H-SERIES GREEN CLASS NET METER
43
62-0424-02
41043
2
Apparent power, phase B
kVA
R
41045
2
Apparent power, phase C
kVA
R
41047
2
Power factor, phase A
% PF
R
41049
2
Power factor, phase B
% PF
R
41051
2
Power factor, phase C
% PF
R
41053
2
Current, phase A
Amps
R
41055
2
Current, phase B
Amps
R
41057
2
Current, phase C
Amps
R
41059
2
Voltage, line to neutral, phase A-N
Volts-N
R
41061
2
Voltage, line to neutral, phase B-N
Volts-N
R
41063
2
Voltage, line to neutral, phase C-N
Volts-N
R
41065
2
Voltage, line to line, phase A-B
Volts-L
R
41067
2
Voltage, line to line, phase B-C
Volts-L
R
41069
2
Voltage, line to line, phase C-A
Volts-L
R
41071
2
Phase angle, phase A
Degree
R
41073
2
Phase angle, phase B
Degree
R
41075
2
Phase angle, phase C
Degree
R
41077
2
Reserved
41079
2
Reserved
41081
2
Reserved
41083*** 2
External Input 1
Pulse
R/W
41085*** 2
External Input 2
Pulse
R/W
**
To clear single meter kWh/kVARh, set multiple points at 41001 for 8 points with data set to
0000 0000 0000 0000 0000 0000 0000 0000. Jumper J6 m
***
External inputs are standard on Class Net Meters and optional on Class 3400 meters (Part of
Expanded Feature Package).To clear Auxiliary Inputs, set multiple points at 41083 or 41085 for
2 points with data set to 0000 0000. Jumper J6 must be closed.
BACnet Object Descriptors:
ID
BACnet
Object
Description
Units
BACnet
Property
Green
Net
Meters
1
Analog Input Energy delivered
kWh
Present Value R
2
Analog Input Energy received
kWh
Present Value R
3
Analog Input Reactive energy delivered
kVARh Present Value R
Modbus Float Registers: