background image

Appendix

51

Distribution limitation

  max. 5 (8) zones per storey controller

  max. 3 connections per zone

  max. 24 actuators per storey controller

  only one type of thermal actuator per storey controller (normally

open or normally closed)

  either heating loops or radiators for each storey controller (floor

heating)

  max. 8 zones for heating/cooling, as a room for heating and a room

for cooling must be assigned for each zone

Summary of Contents for HCE 60

Page 1: ...Storey Controller HCE 60 Installation and Operation ...

Page 2: ......

Page 3: ...an 5 Determining temperature zones 5 Filling out zoning plan 6 Installation 10 Wall installation 11 DIN rail installation 12 Installing Hometronic components 12 Configuration and electrical connection 13 Opening housing 14 Cabling connections 16 Start up 26 Preparing for start up 26 LED indicators on storey controller 28 Operating modes of storey controller 29 Buttons 30 Cooling function 30 ...

Page 4: ...37 Assigning room names for cooling function 37 Canceling assignment 38 Deleting assignment of a room name at the Hometronic Manager 39 Saving settings on Hometronic Manager 40 Checking configuration 40 Checking wireless transmission 41 Checking assignment of room names 42 Displaying faults 42 Completing start up 43 Resetting storey controller to state of delivery 44 Appendix 45 Glossary 45 Help w...

Page 5: ... Using this information the storey controller regulates the boiler feedback the pump relay and the thermal actuators see Page 48 Hometronic heating components It has a self learning controller fuzzy logic which automatically ad justs itself to the ambient conditions The desired room temperature is reached quickly and then maintained A sticker has been included on the back for a quick overview of t...

Page 6: ...d electrical connection Set the storey controller to the actuator type attach cables to the respective connections and connect components together Start up Assign setpoint adjusters and any room temperature sensors to the temperature zones Assign room names at the Hometronic Manager if necessary Assign the time program of the wireless setpoint adjuster HCU 30 to the temperature zones if necessary ...

Page 7: ...controller to 8 A maximum of 3 actuators can be connected in each zone Thus the total number of actuators which can be controlled by one storey controller is limited to 24 Determining temperature zones Caution Damage caused by equipment from other manufac turers The storey controller was designed for use with com ponents from Honeywell only Use only H 200 BG closed without current or H 200 BO open...

Page 8: ...8 24 1 16 48 2 24 72 3 The example at the end of this section shows zone divisions with corresponding zoning plan Filling out zoning plan Copy the sample zoning plan see Appendix Page 50 archive it Enter the type and installation location of the respective actuator in each temperature zone Assign a setpoint adjuster to each temperature zone Assign room names if necessary Hand over the zoning plan ...

Page 9: ...Creating a zoning plan 7 Example of zone divisions 1 2 etc Zone A Living room E Bedroom B Dining room F WC C Kitchen G Bathroom D Hall ...

Page 10: ...odule HCS 60 is required for this partitioning A total of 8 actuators are controlled by the storey controller Up to 8 temperature zones can be controlled by the additional module HCS 60 Planned temperature zones are generated in gray The room names for each temperature zone are entered at the Hometronic Manager ...

Page 11: ...CM 200 Heating loop 1 living room Living room Living Zone 1 Heating loop 2 living room Heating loop 3 living room Zone 2 Heating loop 1 dining room Dining room Dining Zone 3 Heating loop 1 kitchen Kitchen Kitchen Zone 4 Heating loop 1 bedroom Bedroom Bedroom Zone 5 Heating loop 1 WC WC WC Zone 6 Heating loop 1 bathroom Bathroom Bathroom Cooling optional ...

Page 12: ...ices Select another installation site if the wireless interfer ence cannot be rectified The storey controller was designed for installation in a distributor box If insufficient space is available select an area where the storey controller can communicate with the setpoint adjusters wirelessly without interference and which is protected from moisture and water The storey controller can be installed...

Page 13: ...imensions of storey controller in mm 324 335 ø4 2 82 65 Note the 60 mm installation height of the storey controller If the storey controller is installed at a severe angle the trans former must be on top to allow for ventilation Mark drill and insert plugs into fastening holes Screw on the storey controller ...

Page 14: ...DIN rail installation Place housing on the DIN rail from below 1 Press housing upward and snap into place 2 Installing Hometronic components Install components as described in the accompanying installation instructions ...

Page 15: ...cabled Touching a live contact causes critical injuries Work may only be carried out by authorized special ized personnel Unplug the power plug before opening the housing Caution Damage to exposed components The electronic components of the storey controller and plug in module can be damaged by static electricity discharge Do not touch such components Touch an grounded piece of metal to discharge ...

Page 16: ...the front 1 Push both snap locks in ward 2 Remove the housing cover from above 3 Plugging in the expansion module optional The expansion module HCS 60 expands the number of possible temperature zones per storey controller from 5 to 8 Insert expansion module into the intended slot ...

Page 17: ... actuators which are closed with current are to be used 2 storey controllers with the respective suitable controller are required 1 Configuration switch O Open C Closed 2 Setpoint temperature of ceramic fuse type 230 V AC 2 5 A fast blowing 5 20 mm The actuators are protected by the ceramic fuse Check the type of actuator being used Set the switch according to the following table ...

Page 18: ...e types and lengths Cable designation Connection between sto rey contr HCE 60 and Max permis sible length JE LiYCY 2 2 0 8 Setpoint adjuster HCW 23 100 m CY 2 2 0 14 Setpoint adjuster HCW 23 100 m JE Y St Y 2 2 0 8 Setpoint adjuster HCW 23 100 m MCR pre regulator 100 m Pump relay HREL1 100 m 1 5 mm2 Thermal actuators H200 BO and H200 BG 100 m Prefabricated cable Thermal actuators H200 BO and H200 ...

Page 19: ... for expan sion module HCS 60 3 Antenna connector 4 Connector of actuator for zones 1 through 8 In general each zone can control up to 3 actuators 3 actuators can be connected for zone 1 and one each for zones 2 through 5 One connection for the expansion module is available for each of the zones 6 through 8 The prefabricated cable of the thermal actuators can be extended from 1 to 3 meters This ca...

Page 20: ...spe cialized personnel If more than 4 actuators are to be connected to the storey controller the cables of the actuator must be wired in a distribution box The storey controller can control up to 24 actuators However no more than 3 actuators may be connected in any one zone The prefabricated cable of the actuators can be extended from 1 to 3 meters This cable is available plug in ready as type HCV...

Page 21: ...l connection 19 Insert connector of actuator connection cables into the sockets of the respective zones Squeeze the cables into the stress relief clamp Break out the openings for the cables on the housing using a diagonal cutter ...

Page 22: ... 38 Use cables in accordance with the table on Page 16 Attach the connectors of the setpoint adjusters to the connector of the storey controller as shown in the following diagram 1 Setpoint adjuster 1 or heating cooling switchover contact 2 Setpoint adjuster 2 3 Zone 1 4 Zone 2 5 Bus not activated 6 Boiler feedback 7 Pump relay HREL 1 TW Temperature selector input RF Room sensor input Ground TW RF...

Page 23: ...00 MCR 40 and ZG 252 N Connect the inputs in accordance with the accompanying instruc tions Ground input on terminal 10 and temperature input on termi nal 5 of the HCE 60 With controller MCR 40 the temperature and ground inputs are lo cated at the following terminals MCR 40 Low voltage input Ground input TW Input 7 8 9 10 4 5 6 1 2 3 TW ...

Page 24: ...7 8 9 11 12 Depending on the design the temperature selector and ground inputs are found on different terminals of the controller MCR 200 Boiler feedback If control cables for heating boiler regression and for the pump relay are available Use cables in accordance with the table on Page 16 Connect boiler regression and pump relay to storey controller as shown in the following diagram ...

Page 25: ...nection 23 Connections of storey controller and pump relay A2 A1 1 2 HREL 1 1 2 3 4 5 6 7 8 9 10 11 12 RC PR Storey controller 1 1 2 3 4 5 6 7 8 9 10 11 12 RC PR Storey controller 2 1 2 3 4 5 6 7 8 9 10 11 12 RC PR Storey controller n ...

Page 26: ...ctrical connection 24 Inserting connectors Insert connectors into the connector strip of the storey controller Insert connector of antenna cable into the antenna socket of the storey controller 1 1 2 2 3 4 5 6 7 8 9 1 0 1 1 ...

Page 27: ...stalled outside metal housings e g switch cabinets 4 Do not lengthen antenna cable Install antenna at a suit able location near the sto rey controller 3 Wireless connection to setpoint adjuster 2 must be en sured Insert antenna cable into the antenna socket of the storey controller Closing housing of storey controller Place cover on housing Snap left and right snap locks into place Tighten screw o...

Page 28: ... HCU 30 if applicable are assigned to the temperature zones of the storey controller A room name is defined for each temperature zone at the Hometronic Manager Preparing for start up Starting up setpoint adjuster HCW 22 Set adjustment dial to posi tion 0 Open housing Press snap lock 1 and remove housing cover 2 ...

Page 29: ...1 Send button required for start up Starting up storey controller Plug in power plug The mains voltage LED illuminates Starting up setpoint adjuster HCU 30 See instructions of setpoint adjuster HCU 30 Starting up room temperature sensor HCF 22 See instructions of room temperature sensor HCF 22 ...

Page 30: ...emperature zones Meaning of the 3 left hand LEDs green Illumi nating Normal mode red Illumi nating Group fault Flashing Fault display yellow Illumi nating Installation mode Flashing Device display LEDs 1 through 8 are assigned to the temperature zones and can illuminate green yellow and red The meaning of the color depends on the selected operating mode ...

Page 31: ...emperature zones Refer to section Displaying faults on Page 42 Installation mode In installation mode temperature zones are assigned to the set point adjusters and the Hometronic Manager Refer to section Assigning zones and issuing room names on Page 32 Device display The device display informs you of the configuration of your Home tronic system i e the assignment of setpoint adjusters to a tem pe...

Page 32: ...troller to the fault display Refer to section Displaying faults on Page 42 Installation button Pressing the Installation but ton switches the storey con troller to installation mode or to the device display Cooling function If the HCE 60 is used as a cooling regulator this function must be activated during installation ...

Page 33: ...tive LED illuminating constantly Heating active Change setting if necessary Press the Installation button The yellow LED switches between flashing and constant illumi nation In the heating cooling operating mode LEDs 1 through 8 of the tem perature zones indicate whether the temperature zones are heated or cooled Red Heating Green Cooling The display is cleared automatically after 30 seconds and t...

Page 34: ...nsor HCF 22 is combined with a remote setpoint adjuster HCW 22 i e assigned to the same zone first assign the remote setpoint adjuster and then the room temperature sensor If the installation button at the storey controller is not pressed for longer than 4 minutes the storey controller re turns automatically to normal mode Example Assigning an HCW 22 setpoint adjuster to zone 1 In the following ex...

Page 35: ...from the setpoint adjuster To assign the setpoint adjuster to another zone press the Installation button until the LED of the desired zone flashes red Press the Send button of the setpoint adjuster The setpoint adjuster is assigned to zone 1 The LED of the selected zone lights continuously red If no Hometronic Manager is installed the storey controller operates with a basic value of 20 C For infor...

Page 36: ...al from the Hometronic Manager The Hometronic Manager is in auto matic mode The display on the Hometronic Man ager shows the standard display for example HOMETRONIC WE 29 10 1999 11 15 No Lifestyle active LIVING 20 0 C Press the Input button The following text is displayed MENU SET DATE TIME ACTIVATE LIFESTYLE LIVING 20 0 C Turn the Input button to the right until Menu is selected MENU SET DATE TI...

Page 37: ... FUNCTION EXTENSION SENSOR FUNCTION Select the Installation submenu and press the Input button The following text is displayed HEATING COOLING SHUTTERS DEVICES LIGHT SENSOR Select the Heating submenu and press the Input button A list of the room names possible temperature zones appears in the display LIVING DINING KITCHEN BEDROOM Turn the Input button until Living is selected Press the Input butto...

Page 38: ...the LED extinguishes The storey controller is back in normal mode If the installation button is not pressed for longer than 4 min utes the storey controller changes to normal mode The assigned temperature zones remain stored in the storey controller even after a power failure Assigning wireless setpoint adjuster HCU 30 to a temperature zone For information on assigning the wireless setpoint adjust...

Page 39: ...nction If the cooling function is activated see Page 30 2 room names can be assigned for each temperature zone Example Heating living Cooling living The time programs and setpoint values are activated by the heating or cooling input signal Switch closed terminals 1 and 3 Cooling active Switch open terminals 1 and 3 Heating active Assigning 2 room names to a temperature zone Enter room name in zoni...

Page 40: ...are assigned to all tem perature zones Canceling assignment Canceling assignment of setpoint adjuster to a temperature zone Press and hold Installation button at least 2 seconds The LED illuminates The LED of zone 1 flashes red Press Installation button repeatedly until the LED of the zone to be removed flashes red Press Fault button until the LED of the temperature zone goes out The assignment of...

