Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
http://www.hls-nordic.com
The
ImperLED E
is a self-contained luminaire with selftest function.
It can be configured as maintained or non-maintained.
Selftest functions
Every 15 days the luminaire will perform an emergency operation test. This will light the light source
for approximately 3 seconds. The red indicator LED will flash during this test sequence.
Every 6 months the luminaire will perform a battery condition test. The test will last for 60 minutes. The
light source will be lit and the yellow indicator LED will flash during this test sequence.
Note:
When using DALI or Wireless communication, the frequencies and schedules for tests will
instead be determined by the connected PC software.
Manual test functions and fault reset
Manual tests and fault reset operations must
be performed using the A-1900 card
(not included and available on request).
Manual tests can only be performed if both mains and
battery are connected.
Light source test
By activating the magnetic contact briefly (less than 5 seconds) an emergency operation test is
performed. The light source will be lit for approximately 3 seconds, the red indicator LED will flash
during this test sequence. The test will start only if the battery has enough charge.
Battery test
By activating the magnetic contact for a period lasting between 5 and 10 seconds, a battery condition
test is performed. This test will last for 60 minutes and can only be performed when the battery is fully
charged (steady green indicator LED). The light source will be lit and the yellow indicator LED will
flash during this test sequence.
Fault reset
Activate the magnetic contact for a period lasting between 10 and 15 seconds to delete all indicated
errors. Then the luminaire enters regular operation mode.
ImperLED E Combi ST LED 230V 1h wPict 10y
Part no.:
290406.10
Lumen output, normal:
250 lm
Lumen output, emergency:
350 lm
Weight:
880 g
Maximum power consumption:
5.4W / 5.6VA
Operation voltage:
220-240V AC / 50-60Hz
Emergency mode duration:
Minimum 1 hour
Battery:
4.8V / 2Ah Li
4
Ti
3
O
12
Charge current:
200-210 mA/CC until 5.6V
Max. discharge current:
910mA
Min. discharge current:
425mA
Battery protection:
Overcharge and full discharge
Charging time:
16 hours
Ambient temperature range:
-25 to +40 °C
Relative humidity:
Up to 95%
Classification:
EN 60598-1, EN 60598-2-22, EN 55015,
EN 61547, EN 61000-3-2, EN 61000-3-3
Technical lifetime (light source): > 100.000 hours
IP rating
IP 65
Expected battery lifetime 10 years
Indicator LEDs
GRE
EN
RED
YEL
LO
W
Normal
Charging (battery test not possible while charging)
Mains off, battery not connected or charger fault
Battery test
Battery fault
Light source test
Light source fault
Battery fault and light source fault
Description
LED status explanation
Off
On
Flashing
Technical description
At the end of their useful life the
packaging, product and batteries
should be disposed of via a
suitable recycling centre. Do not
dispose of with your normal
household waste. Do not burn.