JADE™ ECONOMIZER MODULE
11
63-2700—11
Fig. 13. Jade with Prestige IAQ thermostat, communicating actuator, CO2 and VFD.
C7400S
OUTSIDE AIR
TEMP/HUMIDITY
(ENTHALPY)
SYLKBUS SENSOR
C7400S
RETURN AIR
TEMP/HUMIDITY
(ENTHALPY)
SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O
Y1I
Y2I
OCC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
C R
C(-)
M35159A
S-BUS
S-BUS
MAT
MAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
MA TEMP
SENSOR
20K NTC
AUX1-0
AUX2-I
3
1
2
MS3103J
OR MS3105J
S-BUS
4
5
S-BUS
R(+)
24 VAC
8
1K1
1K1
1
2
3
4
I/O BOARD ON SMARTVFD
HVAC DRIVE HVFDSD
G
C
Y2
Y1
W1
Y1
W1
Y2
G
Y2
W1
C
C
C
C
6
14
C
RELAY 1, DPDT RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 4 FOR HIGH SPEED FAN WITH W1 CALL.
RELAY 2, DPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 4 FOR HIGH SPEED FAN WITH Y2 CALL.
RELAY 3, SPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 1 FOR LOW SPEED FAN WITH Y1 CALL.
RELAY 4, SPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 1 FOR LOW SPEED FAN WITH G CALL.
LOW SPEED FAN IS CONFIGURED BY SETTING “MINIMUM FREQUENCY” WITH PARAMETER M1.8 OF THE STARTUP
WIZARD OF THE SMARTVFD HVAC.
HIGH SPEED FAN IS CONFIGURED BY SETTING “PRESET FREQUENCY 1” WITH PARAMETER M3.3.12 OF THE
SMARTVFD HVAC.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B
AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
NOTES: SEE INSTALLATION INSTRUCTIONS
62-0331 FOR SPECIFIC W7220 JADE
WIRING INFORMATION.
3
4
2
1
5
6
5
6
1
+10 Vref REFERENCE OUTPUT
2
AI1+
ANALOG INPUT,
VOLTAGE OR CURRENT* VOLTAGE
3
AI1- ANALOG INPUT COMMON
(CURRENT)
4
AI2+
ANALOG INPUT,
VOLTAGE OR CURRENT
CURRENT
5
AI2 ANALOG INPUT COMMON
(CURRENT)
6
24Vout 24V AUX. VOLTAGE
7
GND
I/O GROUND
8
DI1
DIGITAL INPUT 1 START FWD
9
DI2
DIGITAL INPUT 2 START REV
10
DI3
DIGITAL INPUT 3
FAULT
11
CM
COMMON A FOR DIN1-DIN6**
12
24Vout 24V AUX. VOLTAGE
13
GND
I/O GROUND
14
DI4
DIGITAL INPUT 4 PRESET
FREQ
SELECT
15
DI5
DIGITAL INPUT 5 PRESET
FREQ
SELECT 2
16
DI6
DIGITAL INPUT 6
FAULT RESE
17
C COMMON A FOR DIN1-DIN6**
18
AO1 ANALOG SIGNAL (+OUTPUT)
OP FREQ
19
AO-/GND ANALOG OUTPUT COMMON
30
+24 Vin
24V AUXILIARY INPUT VOLTAGE
A
RS485 DIFFERENTIAL RECEIVER/
TRANSMITTER
B
RS485 DIFFERENTIAL RECEIVER/
TRANSMITTER
BASIC I/O BOARD
TERMINAL
SIGNAL
DEFAULT
8
7
8
7