Step 6: The control of maintained or non-maintained operation of the luminary is achieved through Switch 4 on 

     

DS1. For maintained operation, switch number 4 must be in ON position. For non-maintained operation, 

switch number 4 must be in OFF position. 

Step 7: Install the included cable tie (if needed) to fasten securely the power cables. 

Step 8: Place the battery connector to the corresponding connector on the PCB. 

Step 9: Refit carefully the removed plastic parts. If the luminaire will be used for maintained operation, see 

chapter “Pictogram installation” below. Finally place the diffusor. Attention! The 6 plastic latches (A) must 

all be secured (click sound). This requirement is important to ensure the IP65 rating. Power on the 

luminaire. 

PICTOGRAM INSTALLATION 

 

 

 

Step 1: Place a flat blade screwdriver and pull up gently the diffusor clips from both sides to remove the diffusor. 

Step 2: Install the pictogram you need in the diffusor and refit it to the luminary. 

(In case you need to change the pictogram follow the same procedure). 

Step 3: Fill in the letter G on the specification label.  

 

Note:   In case of battery replacement, this must be replaced with parts of the same type and characteristics. 

The replacement must be performed by the manufacturer or a competent person. 

 

Note:   The light source is non-replaceable. 

 

Note:   If the supply cable of the luminaire is damaged, it shall exclusively be replaced by a competent person 

in order to avoid hazard. 

 

 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

GB 

Important notice when installing luminaires within the 

same area! 

To avoid that luminaires perform their battery test at the 

same day, connect the battery packs with more than 1,5 

minutes inbetween. 

Summary of Contents for ImperLED E

Page 1: ... of the designated positions in order to pass the cables and install the included gasket verify that it is not deformed Step 4 Always use in any case round cable with a diameter of 5 10mm H05RN F type 2x1mm2 or any other type at least equal to its mechanical and electrical properties ATTENTION The cable must not be deformed in any way this requirement is important to ensure the IP rating Make a ho...

Page 2: ...r on the luminaire PICTOGRAM INSTALLATION Step 1 Place a flat blade screwdriver and pull up gently the diffusor clips from both sides to remove the diffusor Step 2 Install the pictogram you need in the diffusor and refit it to the luminary In case you need to change the pictogram follow the same procedure Step 3 Fill in the letter G on the specification label Note In case of battery replacement th...

Page 3: ...on test is performed This test will last for 60 minutes and can only be performed when the battery is fully charged steady green indicator LED The light source will be lit and the yellow indicator LED will flash during this test sequence Fault reset Activate the magnetic contact for a period lasting between 10 and 15 seconds to delete all indicated errors Then the luminaire enters regular operatio...

Page 4: ...n av de avmerkede plassen Monter nippel påse at den ikke er deformert Pkt 4 Benytt alltid rund kabel med en diameter på 5 10mm H05RN F type 2x1mm2 eller annen type tilsvarende minst de mekaniske og elektriske egenskapene MERK Kabelen må på ingen måte være deformert dette er viktig for å opprettholde armaturens tetthet Lag et hull i nippelen med en liten skrutrekker tre den runde kabelen gjennom ni...

Page 5: ...e IP65 tetthet Slå på nettspenningen PIKTOGRAMINSTALLASJON Pkt 1 Bruk en flatspor skrutrekker til forsiktig å trekke opp de 6 låseklipsene på lampedekslet Ta av lampedekslet Pkt 2 Installer valgt piktogram i lampedekslet og monter tilbake dekslet Dersom du behøver å bytte ut piktogrammet følg samme prosedyre Pkt 3 Fyll inn bokstaven G på spesifikasjonsetiketten Merk Dersom batteriet skal skiftes u...

Page 6: ...rikapasitetstest Denne testen varer i 60 minutter og kan kun utføres om batteriet er fullt oppladet grønn LED lyser fast Armaturen vil lyse i denne perioden og gul LED blinke Feilreset Aktiver magnetkontakten kontinuerlig i en periode på mellom 10 og 15 sekunder for å slette alle indikerte feil Armaturen går deretter over i normal drift ImperLED E Combi ST LED 230V 1h wPict 10y Artikkelnr 290406 1...

Page 7: ...ngshålet inte passar ska ett nytt hål borras på en av de markerade platserna Montera genomföringen se till att den inte är deformerad Steg 4 Använd alltid en rund kabel 5 10 mm i diameter H05RN F typ 2x1mm2 eller annan typ motsvarande åtminstone de mekaniska och elektriska egenskaperna OBS Kabeln får inte på något sätt deformeras detta är viktigt för att bibehålla armaturens täthet Gör ett hål i g...

Page 8: ...ATION Steg 1 Använd en platt spårskruvmejsel för att försiktigt dra upp de 6 låsklämmorna på lampskyddet Ta bort lampskyddet Steg 2 Montera det valda piktogramet i lampskyddet och sätt tillbaka locket Om du behöver byta ut piktogramet följ samma procedur Steg 3 Ange bokstaven G på specifikationsetiketten Notera Vid ett batteribyte måste det ersättas med ett nytt av samma typ och kapacitet Bytet sk...

Page 9: ...lan 5 till 10 sekunder startas ett test av batterikapaciteten Testet pågår under 60 minuter och kan endast startas när batteriet är fullt uppladdat grön diod lyser konstant Armaturens LED lampa tänds upp och den gula indikeringsdioden blinkar under testperioden Återställning av fel Aktivera magnetkontakten kontinuerligt under en period mellan 10 till 15 sekunder för att återställa eventuella felin...