Limitless™
WDRR Receiver
Issue 1,
50063987
www.honeywell.com/limitless
14
6
ELECTRICAL CONFIGURATIONS/CONNECTIONS
WARNING
RISK OF ELECTRICAL SHOCK
*
Potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 Vdc
may be accessible.
Failure to comply with these instructions could result in death or serious injury.
ATTENTION
Do not run the electrical wires in parallel and close proximity to the antenna or antenna cable.
6.1
Configuration DIP Switches
Refer to Figure 2.
The NPN/PNP-type outputs
, NPN/PNP-type “low battery” output
, and NPN/PNP-
type “Lost RF Link” output
may be connected for use as: NPN-type current sinking or totem pole; PNP-
type current sourcing or totem pole. The configuration DIP switches
identified as “1” and “2” on the DIP
switch housing can be set to interface with a PLC as follows:
OUTPUT TYPE
DIP SW 1 LOGIC
DIP SW 2 LOGIC
NPN-type: Current sinking open collector
OFF
OFF
PNP-type: Current sourcing open collector ON
OFF
NPN-type: Totem pole (current sinking)
OFF
ON
PNP-type: Totem pole (current sourcing)
ON
ON
Note: DIP switches 3 thru 8 are not used; factory default for both DIP switches is OFF.
6.2
RF Link Switch
Refer to Figure 2.
The RF Link switch allows selection among the 14 different Limitless™ outputs to view
the RF link strength of a specific Limitless™ input. The five (5) blue LEDs will then indicate the RF link
strength of the Limitless™ input and corresponding chosen output (reference section 5.5). The following
chart identifies switch position related to each Limitless™ input/output.
Switch position NPN/PNP Input/Output # - RF Link strength displayed
0
None-Normal operation
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
A
10
B
11
C
12
D
13
E
14
F
None-LED test mode
Note: Factory default switch position is zero.