Page 41: ...e LED of the temperature zone goes out The assignment of the room name or the time program to the tem perature zone is canceled Deleting assignment of a room name at the Hometronic Manager Change to submenu Settings as described on Page 34 The following text is displayed INSTALLATION DE INSTALLATION FUNCTION EXTENSION SENSOR FUNCTION Select the De Installation submenu and press the Input button Th...

Page 42: ...TCHEN BEDROOM The assignment is deleted and can be reassigned Saving settings on Hometronic Manager Before start up is completed the settings at the Hometronic Manager must be saved For information on saving settings refer to the operating instructions of the Hometronic Manager in the chapter entitled Adaptation Checking configuration Press Installation button briefly The LED flashes yellow The st...

Page 43: ...tivated the following information can be called up Press Installation button briefly again The colors of LEDs 1 through 8 indicate the assignment of room names to the temperature zones Green Room name for cooling assigned Red Room name for heating assigned Orange Room name for heating cooling assigned Checking wireless transmission Press Send button on setpoint adjuster LEDs 1 through 8 of the ass...

Page 44: ...EDs 1 through 8 of the assigned zone flash up to three times The assignment is correct The storey controller exits the device display after approx 60 seconds and returns to normal mode Displaying faults If the LED illuminates a fault is present in at least one tempera ture zone Press Fault button The LED flashes red The storey controller switches to the fault display ...

Page 45: ...oint adjuster HCU 30 Orange No connection to setpoint adjuster and Hometronic Man ager The storey controller exits the fault display after approx 60 seconds and returns to normal mode Completing start up Closing setpoint adjuster Replace cover and snap in both snap locks Handing over zoning plan Hand over the completed zoning plan and the installation instructions to the customer Both documents ar...

Page 46: ...uminate The LED of zone 1 is red Press the installation button briefly The LED of Zone 1 is extinguished The LED of zone 2 is illumi nated Press the fault button Pull the connector of the storey controller again and plug it in again The storey controller is reset to the state of delivery Note to installer After the storey controller has been started up you should inform your customer about the Hom...

Page 47: ...etects the room temperature and transfers it to the storey controller Setpoint adjuster Senses the actual temperature and changes the setpoint tem perature Installed in a user friendly location in each zone Setpoint temperature Room temperature which is to be reached Thermal actuator Opens and closes a heating circuit Controlled by the storey controller Time program Defined combination of setpoint...

Page 48: ...hether batteries in setpoint ad juster are inserted properly Check wireless connection LEDs 1 through 8 of the zones do not illuminate green con tinuously during start up The room name cannot be assigned Check whether Hometronic Manager is installed Check whether or not a room name is assigned to zone Reassign zone if applicable Not all rooms are warmed cooled Check heating and inlet temperature C...

Page 49: ...i nates after start up A fault is present in one of the temperature zones See Page 42 Check wireless connection Check cabling for cable break Check whether zone is assigned correctly Check batteries of the storey controller and wireless setpoint adjuster Room controlled incorrectly Check whether adjusting ring of setpoint adjuster is at position 0 Check whether adjusting ring can be turned between...

Page 50: ...Appendix 48 ...

Page 51: ...temperatures C Room temperature sensor for storey controller HCF 22 Transmits room temperature information to storey controller D Hometronic Manager Central operating unit of the house automation system E Setpoint adjuster HCW 23 wired Regulates setpoint temperature for each temperature zone via adjustment dial F Storey controller HCE 60 Controls actuators of floor heaters radiators communicates w...

Page 52: ...Appendix 50 Zoning plan Zone Actuator type location Setpoint adjuster location Room name 1 Heating Cooling 2 Heating Cooling 3 Heating Cooling 4 Heating Cooling 5 Heating Cooling Cooling optional ...

Page 53: ...4 actuators per storey controller only one type of thermal actuator per storey controller normally open or normally closed either heating loops or radiators for each storey controller floor heating max 8 zones for heating cooling as a room for heating and a room for cooling must be assigned for each zone ...

Page 54: ...Notes 52 Notes ...

Page 55: ......

Page 56: ...D 71101 Schönaich Tel 01801 466390 The right is reserved to make modifications This company is certificated to This document is definitive for the enclosed product and replaces all previous publi cations No 7157521 EN1H 0134 GE51R1102 ...

Reviews: