HE360 HUMIDIFIER AND INSTALLATION KIT

3

69-1646EF—01

1.

Turn off power to the air handing system at the cir-
cuit breaker.

2.

Draw a level line on the plenum in the location 
chosen for the humidifier. (Leveling assures opti-
mal humidifier performance.)

3. Locate the template (form number 69-1651 

included in the box).

4. Tape the template in position and trace around 

the template. 

5. Remove the template and carefully cut the rect-

angular opening.

6.

Disassemble the humidifier; remove the cover and 
take out the humidifier pad assembly. See Fig. 3.

Fig. 3. Disassembling humidifier.

7.

Position the securing clips as shown in Fig. 4.

Fig. 4. Position securing clips.

8.

Make sure the humidifier housing is level, then 
position it in the opening so the plastic tabs are in 
place on the 

lower sheet metal edge

 of the open-

ing. Use pliers, as necessary, to flatten cut edges. 
See Fig. 5.

9.

Push in securing clips until completely seated.

10.

Drill holes and install the three sheet metal screws 
on the top of the humidifier housing. Secure the 
housing with the three remaining screws. 

Fig. 5. Installing humidifier on duct.

11.

Reinstall the humidifier pad assembly in the humid-
ifier housing.

IMPORTANT

Be sure to reconnect the water feed tube and 
ensure that the tube is not pinched or kinked.

12.

Hinge the cover in place and secure with the 
thumbscrew located at the bottom of the cover.

Connecting the Plumbing

Use hot or cold water and either hard or softened water 
in the humidifier.

1.

Shut off the water.

CAUTION

Chemical Hazard. 
Can cause personal injury or equipment 
damage.

Do not use any line connected to an air 
conditioner. 
Do not use gas line.

2.

Use the self-piercing saddle valve (included) to tap 
into the water supply line at the location selected. 
See Fig. 6. If tapping into galvanized pipe, drain 
line and pre-drill 3/17 in. tap for saddle valve.

NOTE: The saddle valve is not designed to regulate 

water flow. The valve is either open or closed.

IMPORTANT

To prevent debris from clogging the solenoid in-
line filter, be sure to install the saddle valve han-
dle pointing toward the ceiling.

M12809

COVER 
ASSEMBLY

HUMIDIFIER 
PAD ASSEMBLY

FEED TUBE NOZZLE

WATER 
DISTRIBUTION TRAY

HUMIDIFIER
HOUSING

THUMB 
SCREW

M12813

CLIP

CLIP

DUCT

LEVEL

SHEET METAL
SCREWS (4)

PLASTIC
TABS (2)

DRAIN TUBING

M20204

OPENING

TO AIR DUCT

69-1646E-01_A.fm  Page 3  Tuesday, June 9, 2009  1:13 PM

Summary of Contents for H8908

Page 1: ... the installation Required Accessories Included Required Tools Tools required for installation include Tin snip Screwdriver Adjustable or open end wrench Drill punch or awl Level Determining Best Location for Humidifier CAUTION Temperature and Static Pressure Hazard Can cause property or equipment damage Locate humidifier where ambient temperature is between 32 F 0 C and 160 F 71 C Do not install ...

Page 2: ...ail without affecting the smooth flow of air in the duct Airflow at the location can be vertical up or down or horizontal IMPORTANT Mounting the S688 in warm air supply duct can reduce the sail life Mount the switch at least 6 in 152 mm upstream from an elbow or junction and at least 15 in 381 mm downstream from an elbow or junction Locate the switch on the opposite side of the duct from the air e...

Page 3: ...ing humidifier on duct 11 Reinstall the humidifier pad assembly in the humid ifier housing IMPORTANT Be sure to reconnect the water feed tube and ensure that the tube is not pinched or kinked 12 Hinge the cover in place and secure with the thumbscrew located at the bottom of the cover Connecting the Plumbing Use hot or cold water and either hard or softened water in the humidifier 1 Shut off the w...

Page 4: ...tube to the humid ifier drain fitting and run to the floor drain see Fig 8 a Slide the drain clamp over the tubing b Push the tubing over the drain nipple on the humidifier c Hand tighten the clamp around the tubing to secure the humidifier drain d Fasten the drain tubing can use duct tape along the route to prevent movement and ensure downward slope for correct drainage NOTE Cut tubing to correct...

Page 5: ... Off position the sail should point into the direction of airflow as shown in Fig 11 Fig 11 Inserting sail switch in direction of airflow 6 Secure the switch by using the sheet metal screws provided 7 After wiring snap on the cover Installing the Humidistat Installing on Mounting Duct 1 Apply the template to the duct location chosen for the humidistat Make sure the template is level before drillin...

Page 6: ... white con ductors to the Com and NO sail switch terminals NC terminal is not used TESTING HUMIDIFIER OPERATION Checklist q Humidifier is level q Control wiring was reviewed using circuit diagram q Humidifier is plugged in q Feed line has no kinks q Drain line slopes continuously down and ends at floor drain q Water hose inside humidifier is connected to PerfectFlow water distribution tray After i...

Page 7: ...t can accumulate moisture on your windows NOTE If these activities persist for more than a few hours set the humidity control to the lowest set ting to turn off the humidifier If the condition does not improve ventilate your home to remove the moisture MAINTAINING YOUR HUMIDIFIER A regular maintenance program prolongs the life of your humidifier and makes your home more comfortable The frequency o...

Page 8: ... the water feed tube is placed in the guide slots 15 Replace the humidifier cover 16 Verify the humidifier operation by following the steps in the Checking Your Humidifier for Correct Operation section CHECKING YOUR HUMIDIFIER FOR CORRECT OPERATION After winter startup or servicing use the following steps to check your humidifier operation 1 Turn on the humidifier power and water supply 2 Turn the...

Page 9: ...Verify plumbing connections Check for kinks Saddle valve Verify that needle pierces water line and then backs out needle to open valve Humidifier Remove cover and verify that water flows into distribution tray Drain tubing Verify no obstructions Low humidity Furnace blower not operating Reset circuit breaker or check for blown fuse Check that the furnace power is on Check all external wiring conne...

Page 10: ...WELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF ANY WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PRODUCT Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation may not apply to you THIS WARRANTY IS THE ONLY EXPRESS WAR...

Page 11: ...HE360 HUMIDIFIER AND INSTALLATION KIT 11 69 1646EF 01 69 1646E 01_A fm Page 11 Tuesday June 9 2009 1 13 PM ...

Page 12: ... U S A on recycled paper containing at least 10 post consumer paper fibers Automation and Control Solutions Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 69 1646E 01_A fm Page 12 Tuesday June 9 2009 1 13 PM ...

Page 13: ...HE360 et un humidistat H8908 de Honeywell ainsi que tous les accessoires nécessaires à l installation INSTALLATION Avant d installer ce produit Il est important d identifier tous les accessoires nécessaires fournis énumérés au Tableau 1 et d avoir sous la main les bons outils Accessoires nécessaires fournis Tableau 1 Accessoires nécessaires Outils nécessaires Les outils nécessaires à l installatio...

Page 14: ...ficateur S il n y a pas de siphon à proximité il est préférable d installer l humidificateur central à tambour ou à disque de Honeywell S assurer que le tuyau de vidange de 3 1 m 10 pi est suffisamment long et permet de raccorder le tuyau de vidange de l humidificateur au siphon de sol Choix de l emplacement de l interrupteur à ailette Choisir un endroit dans la gaine de reprise d air froid où l i...

Page 15: ...igneusement une ouverture rectangulaire 6 Démonter l humidificateur enlever le couvercle et retirer l ensemble écran évaporateur Voir la Fig 3 Fig 3 Démontage de l humidificateur 7 Placer les pinces de fixation comme l indique la Fig 4 Fig 4 Position des pinces de fixation 8 S assurer que le boîtier de l humidificateur est de niveau puis le placer de manière que les attaches de plastique soient su...

Page 16: ...rémité du tuyau c Glisser l anneau de compression en plastique sur le tuyau Mettre de côté l anneau de com pression en cuivre fourni avec le robinet REMARQUE Pour empêcher les fuites avec des tuyaux en plastique utiliser des anneaux en plastique Delrin N utiliser des anneaux en cuivre qu avec des tuyaux en cuivre d Insérer le tuyau dans le raccord de l électro vanne et serrer l écrou de compressio...

Page 17: ...p Enlever le support attaché au support marqué Down Courant d air horizontal Enlever les deux ressorts 1 Placer le gabarit fourni avec l interrupteur à ailette à l endroit choisi REMARQUE S assurer que la flèche indiquant le sens de la circulation de l air pointe dans la bonne direction a Dans le cas d un montage horizontal placer le long côté horizontalement à l aide d un niveau b Dans le cas d u...

Page 18: ...ISE EN GARDE Risque de choc électrique Peut causer des blessures ou des dommages matériels Couper l alimentation électrique avant de faire l installation ou l entretien IMPORTANT Tout le câblage doit être conforme aux codes et règlements locaux Câbler l électrovanne de l humidificateur l interrupteur à ailette l humidistat et le transformateur Voir la Fig 13 Fig 13 Câblage des appareils 1 Passer l...

Page 19: ...l appareil de chauffage passe sur l écran évaporateur de l humidificateur et capte l air humide pour le faire circuler dans la maison L air humidifié est plus chaud et il assure un meilleur confort Le point de consigne du thermostat peut donc être abaissé ce qui permet de diminuer les coûts de chauffage Avec un humidificateur la maison devient confortable et éconergétique Réglage de l humidificate...

Page 20: ...e tuyau de vidange avec de l eau sous pression eau du robinet pour le nettoyer 11 Replacer le tuyau de vidange sur le raccord de vidange 12 Replacer le gicleur sur le plateau 13 S assurer que la partie marquée de l écran évapo rateur est orientée vers le haut Remettre le pla teau sur le cadre 14 Mettre l ensemble écran évaporateur d humidifica teur dans le boîtier de l humidificateur en appuyant j...

Page 21: ...ectrovanne Tuyauterie Vérifier les raccords des tuyaux Vérifier si les tuyaux sont pincés Robinet vanne à étrier Vérifier si le pointeau perce la ligne d eau et revient en position pour ouvrir le robinet vanne Humidificateur Enlever le couvercle et vérifier si l eau s écoule dans le plateau de distribution Tuyau de vidange Vérifier s il y a blocage Faible humidité Le ventilateur de l appareil de c...

Page 22: ...placer le produit conformément aux modalités susmentionnées HONEYWELL N ASSUME AUCUNE RESPONSABILITÉ POUR QUELQUE DOMMAGE INDIRECT QUE CE SOIT RÉSULTANT D UNE VIOLATION QUELCONQUE D UNE GARANTIE EXPRESSE OU TACITE APPLICABLE AU PRÉSENT PRODUIT Certains territoires et provinces ne permettent pas l exclusion ou la restriction des dommages indirects et par conséquent la présente restriction peut ne p...

Page 23: ...HUMIDIFICATEURS HE360 ET TROUSSE D INSTALLATION 11 69 1646EF 01 69 1646F 01_A fm Page 11 Wednesday June 10 2009 2 22 PM ...

Page 24: ...09 www honeywell com yourhome HUMIDIFICATEURS HE360 ET TROUSSE D INSTALLATION Solutions de régulation et d automatisation Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 69 1646F 01_A fm Page 12 Wednesday June 10 2009 2 22 PM ...

Reviews: