JADE™ ECONOMIZER MODULE
19
63-2700—11
Table 5. Menu Structure
a
.
Menu
Parameter
Parameter
Default
Value
Parameter
Range and
Increment
b
Notes
STATUS
ECON AVAIL
NO
YES/NO
YES = economizing available; the system can use Outdoor Air for free
cooling when required.
ECONOMIZING
NO
YES/NO
YES = Outdoor Air being used for 1
st
stage cooling.
OCCUPIED
NO
YES/NO
YES = OCC signal received from space thermostat or unitary controller.
YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC.
HEAT PUMP
n/a
c
COOL
HEAT
Displays COOL or HEAT when system is set to heat pump (non-
conventional)
COOL Y1-IN
OFF
ON/OFF
Y1-I signal from space thermostat or unitary controller for cooling
stage 1.
ON = 24 Vac on term Y1-I
OFF = 0 Vac on term Y1-I
COOL Y1-OUT
OFF
ON/OFF
Cool Stage 1 Relay Output to mechanical cooling (Y1-OUT terminal).
COOL Y2-IN
OFF
ON/OFF
Y2-I signal from space thermostat or unitary controller for second
stage cooling.
ON = 24 Vac on term Y2-I
OFF = 0 Vac on term Y2-I
COOL Y2-OUT
OFF
ON/OFF
Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT terminal).
MA TEMP
_ _._ ºF
-40 to 150 ºF
Displays value of measured mixed air from MAT sensor. Displays --.- if
not connected, short, or out- of-range.
DA TEMP
_ _._ ºF
-40 to 150 ºF
Displays when Discharge Air Sylk Bus sensor is connected and displays
measured discharge air temperature.
Displays --.-°F if sensor sends invalid value, if not connected, short or
out-of-range.
OA TEMP
_ _._ ºF
-40 to 140 ºF
Displays measured value of outdoor air temperature.
Displays --°F if sensor sends invalid value, if not connected, short or
out-of-range.
OA HUM
_ _ %
0 to 100%
Displays measured value of outdoor humidity from OA Sylkbus sensor.
Displays --% if not connected, short, or out- of-range.
RA TEMP
_ _._ ºF
0 to 140 ºF
Displays measured value of return air temperature from RA Sylkbus
sensor. Displays --°F if sensor sends invalid value, if not connected,
short or out-of-range.
RA HUM
_ _ %
0 to 100%
Displays measured value of return air humidity from RA Sylkbus
sensor. Displays --% if sensor sends invalid value, if not connected,
short or out-of-range.
IN CO2
_ _ _ ppm
0 to 2000
ppm
Displays value of measured CO2 from CO2 sensor. Invalid if not
connected, short or out-of-range. May be adjusted in Advanced menu
by Zero offset and Span. See note on page 6 concerning C7632
sensor.
DCV STATUS
n/a
ON/OFF
Displays ON if above setpoint and OFF if below setpoint, and ONLY if a
CO2 sensor is connected.
DAMPER OUT
2.0V
2.0 to 10.0 V
Displays output voltage or position to the damper actuator.
e
ACT POS
n/a
0 to 100%
Displays actual position of actuator.
ACT COUNT
n/a
1 to 65,535
Displays number of times actuator has cycled. 1 Cycle equals the sum
of 180° of movement in any direction.
ACTUATOR
n/a
OK/Alarm
(on Alarm
menu)
Displays Error if voltage or torque is below actuator range
EXH1 OUT
OFF
ON/OFF
Output of EXH1 terminal. Displays ON when damper position
reaches programmed percentage setpoint.
ON = 24 Vac Output; OFF = No Output.