WIRING
Humidifier 69-2413EF—09
21
Honeywell has already programmed this control to work properly in most applications. However, you can adjust
the advanced settings by following the steps below.
Press
p
or
q
to change settings.
Press
NEXT
to advance to the next function.
Press
DONE
to exit and save settings.
Function Number
Setting
Displayed
Description
1
System Type
1
Humidifier
2
Dehumidifier
4
Control Mode
Automatic Mode is Default when Outdoor Sensor Detected
Manual Mode is Default when NO Outdoor Sensor Detected
1
Automatic
2
Manual
5
Automatic Mode RH% (Hum)
This is the humidity setpoint (RH%) the control will operate to.
The homeowner does not change this and will only need to set
the appropriate window protection setting.
Range: 20%-60%
Default = 35%
11
Automatic Mode Humidity Boost
Increases Preset RH% (#5) when user sets window protection
to 11.
0
OFF
5%
5%
10%
10%
17
Automatic Mode High Temp Shut-Off
Turns humidifier OFF when Outdoor Temperature is greater
than selected setting.
Range: 40° - 90°
0 = OFF
Default = 65°
19
High Hum Limit
Range: 10% - 90%
Default = 60%
20
Low Hum Limit
Range: 10% - 90%
Default = 10%
21
High Dehum Limit
Range: 10% - 90%
Default = 80%
23
Low Dehum Limit
Range: 10% - 90%
Default = 40%
25
Dehumidifier Compressor Lockout
0 - 5 Minutes
Default = 0 Minutes (OFF)
30
Humidity Sensing Calibration
This feature will offset the sensed indoor humidity.
Range: -9% to +9%
Default = 0
(Displays Actual RH%)
35
Outdoor Temperature Sensor Calibration
This feature will offset the sensed outdoor temperature if
needed.
Range: -9° to +9°
Default = 0
(Displays Actual
Outdoor Temp)
To begin,
press and hold
the
p
and
LIGHT
buttons until
the display changes.
1
1
Done
Next
M29387A
Advanced Installer Setup