Lynx Plus Series Installation and Setup Guide
- 28 -
Data Field Descriptions
Field
✻
50:
Field *50 is used to program different features in the Lynx Plus and LynxSIA Plus controls.
Please be sure that you use the correct field for the control being installed.
50
50
50
50
15
15
15
15 SEC
SEC
SEC
SEC DIAL
DIAL
DIAL
DIAL DLY
DLY
DLY
DLY
(
This field applies only to
the Lynx Plus control)
15-Second Dialer Delay (Burglary)
(This field applies only to the Lynx Plus control)
If enabled, provides delay of burglary report to the central station, and allows time for
the subscriber to avoid a false alarm transmission. The delay applies only to zone type 3
and 5 alarms and not to zone type 24 alarms (silent burglary) or to 24-hour zone types
6, 7, and 8 (silent panic, audible alarm, auxiliary alarm), which are always sent as soon
as they occur.
UL installations:
must be 0 (no delay)
Lynx Plus SELECTIONS
0 = no dialer delay
1 = provide 15-second delay of burglary alarm report when armed away
50
50
50
50
ABORT
ABORT
ABORT
ABORT WINDOW
WINDOW
WINDOW
WINDOW
(
This field applies only to
the LynxSIA Plus control)
Burglary Abort Window
(This field applies only to the LynxSIA Plus control
)
This field provides the option for an Abort Window for Burglary zone types that report
to the central station. This feature allows time for the subscriber to avoid a false alarm
transmission. This feature does not apply to zone type 9 or 16 alarms (Supervised Fire)
or to 24-hour zone types 6, 7, and 8 (silent panic, audible alarm, auxiliary alarm), which
are always sent as soon as they occur.
SIA
The burglary abort window must be set to a minimum of 15 seconds. The sum of the
burglary abort window entered in
✻
50 and the entry delays entered in either Field
✻
35
or
✻
36 should not exceed 1 minute.
Note:
The LynxSIA Plus control validates the data entered in this field. If the selection is not
valid the control will emit a single long beep indicating that the selection has been
rejected. The control replaces the selection with the default value “2”, which is
displayed on the keypad, and advances to the next field.
LynxSIA Plus SELECTIONS
1 = 15-second abort window
2 = 30-second abort window
3 = 45-second abort window
51
51
51
51
PERIOD
PERIOD
PERIOD
PERIOD TEST
TEST
TEST
TEST RRRREEEEPPPP
Periodic Test Report
Test report code entered in field
✻
64 is sent.
SELECTIONS
0 = no test report
1 = once every 24 hrs
2 = weekly
3 = once every 30 days
52
52
52
52
TEST
TEST
TEST
TEST REP
REP
REP
REP OFFSET
OFFSET
OFFSET
OFFSET
First Test Report Offset
Select the time for the first report following pwer-up/programming or downloading.
SELECTIONS
0 = 24 hrs after exit program mode or download
1 = 6 hours after exit program mode or download
2 = 12 hrs after exit program mode or download
3 = 18 hrs after exit program mode or download
53
53
53
53
SESCOA
SESCOA
SESCOA
SESCOA
/
RADIONICS
RADIONICS
RADIONICS
RADIONICS
Sescoa/Radionics Select
If disabled, selects Radionics, which uses hexadecimal 0-9, B-F reporting.
If enabled, selects Sescoa, which uses only numeric reporting (0-9). Select 0 for all other
formats.
SELECTIONS
0 = Radionics (0–9, B–F reporting)
1 = SESCOA (0–9 only reporting)