M200-102-01

11

I56-6576-001

APPENDIX B - PRACTICAL PIPE DESIGNS 

for

 ASPIRATING SYSTEMS

The following tables show some typical EN54 

compliant pipe designs for FAAST LT-200 

devices  with  different  overall  pipe  lengths. 

Each design has a one size sample hole for 

ease of installing and testing the system. 

No exhaust pipe has been included in these 

designs.
In all the suggested layouts, the sample hole 

spacing is set to 10m between holes, which 

is the recommended arrangement for point 

smoke  detectors  in  the  UK  (BS  5839).  Air 

flow through the detector has been kept at, or 

above, 39 l/min for best performance.

In the designs with non-sensing end holes, 

the distance to the first hole is 9m and the 

end hole is 1m from the last sample hole

.

CLASS

 

C

 

PIPE

 

DESIGNS

 

WITH

 

SINGLE

 

SAMPLE

 

HOLE/END

 

HOLE

 

SIZE

 

AND

 

10m

 

SPACING

 

1

 

PIPE

 

Pipe

 

Length

 

Number

 

of

 

holes

 

Hole

 

size

 

End

 

hole*

 

Air

 

flow

 

Flow

 

balance

Average

 

sensitivity

Alarm

 

level

 

Fan

 

Total

 

hole

 

area

 

(m) 

 

(mm)  (mm)  (I/min)

 

(%/m) 

 

 

(mm

2

100 

10 

40 

0.5 

0.74 

10 

77.76 

90 

39 

0.53 

0.66 

10 

70.70 

80 

3.5 

3.5 

43 

0.52 

0.91 

10 

86.60 

70 

3.5 

3.5 

42 

0.62 

0.79 

10 

76.98 

60 

45 

0.6 

1.14 

10 

87.98 

50 

4.5 

4.5 

45 

0.62 

0.98 

95.44 

40 

4.5 

4.5 

45 

0.76 

0.80 

10 

79.53 

30 

46 

0.83 

1.29 

10 

78.55 

20 

5.5 

5.5 

45 

0.92 

0.97 

10 

71.28 

10 

6.5 

6.5 

45 

1.31 

10 

66.37 

* Non‐sensing end hole 

CLASS

 

C

 

PIPE

 

DESIGNS

 

WITH

 

SINGLE

 

SAMPLE

 

HOLE/END

 

HOLE

 

SIZE

 

AND

 

10m

 

SPACING

 

2

 

PIPE

 

(T

 

FORM)

 

Per

 

pipe

 

length

 

Number

 

of

 

holes

 

Hole

 

size

 

End

 

hole*

 

Air

 

flow

 

Flow

 

balance

Average

 

sensitivity

Alarm

 

level

 

Fan

 

Total

 

hole

 

area

 

(m) 

 

(mm)  (mm)  (I/min)

 

(%/m) 

 

 

(mm

2

80 

2.5 

2.5 

47 

0.71 

1.16 

83.46 

70 

2.5 

2.5 

45 

0.77 

1.03 

73.64 

60 

46 

0.72 

0.91 

91.90 

50 

45 

0.81 

1.16 

77.76 

40 

3.5 

3.5 

45 

0.81 

0.97 

86.60 

30 

3.5 

3.5 

44 

0.91 

1.30 

67.36 

20 

44 

0.95 

0.98 

62.84 

10 

45 

1.31 

58.91 

* Non‐sensing end hole 

CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE (Inc. SAMPLING END HOLE) 

AND 10m SPACING ‐ 1 PIPE 

Pipe 

Length 

Number 

of holes 

Hole 

size 

Air 

flow 

Flow 

balance 

Average 

sensitivity 

Alarm 

level 

Fan 

Total 

hole area 

(m) 

 

(mm)  (I/min) 

 

(%/m) 

 

 

(mm

2

100 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

90 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

80 

3.5 

42 

0.6 

0.79 

10 

76.98 

70 

44 

0.58 

0.70 

10 

87.98 

60 

4.5 

44 

0.59 

1.00 

95.44 

50 

5.5 

45 

0.54 

0.86 

118.81 

40 

44 

0.65 

0.67 

113.11 

30 

6.5 

45 

0.78 

0.99 

99.56 

20 

6.5 

44 

0.92 

1.31 

10 

66.37 

10 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

‐ 

X: No adequate or recommended single sample hole size design 

Summary of Contents for LT-200 MI-FL20 Series

Page 1: ...he performance of this system is dependent upon the pipe network Any extension or modification to the designed installation may cause improper operation The operational effects of such changes need to be verified using the PipeIQ design software This equipment and all associated pipe work must be installed in accordance with all relevant codes and regulations PARTS LIST Description Quantity FAAST ...

Page 2: ...NDICATES CENTRE OF ASPIRATING PIPES FIXING HOLE FIXING HOLE USE FOR PLUMB LINE 90 mm 99 mm 59 329 212 mm 144 mm 41 mm mm mm POSITION OF BRACKET PLUMB LINE BASE OUTLINE OUTER DIMENSION OF UNIT 1 2 3 4 5 6 Minimum clearance required from hinges to open door 35 mm Figure 1 Dimensions and Knock Outs PHYSICAL INSTALLATION Front Panel Labels The LT 200 MI FL01 is shipped without the front panel labels f...

Page 3: ...should be kept sealed Note 2 Do NOT glue pipes into the pipe holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using highest level 1 sensitivity 1 2 3 4 5 6 CHANNEL 1 CHANNEL 2 ONLY FUNCTION ON 2 CHANNEL UNITS CHANNEL 1 NOT USED FOR COMMON CHAMBER UNIT CHANNEL 2 ONLY FUNCTIONS ON 2 CHANNEL AND COMMON CHAMBER UNITS CLASS PIPE LENGTH m MAX No HOLES CH HOLE SIZES C 10...

Page 4: ...f the unit to lever open the door as shown above SAMPLING AREA SAMPLING AREA Whenever the FAAST LT 200 is installed outside the risk area return of the exhaust air back into the protected area can reduce flow faults due to pressure difference MODULE MOUNT MODULE MOUNT F LT PMB MODULE MOUNT KIT OPTIONAL If required an input output module can be installed into the FAAST LT 200 unit The optional modu...

Page 5: ... 7 NO Alarm Relay CH1 8 NC Alarm Relay CH2 T3 9 C Alarm Relay CH2 10 NO Alarm Relay CH2 11 NC Fault Relay CH1 T4 12 C Fault Relay CH1 13 NO Fault Relay CH1 14 NC Fault Relay AUX CH2 T5 15 C Fault Relay AUX CH2 16 NO Fault Relay AUX CH2 17 Sounder Output 1 47 k ohm EOL Resistor T6 18 Sounder Output 1 19 Sounder Output 2 47 k ohm EOL Resistor T7 20 Sounder Output 2 21 Configurable Input Reset Defaul...

Page 6: ...this Note The sensors communicate with the fire panel through the loop connection whether the 24VDC power supply is on or not Module The module address is set by means of rotary decade address switches located behind the door of the unit Use a screwdriver to rotate the wheels to the desired address The selected address refers to channel 1 on 2 channel units the device assigns the next 1 module add...

Page 7: ... ACTION WARNING OR TROUBLE COMMENT ACTION LOW FLOW 1 Blink Yellow Fault delay in progress Default is 60s general fault set at end of delay ON Yellow Low flow fault Check filter check pipe network for blockages INPUT 1 BLINK Yellow External input fault Not used with default settings SENSOR 2 BLINKS Yellow Sensor communication fault Check sensor addresses and installation replace sensor ASPIRATOR ON...

Page 8: ... smoke The choice of smoke source is dependant on the installation but in all cases the smoke must be present for the duration of the test Smoke pellets or matches can be used close to the sampling point to introduce smoke particulates into the system It is recommended that smoke with a particulate life cycle of greater than 120s should be used standard aerosol sprays for point detector testing do...

Page 9: ...rt in the centre of the device to a spare USB port on the PC make sure that the USB connector is pushed fully into the FAAST LT 200 port until it clicks The device will now be in Remote Maintenance mode The USB connection must be made within 5 minutes of entering the Maintenance mode password The first time a PC running PipeIQ is connected to a FAAST LT 200 device the USB port drivers will be inst...

Page 10: ... 45l min 6 Repeat from step 3 adjust hole diameters and fan speed to achieve all the above figures 7 Next check that the sample hole sensitivity is practical for the chosen class i e it is not too sensitive Ideally to avoid false alarms hole sensitivity for a class C system should be 1 m or greater and certainly 0 5 m 8 If necessary change the Alarm level to reduce the sample hole sensitivity The ...

Page 11: ...76 98 60 6 4 4 45 0 6 1 14 3 10 87 98 50 5 4 5 4 5 45 0 62 0 98 3 9 95 44 40 4 4 5 4 5 45 0 76 0 80 3 10 79 53 30 3 5 5 46 0 83 1 29 4 10 78 55 20 2 5 5 5 5 45 0 92 0 97 4 10 71 28 10 1 6 5 6 5 45 1 1 31 5 10 66 37 Non sensing end hole CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE END HOLE SIZE AND 10m SPACING 2 PIPE T FORM Per pipe length Number of holes Hole size End hole Air flow Flow balance Av...

Page 12: ...pe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117 83 40 3 4 5 4 5 46 0 89 0 40 1 5 95 44 30 3 4 4 46 0 93 0 40 1 7 75 41 20 2 5 5 46 0 96 0 40 2 6 78 55 10 1 6 5 6 5 44 1 0 33 3 8 66 37 CLASS B PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 1 PIP...

Page 13: ... 83 0 20 1 9 84 83 20 2 6 5 6 5 44 0 94 0 14 1 10 66 37 10 X X No adequate or recommended single sample hole size design CLASS A PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE Inc SAMPLING END HOLE AND 10m SPACING 2 PIPE T FORM Each pipe Number of holes Hole size End hole Air flow Flow balance Average sensitivity Alarm level Fan Total hole area m per pipe mm mm I min m mm2 50 3 5 5 45 0 84 0 40 1 4 117...