Honeywell HPT724 Product Installation Document Download Page 4

4

HPT724 Installation Document  P/N 52765:A  1/25/06

Depress ENTER to scroll until flashing cursor appears under DS (daylight savings mode) in display.  To change mode 
depress UP or DWN once and ST (standard time mode) will appear in display.  Depress ENTER to accept correct 
selection.  Note: The flashing cursor denotes location of data entry selection to be made.  If an entry was made in error or 
requires changing, depress SET to backspace, make the correct selection and depress ENTER to accept data and advance 
the cursor.

To change or program clock/calendar simply repeat the steps above.

B.  Setting Events  

Depress ENTER until the flashing cursor appears under OFF in display.  Now select type of event required by scrolling 
using the UP and DWN push buttons until either ON, OFF, or PL appears in display (ON-Relay ON [latching mode], 
OFF-Relay OFF [latching mode], PL-Relay Pulse [momentary]).  Depressing ENTER will make selection.  When 
selecting pulse mode PL01 will appear in display.  It is now necessary to assign the length of time (duration of relay 
activation).  The pulse can range in length from 1 to 15 secondsand is selected using UP or DWN push buttons then 
depressing ENTER to accept.  Note: If pulse duration is not selected relay output defaults to 1 second.  Next, select the 
day of the week and time (military) by using UP or DWN and depressing ENTER to accept.  You may continue to 
program events by repeating the previous steps or exit programming by depressing SET.  Note: When programming 
additional events it is necessary to select the next consecutive event number following the last event program to continue.  
Also, when it is required to have the same event repeated on two (2) or more consecutive days of the week (block 
programming), enter the first day followed by the last day by depressing SUN through SAT.  Example--Monday through 
Thursday, depress MON followed by THURS.  For Wednesday through Sunday, depress WED followed by SUN.

C.  Setting Block Events (weekly repeat):     

A flashing cursor will appear at the location of te first day of the week desired.  Depress UP and DWN to delect day.  
Depress ENTER to confirm selection, then cursor will appear at the location of the last day of the week desired.  Depress 
UP and DWN to select day.  Depress ENTER to confirm selection.  Depress ENTER again to escape.

D.  Setting Holiday Events:    

Next, select HL to indicate as holiday event and time by using UP and DWN push buttons and depress ENTER to accept.  
You may continue to program more holiday events by repeating the previous steps or exit programming by depressing 

SET. 

   

       

ENTER to 

SET EVENT

#01^OFF
SU 00:00

Depress SET until                                     appears in display.

Depress ENTER                                      will appear in display.

ENTER to 

SET BK

BK=SA/SU

TIME=DS

Depress SET until                                     appears in display.

Depress ENTER                                      will appear in display.

ENTER to 

SET EVENT

#01^ON

HL 00:00

Depress SET until                                     appears in display.

Depress ENTER                                       will appear in display.

Continued on next page...

Summary of Contents for HPT724

Page 1: ...0 mA Form C relay contacts are rated 10 amp 120 VAC 28 VDC EE Prom memory protects against loss of programming due to power failure Accurate crystal controlled clock displays time in military format Momentary and or latching events 50 individually programmed daily weekly events Block programming capacity can accommodate a total of 350 events per week 10 programmable holiday dates First man in opti...

Page 2: ...e individually selected by date and will override all regularly scheduled events The four 4 output relay modes consist of Relay OFF De energizes the relay until a relay ON event is detected Relay ON Energizes the relay until a relay OFF event is detected Disable Used to cancel an existing programmed event Pulse Momentarily energizes the relay for a selectable time period of 1 to 15 seconds Time is...

Page 3: ...amming Escaping out of existing programming ENTER Accepts selections made to progamming UP Scrolls through selections DWN Scrolls through selections UP and DWN keys can be used to select data entries After scrolling to the correct entry depress ENTER to accept SET ENTER UP DWN DC AC FM BAT 12VDC NO C NC Standby Battery Lithium Battery Socket order model CR2032 Push Button Layout Output Contact Ter...

Page 4: ...cept You may continue to program events by repeating the previous steps or exit programming by depressing SET Note When programming additional events it is necessary to select the next consecutive event number following the last event program to continue Also when it is required to have the same event repeated on two 2 or more consecutive days of the week block programming enter the first day foll...

Page 5: ... UP and DWN push button until DIS is displayed depress ENTER to confirm G Delete All Events All previously programmed events can be deleted by depressing SET until ENTER to CLR MEM appears in display as shown below Depressing UP push button will now clear all events previously programmed If you wish to escape from this selection depress any of the other push buttons SET ENTER or DWN For additional...

Page 6: ...6 HPT724 Installation Document P N 52765 A 1 25 06 Customer Event Log Event Relay Day Block Holiday Dates Event Type ...

Reviews: