATUS REPORT CODES
(
✻
59–
✻
68)
59
59
59
59
EXIT
EXIT
EXIT
EXIT ERROR
ERROR
ERROR
ERROR REP
REP
REP
REP
Exit Error Report Code
(See notes above)
Lynx Plus ONLY
If the system is armed and an entry/exit or interior zone is still open after the exit delay
time has expired, an alarm will sound at the keypad and external sounder. If the system
is disarmed before the end of the entry delay that immediately follows, the alarm
sounding will stop and no message will be sent to the central station. The keypad will
display “CA Canceled Alarm”.
If an Exit Error report code is selected in this field and the system is not disarmed before
the end of the entry delay, and an entry/exit or interior zone is still open, an “exit alarm”
message will be sent to the central station. The keypad will display “EA Exit Error”, and
the alarm sounding will continue until the system is disarmed (or timeout occurs).
An Exit Alarm condition will also result if a fault occurs in an exit or interior zone within
2 minutes following the end of the exit delay, and an “Exit Alarm” message will be sent
to the central station.
If Contact ID® format has been programmed, the message will contain the zone number
and error code 374 (Trouble–Exit Error). If 4+2 format is used, the digit entered in this
field will be sent followed by the second digit of the programmed alarm code for that
zone.
If 3+1 or 4+1 format is used, only the digit entered in this field will be sent. This message
will go to the Primary Phone Number. No restore message will be sent under any of
these conditions,.
If “0” is entered in this field, no special message will be sent, only the regular alarm and
alarm restore code for the zone.
LynxSIA Plus ONLY
Always enabled however, a report code can be entered if reporting formats other than
Contact ID
®
are used.
Note:
The LynxSIA Plus control validates the data entered in this field. If the selection is not
valid the control will emit a single long beep indicating that the selection has been
rejected. The control replaces the selection with the default value “1”, which is
displayed on the keypad, and advances to the next field.
If the system is armed and an entry/exit or interior zone is still open, after the exit delay
time has expired, an alarm will sound at the keypad and external sounder, the keypad
will display “EA Exit Error” and the entry delay begins. If the system is disarmed before
the end of the entry delay that immediately follows, the alarm sounding will stop and no
message will be sent to the central station. Additionally, if the cancel display option was
enabled in field
✻
57, the keypad will display “CA Canceled Alarm”.
If the system is not disarmed before the end of the entry delay, and an entry/exit or
interior zone is still open, an “Exit Error” message and a “Zone Alarm” message will be
sent to the central station. The keypad will display “EA Exit Error”, and the alarm
sounding will continue until the system is disarmed (or timeout occurs).
If Contact ID® format has been programmed, the message will contain the zone number
and error code 374 (Alarm–Exit Error).
60
60
60
60
TROUBLE
TROUBLE
TROUBLE
TROUBLE REP
REP
REP
REP CODE
CODE
CODE
CODE
Trouble Report Code
(See notes above)
A Trouble Report will be sent if a zone goes into trouble.