5.4
Pairing Mode
Pairing is required to initiate and establish an RF communication link between each single Limitless™ switch and a
single WPMM. The Limitless™ switch will be shipped from the factory with two identification labels
that are
recommended to be completed and applied to the Limitless™ switch housing during the pairing mode. As there are
up to 16 Limitless™ switches that can be paired to a single WPMM, these labels will be used to identify the
Limitless™ switch in the sequence of #1 to #16. The initial Limitless™ switch paired to the WPMM will be Sequence
#1, the second Limitless™ switch paired will be Sequence #2 and so on. If replacing a Limitless™ switch that has
been purged (see section 6.5), identify the correct replacement Sequence # on the identification labels.
ATTENTION
If there are multiple WPMMs being used in the application, apply power to previously paired WPMMs
first (if any) and then to one WPMM at a time.
Allow time for each WPMM to complete its start-up
sequence before applying power to the next WPMM.
ATTENTION
The purging of a Limitless™ switch is required when a previously paired Limitless™ switch is to be
paired again. Refer to the Limitless™ switch installation and technical manual for purge mode
information for the particular model of Limitless™ switch.
The battery will need to be activated in the Limitless™ switch and proper power applied to the WPMM (green
LED illuminated) before proceeding with this pairing procedure. Once the pairing is completed, the Limitless™
switch selected will only communicate with the WPMM it was paired to and no other device.
Step Action
1
Completely read this procedure before starting in order to understand the timing of events that need to be
performed.
2
Limitless™ switch: Remove (if required) the two screws
on the housing cover of the Limitless™ switch
(see Figure 3) and locate the function button
(see Figure 5) to be used in Step 4.
3
WPMM: Press the Function button
on WPMM (see Figure 4) for more than four seconds and less than
eight seconds at which time the green
and amber
LEDs (see Figure 4) will be flashing which indicates
to release the function button immediately as it has entered the pairing mode.
4
Limitless™ switch: Within a 30 second interval of Step 3, depress the function button
and hold depressed
for more than one second and less than 12 seconds at which time the orange
LED turns on (see Figure
5). While in pairing mode, the orange led will flash on for 100 ms every second. The orange
LED flashes
three times 100 ms on, 100 ms off when pairing succeeds. If pairing does not succeed, the orange
LED
will turn off and user will need to repeat steps starting with Step #3.
5
WPMM: Successful pairing will be indicated by the green
and amber
LEDs ceasing to flash and
remaining on for a few seconds before turning off. A short buzzer beep will also occur.
6
To confirm proper pairing between the Limitless™ switch and WPMM, actuate the Limitless™ switch, and
the red LED
(see Figure 4) should illuminate along with a buzzer sound.
7
Record the Limitless™ sequence # on identification labels
and apply to the Limitless™ housing in desired
locations (See Figure 6).
8
Repeat Steps 2-7 to add additional Limitless™ switches. Up to 16 Limitless™ switches can be paired to a
single WPMM.
ATTENTION
The WPMM will go back to normal operation after 35 seconds if pairing does not occur.