Hardware Installation
151153
3-6
Figure 3-7 SBUS Class B Wiring to RPS-1000
3.5
Flexputs
™
I/O Circuits
The six Flexput™ circuits are an innovative and versatile feature of the RPS-1000
panel. They can be used as: Class A or B notification circuits, Class A or B initiation
circuits (either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or
door holder).
This section of the manual explains how to install conventional notification appliances
and initiating devices to be used with the RPS-1000.
3.5.1
Conventional Notification Appliance
This sub-section of the manual explains how to install conventional notification
appliances for Class A (Style Z) and Class B (Style Y) configurations.
3.5.2
Releasing Operations
Approved releasing solenoids are list in Table 3-1
Do not mix cross alarming zones
with smoke verification zones. There must be at least two automatic detection
devices in each protected space. Spacing must be reduced to 0.7 times the linear