JADE™ ECONOMIZER MODULE
63-2700—11
6
Economizer Module Wiring Method
Wire the sensors and outputs, then wire the power
connection.
Each terminal can accommodate the following gauges of
wire:
• Single wire – from 18 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
• For the 24 Vac connections: single wire – from 14 to 18
AWG solid or stranded
• For S-BUS wiring, the sensors may be mounted up to
200 ft. (61 m) from the JADE controller. When the
length of wire is over 100 feet use twisted pair shielded
wire.
• All sensor wiring to the Sylk bus and analog sensors is
polarity insensitive.
Prepare wiring for the terminal blocks, as follows:
1.
Remove the plastic tabs from the side of the control-
ler where the connectors will slide onto the PWA.
2.
Strip 1/2 in. (13 mm) insulation from the conductor.
3.
Cut a single wire to 3/16 in. (5 mm). Insert the wire in
the required terminal location and tighten the screw.
4.
If two or more wires are being inserted into one
terminal location, twist the wires together a
minimum of three turns before inserting them to
ensure proper electrical contact. See Fig. 5 on
page 6.
5.
Cut the twisted end of the wires to 3/16 in. (5 mm)
before inserting them into the terminal and
tightening the screw.
6.
Pull on each wire in all terminals to check for good
mechanical connection.
Fig. 5. Attaching two or more wires at terminal blocks.
Economizer Module Wiring Details
The wiring connection terminals for each module/sensor
are:
• “JADE™ Economizer Module Wiring” on this page.
• “Sylk Bus Sensor Wiring” on page 7.
JADE™ Economizer Module Wiring
Use Fig. 6 and Tables 1 and 2 to locate the wiring
terminals for the Economizer module.
NOTE:
The four terminal blocks are removable. You can
slide out each terminal block, wire it, and then
slide it back into place.
Fig. 6. W7220 Economizer module terminal connection
labels.
1/2 (13)
1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
ONE TERMINAL.
2. TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING SCREW.
THEN PULL ON EACH WIRE IN ALL
TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M24382A
Table 1. Economizer Module - Left hand terminal
blocks.
Label
Type
Description
Top Left Terminal Block
MAT
MAT
20k NTC
and
COM
Mixed Air Temperature Sensor
(polarity insensitive connection)
OAT
OAT
20k NTC
and
COM
Outdoor Air Temperature Sensor
(polarity insensitive connection)
S-BUS
S-BUS
SYLK Bus Sylk Bus sensor
(polarity insensitive connection)
Bottom Left Terminal Block
IAQ 2-10
2-10 Vdc
Air Quality Sensor Input
(e.g. CO
2
sensor)
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 Vac
Air Quality Sensor 24 Vac Source
ACT 2-10
2-10 Vdc
Damper Actuator Output (2-10
Vdc)
ACT COM COM
Damper Actuator Output Common
ACT 24V
24 Vac
Damper Actuator 24 Vac Source
n/a
The bottom pin is not used.