HPT724 Installation Document  P/N 52765:A  1/25/06

3

6 Push Button Description Table   

7 Programming Instructions

A.  Setting Clock/Calendar:    

Enter the current date, day of the week and time (military) by depressing UP and DWN to make the selction, then depress 
ENTER to accept.  Next, select either DS (daylight savings mode) or ST (standard time mode) by sepressing SET until 
“ENTER to SET BK: appears in display as shown below.  

Push Button

Function/Description

SET

  Scrolling keys for programming. Escaping out of existing programming.

ENTER

  Accepts selections made to progamming.

UP

  Scrolls through selections.

DWN

  Scrolls through selections.

UP and DWN keys can be used to select data entries.  After scrolling to the correct entry, depress ENTER to accept.

SET ENTER UP

DWN

+DC--

~AC~

FM

+BAT--
12VDC

NO

C

NC

Standby Battery Lithium Battery Socket

(order model #CR2032)

Push Button Layout

Output Contact 

Terminals

LCD Display

12-24volt

AC/DC Input

First Main In Terminal

RLY OFF
SU 01:01

ENTER to 

SET TIME

01/01/01

SU 01:01

Upon initial power up                                     will appear in display.

Depress SET                                      will appear in display.

Depress ENTER                                      will appear in display.

ENTER to 

SET BK

Continued on next page...

Summary of Contents for HPT724

Page 1: ...0 mA Form C relay contacts are rated 10 amp 120 VAC 28 VDC EE Prom memory protects against loss of programming due to power failure Accurate crystal controlled clock displays time in military format Momentary and or latching events 50 individually programmed daily weekly events Block programming capacity can accommodate a total of 350 events per week 10 programmable holiday dates First man in opti...

Page 2: ...e individually selected by date and will override all regularly scheduled events The four 4 output relay modes consist of Relay OFF De energizes the relay until a relay ON event is detected Relay ON Energizes the relay until a relay OFF event is detected Disable Used to cancel an existing programmed event Pulse Momentarily energizes the relay for a selectable time period of 1 to 15 seconds Time is...

Page 3: ...amming Escaping out of existing programming ENTER Accepts selections made to progamming UP Scrolls through selections DWN Scrolls through selections UP and DWN keys can be used to select data entries After scrolling to the correct entry depress ENTER to accept SET ENTER UP DWN DC AC FM BAT 12VDC NO C NC Standby Battery Lithium Battery Socket order model CR2032 Push Button Layout Output Contact Ter...

Page 4: ...cept You may continue to program events by repeating the previous steps or exit programming by depressing SET Note When programming additional events it is necessary to select the next consecutive event number following the last event program to continue Also when it is required to have the same event repeated on two 2 or more consecutive days of the week block programming enter the first day foll...

Page 5: ... UP and DWN push button until DIS is displayed depress ENTER to confirm G Delete All Events All previously programmed events can be deleted by depressing SET until ENTER to CLR MEM appears in display as shown below Depressing UP push button will now clear all events previously programmed If you wish to escape from this selection depress any of the other push buttons SET ENTER or DWN For additional...

Page 6: ...6 HPT724 Installation Document P N 52765 A 1 25 06 Customer Event Log Event Relay Day Block Holiday Dates Event Type ...

Reviews: