Hardware Installation
151153
3-1
Section 3
Hardware Installation
RPS-1000 installation involves the following steps:
•
AC power (Section 3.1) and backup battery connection (Section 3.2).
•
Physical connection to the IFP-1000 or IFP-1000ECS FACP to the controlling RPS-1000
(see Section 3.3).
•
Setting an ID for the RPS-1000 (Section 3.3.1).
•
Physical connection of SBUS modules that will be powered by this RPS-1000 (Section
3.4).
•
Physical connection of any outputs (conventional relays, notification appliances, auxiliary
power modules, and so on) that will be powered by this RPS-1000. See Section 3.5.1 for
notification appliance wiring information. Refer to the IFP-1000 Installation Manual (PN
151139) or IFP-1000ECS Installation Manual (PN 151460), for software configuration
information and other information about installing outputs.
3.1
AC Power
At installation, connect the AC terminals to 120 VAC source as shown in Figure 3-1. It
may be necessary for a professional electrician to make this connection.
The AC terminals are rated as 120 VAC, 50 or 60 Hz, 2.7 A (for the RPS-1000) or 240
VAC, 50 or 60 Hz, 1.4A (for the RPS-1000HV).
Figure 3-1 AC Power Connection
To 120 VAC
Power Source
Wh
ite
Green
Black
For RPS-1000
For RPS-1000HV
To 240 VAC
Power Source
Earth
(Ground)
Note: RPS-1000HV
models are labeled.